Plan Review Details - Permit 07060823
Plan Review Stops For Permit 07060823
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-04 Cont ID  
Sent By rmcdouga Date 2008-03-04 Time 12:39 Rev Time 0.00
Received By rmcdouga Date 2008-03-04 Time 12:39 Sent To  
Notes
2008-03-04 12:40:19PROCESS PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-02-26 Cont ID  
Sent By rmcdouga Date 2008-02-26 Time 16:20 Rev Time 0.00
Received By rmcdouga Date 2008-02-26 Time 16:20 Sent To  
Notes
2008-02-26 16:19:58PERMIT STATUS WILL BE CHANGED TO PASS WHEN IMPACT FEES
 ARE PAID AND COPY OF PAID RECEIPT SUBMITTED AND COPY OF
 RE-RECORDED NOC IS SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-11-19 Cont ID  
Sent By rmcdouga Date 2007-11-19 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2007-11-19 Time 10:25 Sent To  
Notes
2007-11-19 10:25:312004 FBC W/2006 SUPPLEMENT
 NEW SINGLE FAMILY DWELLING
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT TWO COPIES OF THE ENERGY CALCULATIONS AND
 COMPLY WITH MECHANICAL REVIEW COMMENTS.
  
 PLEASE REVIEW THE STORM PANEL PRODUCT APPROVALS AND THE
 INSTALLATION SCHEDULE FOR ACCURACY.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-25 Cont ID  
Sent By rmcdouga Date 2007-09-25 Time 16:30 Rev Time 0.00
Received By rmcdouga Date 2007-09-25 Time 16:30 Sent To  
Notes
2007-09-25 16:57:592004 FBC W/2006 SUPPLEMENT
 NEW SINGLE FAMILY DWELLING
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT TWO COPIES OF THE ENERGY CALCULATIONS AND
 COMPLY WITH MECHANICAL REVIEW COMMENTS.
  
 4) SOME OF THE INFORMATION LISTED ON THE STORM PANEL
 SCHEDULE IS INCORRECT. THE GLASS SEPARATION IS REQUIRED
 TO BE A MINIMUM OF 2-3/4" PER TABLE 2 ON SHEET 6 OF THE
 NOA. THE SPAN IS THE LENGTH OF THE PANELS WHICH WILL BE
 WIDER THAN THE OPENING PLUS THE EDGE DISTANCE AT BOTH
 SIDES OF THE OPENING. FOR EXAMPLE IF THE SHUTTER IS
 INSTALLED VERTICALLY AND THE OPENING HEIGHT IS 63" WITH
 A 2" EDGE DISTANCE, THEN THE SPAN WOULD HAVE TO BE AT
 LEAST 67" FOR C TRACK INSTALLATION. PLEASE REVIEW THE
 NOA.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-16 Cont ID  
Sent By rmcdouga Date 2007-07-16 Time 07:10 Rev Time 0.00
Received By rmcdouga Date 2007-07-16 Time 07:10 Sent To  
Notes
2007-07-16 08:30:39DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT A DRAINAGE PLAN SHOWING COMPLIANCE WITH FBC R
 401.3. SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM
 SEWER CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION
 SO AS NOT TO CREATE A HAZARD. LOTS SHALL BE GRADED SO
 AS TO DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS.
 THE GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A
 MINIMUM OF 6 INCHES WITHIN THE FIRST 10 FEET.
  
 4) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE
 SIGNED BY THE OWNER/ AGENT PER FBC CHAPTER 13.
  
 5) SHOW COMLIANCE WITH FBC R 309.1 AND 309.2 FOR
 OPENING PROTECTION (DOOR REQUIREMENTS) AND GARAGE
 SEPARATION (WALL REQUIREMENTS).
  
 6) ON SHEET 3 THE EDITION OF SOME OF THE STANDARDS THAT
 WERE SPECIFIED ARE INCORRECT. IN ORDER TO COMPLY WITH
 THE EDITION OF THE STANDARDS REFERENCED IN THE 2004
 FBC, PLEASE UPDATE TO ACI 530-02/ ASCE 7-02 AND TMS
 402-02.
  
 7) REVISE THE ROOF SHEATHING NAILING SCHEDULE ON SHEET
 4. THE CORNERS OF HIP ROOFS ARE ALSO ZONE 3. SEE
 DIAGRAM FBC R301.2(8).R 803.2.3.1 REQUIRES 8D RING
 SHANK NAILS FOR ALL ROOF ZONES.
  
 8) TWO COPIES OF ALL PRODUCT APPROVALS ARE REQUIRED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATE APPROVAL, BUT
 HAS A MIAMI-DADE NOA, THE NOA IS ACCEPTABLE BY ITSELF.
  
 9) THE WINDOW SCHEDULE ON SHEET 2 HAS WINDOWS LISTED
 THAT ARE NOT USED IN THIS PROJECT. REVISE THE SCHEDULES
 TO ONLY LIST INFORMATION THAT PERTAINS TO THIS
 PROJECT.
  
 10) SUBMIT PRODUCT APPROVALS FOR THE FOLLOWING:
 - SINGLE HUNG WINDOWS
 - ARCHED FIXED GLASS WINDOWS
  
 11) THE PRODUCT APPROVAL FOR THE GAF SHINGLES HAVE BEEN
 REVISED. SUBMIT THE NEW STATE COVERSHEET AND THE NEW
 NOA # 05-1115.08.
  
 12) THE PRODUCT APPROVAL SUBMITTED FOR THE MASONITE
 DOOR, FL 19 IS NO LONGER VALID.
  
 13) SUBMIT PRODUCT APPROVALS FOR THE OVERHEAD GARAGE
 DOORS.
  
 14) SUBMIT AN INSTALLATION SCHEDULE FOR THE STORM
 PANELS. SPECIFY THE CONNECTION/MOUNT TYPE, THE ANCHOR
 TYPES, THE ANCHOR SPACINGS, ETC.SEE ATTACHED.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-08-22 Cont ID  
Sent By btrobaug Date 2008-08-22 Time 11:45 Rev Time 0.00
Received By btrobaug Date 2008-08-22 Time 11:45 Sent To PC
Notes
2008-08-22 11:46:06 
  
 REVISION FOR SERVICE L9OCATION./WRT.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2008-08-08 Cont ID  
Sent By dpalmer Date 2008-08-08 Time 10:00 Rev Time 0.00
Received By dpalmer Date 2008-08-08 Time 10:00 Sent To M
Notes
2008-08-08 10:00:43**DENIEDREVIEW**
  
  
  
 1) NOTE:PLEASE SEE THAT PLANS WERE SUBMITTED FOR
 *RE-STAMP ONLY* FOR INSPECTIONS YET THERE ARE REVISIONS
 NOW HAND DRAWN ON PAGES.
 PLANS NOW SHOW ELECTRICAL PANEL IN TWO LOCATIONS.
 PLANS NOW SHOW METER IN TWO LOCATIONS.
  
 ** IF PLANS ARE BEING REVISED PLEASE HAVE THE DESIGNER
 OF RECORD REVISE PLANS, REPRINT SHEETS WITH OUT HAND
 DRAWN CHANGES AND SUBMIT AS REVISIONS NOT AS A
 RE-STAMP.
 A RE-STAMP IS ONLY FOR PLANS WHICH ARE *EXACTLY* AS
 ALREADY ON FILE WITH NO CHANGES.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-07-30 Cont ID  
Sent By dpalmer Date 2008-07-30 Time 10:32 Rev Time 0.00
Received By dpalmer Date 2008-07-30 Time 10:32 Sent To M
Notes
2008-07-30 10:32:25PLANS ARE REQUIRED TO MEET MINIMUM SCALE PER FBC 106.1

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-02-15 Cont ID  
Sent By dpalmer Date 2008-02-15 Time 14:26 Rev Time 0.00
Received By dpalmer Date 2008-02-15 Time 14:26 Sent To M
Notes
2008-02-15 14:27:48REDLINED PLANS.
  
 VERIFY OCP ON CU AS OCP SEEMS HIGH.
  
 OWNER BUILDER MUST USE RESIDENCE FOR OWN USE AND
 OCCUPANCY PER FS 489.SIGNED AFFIDAVIT AS REQUIRED
 UNDER STATUTES.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-11-02 Cont ID  
Sent By dpalmer Date 2007-11-02 Time 12:11 Rev Time 0.00
Received By dpalmer Date 2007-11-02 Time 10:18 Sent To M
Notes
2007-11-02 12:11:26 
 ** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS
 INCLUDING NEW COMMENTS ARE STILL NEEDED TO BE
 ADDRESSED.
  
  
 1) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 AS THE
 DINING ROOM RECEPTACLES SHALL BE ON ONE OR MORE OF THE
 SMALL APPLIANCE CIRCUITS. IF MORE THAN THE TWO MINIMUM
 THEN PLEASE SEE THE ADDITIONAL VA IS 1500 VA FOR EACH.
 PANEL AND LOAD ONLY SHOWS 1.0 KVA.
  
  
 2) NOTE: PLEASE SEE THE PANEL SCHEDULE HAS NOW CHANGED
 THE AHU HEAT DOWN TO 5KW WHEN THE PREVIOUS HAD THE HEAT
 AS 10KW. THE PREVIOUS REVIEW GAVE A NOTICE TO 424.3B AS
 THE CIRCUIT WAS A SINGLE POLE 20AMP CIRCUIT. THERE WAS
 NO COMMENT ABOUT THE KW RATING TO BE CHANGED. PLEASE
 SEE THE LOAD CALCULATIONS STILL CONTAIN 10KW WHEN PANEL
 IS 5KW.
 PLEASE COORDINATE AND ADJUST. FBC 106.3.5.4, 106.1.2,
 NEC 310.16, 240.4 ETC
 ** PLEASE SEE THE OVER CURRENT PROTECTION AND CIRCUIT
 SIZE FOR THE 3-TON CONDENSING UNIT IS TOO HIGH. PLEASE
 KNOW THE MAXIMUM OVER CURRENT PROTECTION IS STATED IN
 THE NEC AND BY THE MANUFACTURE.
 110.3, 90.7, 422.11E(3)
  
 3) NOTE: PLEASE SEE PREVIOUS COMMENT WITH RESPECT TO
 THE OWNER BUILDER APPLYING FOR AN OWNER BUILDER PERMIT
 WHEN HOMESTEAD EXEMPTION IS LISTED ON MULTIPLE
 PROPERTIES. THIS WILL BE VERIFIED WITH THE BUILDING
 OFFICIAL AND LAW DEPARTMENT. CONTACT MAY BE MADE TO THE
 PROPERTY APPRAISER'S OFFICE TO VERIFY THE ALLOWANCE AS
 STATED IN FS 489.
  
 4) NOTE: PLEASE SEE THE SMOKE ALARMS ARE NOT CIRCUITED
 SO THE VERIFICATION OF THE REQUIRED ARC FAULT
 PROTECTION PER 210.12.
  
 5) NOTE: PLEASE SEE CODE AS LISTED FOR BATH CIRCUIT
 DOES NOT NEED TO BE ON PLANS. THIS IS SHOWN AS
 210.11-2-3, HOWEVER THE CORRECT CODE IS 210.11C3. THIS
 WOULD HAVE BEEN REDLINED IF THIS WAS THE ONLY ITEM.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-27 Cont ID  
Sent By dpalmer Date 2007-10-27 Time 08:37 Rev Time 0.00
Received By dpalmer Date 2007-10-27 Time 08:27 Sent To PC
Notes
2007-10-27 08:40:37 
  
 PERMIT FEE BALANCE AND RESUB FEES NOT PAID.
 NO REVIEWS TO BE DONE UNTIL FEES ARE PAID. PLANS HAVE
 BEEN PLACED OUT FRONT UNDER "L"ON HOLD.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-27 Cont ID  
Sent By dpalmer Date 2007-08-27 Time 18:05 Rev Time 0.00
Received By dpalmer Date 2007-08-27 Time 15:50 Sent To M
Notes
2007-08-27 18:05:55 
 *** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE THERE ARE STILL SOME COMMENTS FROM THE
 PREVIOUS REVIEW WHICH NEED TO BE ADDRESSED ALONG WITH
 SOME NEW COMMENTS BASED ON REVISIONS MADE TO PLANS AND
 INFORMATION WHICH COULD NOT BE REVIEWED PREVIOUSLY.
  
  
 1) NOTE:AS STATED ON THE PREVIOUS REVIEW:PLEASE SEE
 THE PERMIT IS BEING APPLIED AS OWNER/ BUILDER WHERE THE
 PALM BEACH COUNTY PROPERTY APPRAISER'S OFFICE ALREADY
 LIST THIS OWNER NOT ONLY ON SEVERAL OTHER PROPERTIES
 BUT ALSO WITH HOMESTEAD EXEMPTION LISTED ON MORE THEN
 ONE PROPERTY WHICH IS NOT PERMITTED UNDER FLORIDA LAW.
 PLEASE SEE THIS INFORMATION FOR MULTIPLE HOMESTEADS
 WILL BE FORWARDED TO THE PBCPA OFFICE.
 PLEASE SEE THAT IN ORDER TO PULL AN OWNER/BUILDER
 PERMIT YOU MUST MEET THE EXCEPTION UNDER FS 489. PLEASE
 KNOW THIS MAY AFFECT THE PERMIT AS APPLIED AND A
 CONTRACTOR MAY BE REQUIRED. INFORMATION MAY ALSO BE
 FORWARDED TO THE COUNTY AND STATE LICENSING BOARD FOR
 REVIEW.
  
 2) NOTE: PLEASESTILL CLARIFY THE MAINPANEL. THE
 PANEL DESCRIPTION STATES THE PANEL IS A NEMA 3R WHICH
 IS AN OUTDOOR PANEL, YET THE PLANS SHOW THIS PANEL
 INSIDE?
 PLEASE KNOW THAT QUOTING THE CODE ON PLANS IN LIEU OF
 SPECIFIC DETAIL IS NOT PERMITTED.
 230.70,230.71.
  
 3) NOTE: AS PREVIOUSLY NOTED:
 PLEASE INDICATE THE AIC RATINGS ON NEW RISER AS THE
 NOTED RATING ABOVE PANEL SCHEDULE MAY CHANGE ONCE THE
 RISER IS REVISED. 110.9
  
 4) NOTE: AS PREVIOUSLY NOTED:
 PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS THE LOADS
 FOR ALL SMALL APPLIANCE AND DINING ROOM CIRCUITS SHALL
 BE FIGURED INTO THE LOAD CALCULATIONS. PLEASE CLARIFY
 THE DINING ROOM/AREA.
 PLEASE SEE THE PLANS INDICATE 15AMP CIRCUIT FOR DINING
 WHICH IS NOT PERMITTED.
 PLEASE SEE THE PLANS INDICATE A SWITCHED RECEPTACLE IN
 THE DINING AREA ON THE LIGHTING CIRCUIT WHICH IS ALSO
 NOT PERMITTED.
 PLEASE ALSO SEE THE PANEL SCHEDULE IS SHOWING 15AMP OCP
 FOR THE SMALL APPLIANCE CIRCUITS WHICH IS NOT
 PERMITTED.
 PLEASE ADJUST THE LOAD CALCULATIONS.
 PLEASE ADJUST THE CIRCUITS.
 PLEASE ADJUST THE OVER CURRENT PROTECTION.
 ETC.
  
 5) NOTE: PLEASE SEE THE PLANS NEEDS TO SHOW ALL
 LOCATION AND IDENTIFY THE LOCATIONS OF THE CU
 DISCONNECT PER 440.11. QUOTING THE CODE IN LIEU OF
 SPECIFIC DESIGN OR DETAIL CAN NOT BE ACCEPTED.
 FBC 106.1.3, 106.1, 106.3.5.4
  
 6) NOTE: PLEASE VERIFY THE GDO/ GARAGE DOOR OPENER ON
 WITH THE OUTSIDE GFI RECEPTACLES.
 THIS WILL NOT BE PERMITTED AS THE LOAD ON GD OPENERS
 TYPICALLY IS LARGE ENOUGH ON THE HORSEPOWER RATING TO
 REQUIRE A DEDICATED CIRCUIT. EVEN THOUGH THE OUTSIDE
 GFI ARE GENERAL PURPOSE AND DO NOT CONTAIN ANY SPECIFIC
 LOAD AT THIS TIME, THESE ARE USED FOR LANDSCAPE
 LIGHTING, HOLIDAY LIGHTING, YARD EQUIPMENT ETC WHICH
 WOULD OVER LOAD THIS CIRCUIT.
 PLEASE ADJUST AND PROVIDE DEDICATE GDO CIRCUIT.
 430.248
  
 7) NOTE: PLEASE SHOW ALL ROOM AND AREA DESIGNATIONS ON
 PLANS. PLEASE BE SURE TO SHOW ALL OF THE CIRCUITS AS
 SOME ARE MISSING.
 FBC 106.1.2
  
 8) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS ON PANEL SCHEDULE.
 PLEASE SEE AS NO CIRCUIT IS SHOWN FOR THE SMOKE ALARMS,
 NEED TO VERY AFCI PROTECTION.
 PLEASE SEE THE PLANS ONLY SHOW AFCI PROTECTION FOR
 RECEPTACLES. THIS CHANGED IN THE 2002 CODE TO REQUIRE
 THE AFCI PROTECTION FOR ALL OUTLETS. AS REQUESTED IN
 THE PREVIOUS REVIEW, PLEASE SHOW THE REQUIRED
 PROTECTION FOR ALL REQUIRED CIRCUITS.
 210.12, 408.4
  
 9) NOTE: AS REQUESTED ON PREVIOUS REVIEW:
 PLANS ARE STILL NOT SIGNED, DATED OR SEAL AS REQUIRED
 BY A DESIGNER OF RECORD OR DESIGN PROFESSIONAL. FS
 481.229, 471.003, 489, ETC
 PLEASE SEE THE TITLE BLOCK INDICATES HOMES DESIGNED BY
 ETC HOWEVER NO LICENSE INFORMATION WAS STATED ON TILE
 BLOCKS FOR SAID FIRM. FAC 61G1-16.004, 61G15-23.002, FS
 481.219 AND 471.023.
 PLEASE SEE THE PLANS EVEN STATE * NOT VALID WITHOUT
 SEAL*.
  
 10) NOTE: PLEASE SEE 424.3B FOR MINIMUM OVER CURRENT
 PROTECTION REQUIRED FOR THE AHU> SHOWS 1-POLE 20AMP
 BREAKER AND #10AWG?? YET PLANS INDICATE 10KW HEAT.
  
 11) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE AS SOME COMMENTS ARE REPEATED.
  
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SHOWN OR
 SUBMITTED FOR REVIEW, THE REVIEW FOR CODE COMPLIANCE
 CAN ONLY BE BASED ON THE PLANS SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-27 Cont ID  
Sent By dpalmer Date 2007-06-27 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2007-06-27 Time 12:57 Sent To Z
Notes
2007-06-27 14:40:55 
  
 *** UNSAT ***
  
  
 1) NOTE: PLEASE SEE PLANS ARE MISSING THE FOLLOWING
 REQUIRED CODES TO BE STATED ON PLANS AND FOR DESIGN.
 PLEASE SEE THE FOLLOWING WHICH WAS ADOPTED AS OF
 DECEMBER 8TH, 2006.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE KNOW THE PLANS WILL BE ROUTED TO THE
 ADDRESSING REVIEWER AS THE PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE DOES NOT INDICATE AND ADDRESS, OUR
 SYSTEM SHOWS 1571 6TH ST AND THE PLANS DO NOT INDICATE
 ANY ADDRESS.
 PLEASE KNOW ONCE THE ADDRESS HAS BEEN DECIDED AND
 CORRECTED, PLEASE REVISED TITLE BLOCKS OF PLANS
 ACCORDINGLY.
 FAC61G1-16.004
  
 3) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK SHALL BE BASED ON THE FBC AND THE ADOPTED
 SUPPORTING DOCUMENTS. PLEASE SEE THE VALUE SHALL
 INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST
 ETC AS STATED IN THE FBC 108.3
 PLEASE SEE THIS INCLUDES EQUIPMENT, MATERIALS ETC EVEN
 IF OWNER SUPPLIED. PLEASE SEE THE VALUE WILL BE
 ADJUSTED.
  
 4) NOTE: PLEASE SEE THE PERMIT IS BEING APPLIED AS
 OWNER/ BUILDER WHERE THE PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE ALREADY LIST THIS OWNER NOT ONLY ON
 SEVERAL OTHER PROPERTIES BUT ALSO WITH HOMESTEAD
 EXEMPTION LISTED ON MORE THEN ONE PROPERTY WHICH IS NOT
 PERMITTED UNDER FLORIDA LAW. PLEASE SEE THIS
 INFORMATION FOR MULTIPLE HOMESTEADS WILL BE FORWARDED
 TO THE PBCPA OFFICE.
 PLEASE SEE THAT IN ORDER TO PULL AN OWNER/BUILDER
 PERMIT YOU MUST MEET THE EXCEPTION UNDER FS 489. PLEASE
 KNOW THIS MAY AFFECT THE PERMIT AS APPLIED AND A
 CONTRACTOR MAY BE REQUIRED. INFORMATION MAY ALSO BE
 FORWARDED TO THE COUNTY AND STATE LICENSING BOARD FOR
 REVIEW.
  
 5) NOTE: PLEASE CLARIFY THE MAIN DISCONNECT AS REQUIRED
 PER 230.70,230.71.
 PLEASE SEE THE RISER MENTIONS A MAIN @ PANEL HOWEVER AS
 THE LOCATION OF THE PANEL IS NOT SHOWN, IT CAN NOT BE
 DETERMINED AT THIS TIME IF CODE COMPLIANCE IS MET.
 PLEASE ALSO SEE NEXT COMMENT.
  
 6) NOTE: PLEASE SHOW THE LOCATION(S) OF ALL SERVICE
 EQUIPMENT AND PANEL(S).
 110.26,240.24,408.7 ETC
 FBC 106.3.5.4
  
 7) NOTE: PLEASE INDICATE THE AIC RATINGS ON NEW RISER
 AS THE NOTED RATING ABOVE PANEL SCHEDULE MAY CHANGE
 ONCE THE RISER IS REVISED. 110.9
  
 8) NOTE: PLEASE SEE MISSING THE RECEPTACLE FOR THE
 DISHWASHER AS THE PLANS ONLY APPEAR TO SHOW A COUNTER
 SPACE RECEPTACLE AND THE PANEL SCHEDULE DOES SHOW AS
 DISHWASHER CIRCUIT.
  
 9) NOTE: PLEASE SEE THE MISSING RECEPTACLE FOR THE
 MICROWAVE WHICH IS LISTED ON LOAD CALCULATIONS BUT NOT
 SHOWN ON PLANS.
 408.4, FBC 106.1.2, 106.3.5.4
  
 10) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS
 THE LOADS FOR ALL SMALL APPLIANCE AND DINING ROOM
 CIRCUITS SHALL BE FIGURED INTO THE LOAD CALCULATIONS.
 PLEASE CLARIFY THE DINING ROOM/AREA.
  
 11) NOTE: PLEASE SEE THE PLANS NEEDS TO SHOW ALL
 LOCATION AND IDENTIFY THE LOCATIONS OF THE AHU AND
 WATER HEATER.
 PLANS INDICATE A 220 RECEPTACLE FOR THE WATER HEATER
 WHICH IS NOT PERMITTED.422.30
 PLEASE SEE MISSING DISCONNECTS PER 440.11 AND 422.31
  
 12) NOTE: PLEASE SEE 422.13 UNDER THE 2005 NEC AS THE
 WATER HEATER NEEDS TO BE SHOWN AT 125%.
  
 13) NOTE: PLEASE SHOW DISCONNECT REQUIRED FOR THE CU.
 440.11
 FBC 106.3.5.4
  
 14) NOTE: PLEASE SEE THE PANEL SCHEDULE SHALL BE
 SPECIFIC FOR ALL CIRCUIT NUMBERS AND DESIGNATIONS ON
 EACH CIRCUIT SHALL BE SPECIFIC TO ALL ROOMS AND AREAS
 IN WHICH THEY FEED.
 PLEASE PLACE THE ROOM AND AREA DESIGNATIONS ON PLANS
 FOR COORDINATION OF CIRCUITS REQUIRED.
 LISTING THE NUMERICAL DESIGNATIONS AS SHOWN IS NOT
 ACCEPTABLE AND LISTING THE GENERAL LTS AND RECEPTS MAY
 NOT BE USED. PLEASE SEE THE FOLLOWING TEXT WHICH HAS
 BEEN EXTRACTED DIRECTLY FROM THE NEC IN 408.4. *SECTION
 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE THAT THE
 IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 15) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS ON PANEL SCHEDULE. PLEASE SEE THE PANEL
 SCHEDULE ONLY INDICATES ONE ARC FAULT CIRCUIT WHICH IS
 NOT POSSIBLE.
 210.12, 408.4
  
 16) NOTE: PLEASE INDICATE THE TYPE OF RECESSED LIGHTS
 PER FBC 13-606.1.ABC.1.2.4
  
 17) NOTE: PLEASE SEE MISSING SOME TYPE OF LIGHT FIXTURE
 OR SWITCHED RECEPTACLE IN ROOMS. THE USE OF A FAN J-BOX
 IS NOT ACCEPTABLE. IF A FAN/ LT IS GOING TO BE CHOSEN,
 THESE MUST BE SHOWN ON PLANS AT THIS TIME AND THEY WILL
 BE REQUIRED TO BE INSTALLED BEFORE FINAL.
 THE SWITCHING OF A HALF SWITCHED RECEPTACLE IS ALSO
 PERMITTED.
 PLEASE SEE 210.70 , HOWEVER ALSO LS 101 7.8 .
  
 18) NOTE: PLEASE SEE MISSING REQUIRE DEDICATED BATH(S)
 CIRCUIT(S) PER 210.11C3. MUST BE 20A AND #12.
  
 19) NOTE: NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE
 INDICATE SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS
 THESE AS SMOKE DETECTORS.
 PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE ALL WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
  
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 AS SHOWN ON PLANS AND NOTED THESE SHOULD INDEED BY SA
 FOR SMOKE ALARMS.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 20) NOTE: PLEASE SEE PLANS ARE NOT SIGNED, DATED AND
 SEALED BY ANY DESIGNER OF RECORD OR DESIGN
 PROFESSIONAL. FS 481.229, 471.003 ETC
 PLEASE SEE THE TITLE BLOCK INDICATES HOMES DESIGNED BY
 ETC HOWEVER NO LICENSE INFORMATION WAS STATED ON TILE
 BLOCKS FOR SAID FIRM. FAC 61G1-16.004, 61G15-23.002, FS
 481.219 AND 471.023.
 PLEASE SEE THE PLANS EVEN STATE * NOT VALID WITHOUT
 SEAL*.
  
 21) NOTE: PLEASE SEE MISSING RECEPTACLE PER 210.52. SEE
 REDLINED PLANS.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SHOWN OR
 SUBMITTED FOR REVIEW, THE REVIEW FOR CODE COMPLIANCE
 CAN ONLY BE BASED ON THE PLANS SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-08-20 Cont ID  
Sent By adarroug Date 2008-08-20 Time 13:26 Rev Time 0.00
Received By adarroug Date 2008-08-20 Time 13:26 Sent To E
Notes
2008-08-20 13:27:14TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-08-06 Cont ID  
Sent By adarroug Date 2008-08-06 Time 10:08 Rev Time 0.00
Received By adarroug Date 2008-08-06 Time 10:08 Sent To E
Notes
2008-08-06 10:09:14TO "DPALMER' DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-07-28 Cont ID  
Sent By adarroug Date 2008-07-28 Time 14:31 Rev Time 0.00
Received By adarroug Date 2008-07-28 Time 14:31 Sent To E
Notes
2008-07-28 14:31:59TO "DPALMER" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-02-14 Cont ID  
Sent By adarroug Date 2008-02-14 Time 10:36 Rev Time 0.00
Received By adarroug Date 2008-02-14 Time 10:36 Sent To E
Notes
2008-02-14 10:37:08TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 11:05 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 11:04 Sent To Z
Notes
2007-10-24 11:05:56TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-23 Cont ID  
Sent By adarroug Date 2007-08-23 Time 11:08 Rev Time 0.00
Received By adarroug Date 2007-08-23 Time 11:08 Sent To Z
Notes
2007-08-23 11:08:28TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-16 Cont ID  
Sent By rmcdouga Date 2007-07-16 Time 7:10 Rev Time 0.00
Received By rmcdouga Date 2007-06-27 Time 09:22 Sent To  
Notes
2007-06-27 09:23:08TO "SFR" "E"

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-12-15 Cont ID  
Sent By rkussner Date 2008-12-15 Time 13:56 Rev Time 0.00
Received By rkussner Date 2008-12-15 Time 13:56 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-08-11 Cont ID  
Sent By tgordon Date 2008-08-11 Time 08:14 Rev Time 0.25
Received By tgordon Date 2008-08-11 Time 08:13 Sent To  
Notes
2008-08-11 08:14:55RE-STAMP MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-07-30 Cont ID  
Sent By tgordon Date 2008-07-30 Time 10:57 Rev Time 0.30
Received By tgordon Date 2008-07-30 Time 10:57 Sent To P
Notes
2008-07-30 15:43:45** RE-STAMP DENIED **
  
 1) THE SIZE OF THE PLAN SUBMITTED FOR RE-STAMP HAS BEEN
 REDUCED AND DIFFICULT TO READ SOME OF THE INFORMATION
 ON IT, THE QUALITY OF THE COPY IS POOR IN SOME AREAS
 AND IS NOT ACCEPTABLE FOR OFFICIAL RECORDS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 PER 2004 F.B.C. 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-02-15 Cont ID  
Sent By tgordon Date 2008-02-15 Time 14:55 Rev Time 0.40
Received By tgordon Date 2008-02-15 Time 14:55 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-11-02 Cont ID  
Sent By tgordon Date 2007-11-02 Time 13:55 Rev Time 0.40
Received By tgordon Date 2007-11-02 Time 13:55 Sent To P
Notes
2007-11-02 14:18:44PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ONLY ONE COPY OF THE ENERGY CALCULATIONS AND COOLING
 LOAD CALCULATION WERE SUBMITTED, TWO COPIES NEED TO BE
 SUBMITTED, SEE 2004 WPB AMEND. 106.1.
  
 2) COOLING LOAD CALCULATIONS ARE CALLING FOR 25,286
 TOTAL BTU'S. MECHANICAL PLAN IS CALLING FOR 35,000
 TOTAL BTU'S. THE MECHANICAL PLANS CAN ONLY CALL FOR 15%
 MORE THAN THE COOLING LOAD CALCULATIONS, SEE 2004 FBC
 13-607.1.ABC.1.1. PLEASE CORRECT.
  
 3) MECHANICAL PLAN IS CALLING FOR A 8 KW HEATER,
 ELECTRICAL PLAN IS CALLING FOR A 5 KW IN ONE PLACE AND
 A 10 KW IN ANOTHER PLACE, THE THREE MUST COINCIDE,
 PLEASE CORRECT.
  
 4) THE MECHANICAL PLANS NEED THESIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN ON THEM, SEE W.P.B.
 AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-29 Cont ID  
Sent By tgordon Date 2007-08-29 Time 14:26 Rev Time 0.45
Received By tgordon Date 2007-08-29 Time 14:26 Sent To P
Notes
2007-08-29 14:57:44PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 15 IS TAKING THE CEILING
 FAN CREDIT. THE ELECTRICAL PLANS NEED TO SHOW CEILING
 FANS (NOT CEILING FIXTURES) IN THE REQUIRED ROOMS.
 ** 2004 FBC 13-607.2.A.3.1 CEILING FANS.CEILING FAN
 CREDIT MAY BE TAKEN IF ONE OR MORE CEILING FANS ARE
 INSTALLED IN EACH OF THE BEDROOMS AND A MINIMUM OF ONE
 CEILING FAN IS INSTALLED IN ALL PRIMARY LIVING AREAS
 (LIVING ROOMS, FAMILY ROOMS, OR GREAT ROOMS).
 PRESCRIPTIVE REQUIREMENTS IN SECTION 13-607.1.A.1 SHALL
 BE MET.
 ** 13-607.1.A.1 CEILING FAN CREDIT.HOUSES FOR WHICH
 CEILING FAN CREDIT IS CLAIMED IN ACCORDANCE WITH THE
 CRITERIA OF SECTION 13-607.2.A.3.1 SHALL HAVE CEILING
 FANS INSTALLED WITH MINIMUM FAN BLADE DIAMETERS OF NO
 LESS THAN THOSE LISTED IN TABLE 13-607.1A.1 FOR THE
 SIZE AND SHAPE OF THE ROOM.
  
 2) ONLY ONE COPY OF THE ENERGY CALCULATIONS AND COOLING
 LOAD CALCULATIONS WERE SUBMITTED. TWO COPIES NEED TO BE
 SUBMITTED, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-28 Cont ID  
Sent By tgordon Date 2007-06-28 Time 13:50 Rev Time 0.45
Received By tgordon Date 2007-06-28 Time 13:49 Sent To P
Notes
2007-06-28 14:15:24*** DENIED ***
 1) SEE ENERGY CALCULATIONS LINE 11A SHOWS 25 FT OF
 SUPPLY AIR IN ATTIC, PLEASE RE-CHECK AS MECHANICAL
 PLANS SHOW OVER 100 FT. OF SUPPLY AIR DUCT IN THE
 ATTIC, CORRECT E-CAL'S.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) ENERGY CALCULATIONS LINE 15 IS TAKING THE CROSS
 VENTILATION CREDIT, SEE 2004 FBC 13-607.1.A.3.1 AND
 EXPLAIN THIS HOUSE APPLIES OR CORRECT E-CAL'S.
 *** 2004 FBC 13-607.1.A.3.1 CROSS VENTILATION CREDIT.
 HOUSES FOR WHICH CREDIT IS CLAIMED FOR CROSS
 VENTILATION IN ACCORDANCE WITH THE CRITERIA IN SECTION
 13-607.2.A.3.3 SHALL HAVE PROVIDED OPERABLE APERTURE
 AREAS TOTALING A MINIMUM OF 12 PERCENT OF THE FLOOR
 AREA OF THE ROOM FOR ALL PRIMARY LIVING AREAS AND MAIN
 BEDROOMS.
 INSECT SCREENS SHALL BE PROVIDED FOR ALL WINDOWS AND
 DOORS TO BE CONSIDERED OPERABLE APERTURE AREA. ALL
 SCREENED ENTRY DOORS AND INTERIOR DOORS IN THE
 VENTILATED AREAS SHALL BE PROVIDED WITH EITHER (1)
 MECHANICALLY ATTACHED DOOR STOPS (OR SIMILAR DEVICES)
 TO HOLD THE DOOR IN AN OPEN POSITION OR (2) OPERABLE
 LOUVERS.
 THE TOTAL APERTURE AREA SHALL BE PROVIDED BY A MINIMUM
 OF TWO DISTINCT WINDOWS. EACH WINDOW SHALL PROVIDE NOT
 MORE THAN 70 PERCENT OF THE TOTAL APERTURE AREA. THE
 WINDOWS (OR SLIDING GLASS DOORS) SHALL BE PLACED IN
 ADJACENT OR OPPOSITE WALLS. THE WINDOWS MAY BE PLACED
 ON A SINGLE OUTSIDE WALL IF WING WALLS ARE USED.
 WHERE WING WALLS ARE INCLUDED IN THE BUILDING DESIGN
 FOR VENTILATION PURPOSES, THEY SHALL BE PLACED BETWEEN
 WINDOWS TO CREATE A HIGH-PRESSURE AND A LOW-PRESSURE
 ZONE ON EACH WINDOW. WING WALLS SHALL EXTEND FROM THE
 GROUND TO EVE HEIGHT, BE LOCATED ON THE WINDWARD SIDE
 OF THE BUILDING, AND EXTEND OUTWARD FROM THE BUILDING A
 DISTANCE AT LEAST EQUAL TO ONE-HALF THE WIDTH OF THE
 WINDOW.
 NOTE: THIS TECHNIQUE IS EFFECTIVE ONLY FOR AREAS WHICH
 EXPERIENCE SIGNIFICANT AND CONTINUOUS WINDS DURING THE
 COOLING MONTHS.
  
 4)THE JOB ADDRESS NEEDS TO BE ON EACH PAGE ON THE
 PLANS, SEE 2004 FBC, CITY WPB AMEND. 106.1.3 AND FAC
 61G1-16.004(3).
  
 5) PLEASE SHOW SIZE FOR SUPPLY AIR GRILL IN BEDROOM #3
 ON MECHANICAL PLANS.
  
 6) PLEASE SHOW THE TOTAL AND SENSIBLE BTU'S FOR THE A/C
 SYSTEM ON THE MECH. PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  

Review Stop P PLUMBING
Rev No 5 Status F Date 2008-07-31 Cont ID  
Sent By mperson Date 2008-07-31 Time 08:14 Rev Time 0.00
Received By mperson Date 2008-07-31 Time 08:14 Sent To PC
Notes
2008-07-31 08:24:31PLUMBING PLAN REVIEW:
 RESTAMP DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. THE REDUCED SIZE COPIED PLANS SUBMITTED FOR RESTAMP
 ARE HARD TO READ AND ARE NOT TO MINIMUM 1/8 INCH SCALE
 AS REQUIRED. PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION
 106.1.3 QUALITY OF BUILDING PLANS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-02-25 Cont ID  
Sent By jleech Date 2008-02-25 Time 07:46 Rev Time 0.00
Received By jleech Date 2008-02-25 Time 07:19 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-11-19 Cont ID  
Sent By jleech Date 2007-11-19 Time 08:06 Rev Time 0.00
Received By jleech Date 2007-11-19 Time 08:06 Sent To B
Notes
2007-11-19 08:17:22DENIED;
 RISER DIAGRAM NOT TO CODE;
 A) W/M BRANCH DRAIN TO BE 3".
 B) VENTING NOT TO CODE
 C) DRAINAGE NOT TO CODE.
 A RISER DIAGRAM IS ON PAGE 5 OF ONE COPY OF PLANS
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-15 Cont ID  
Sent By jleech Date 2007-09-15 Time 12:53 Rev Time 0.00
Received By jleech Date 2007-09-15 Time 12:53 Sent To B
Notes
2007-09-15 12:57:40DENIED;
 1. SEE ELECTRICAL PLAN REVIEWER'S NOTE 1.
 2. 2ND REQUEST, A SANITARY PLUMBING RISER IS REQUIRED
 PER FBC-2004 BUILDING CHAPTER 1 SECTION 106.3.5.1.3. A
 FLAT LINE DRAWING DOES NOT GIVE ENOUGH INFORMATION.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By jleech Date 2007-07-11 Time 07:27 Rev Time 0.00
Received By jleech Date 2007-07-11 Time 07:25 Sent To B
Notes
2007-07-11 07:36:07DENIED;
 NOT ENOUGH INFORMATION. A SANITARY RISER DIAGRAM
 REQUIRED SEE FBC-2004 CHAPTER 1 ADMINISTRATION CODE
 SECTION 106.3.5.1.3.
 PLUMBING PLAN REVIEW;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-25 Cont ID  
Sent By choops Date 2007-10-25 Time 14:53 Rev Time 0.00
Received By choops Date 2007-10-25 Time 14:53 Sent To E
Notes
2007-10-25 14:54:18***APPROVED - RESUB #2***
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 2 Status F Date 2007-08-27 Cont ID  
Sent By choops Date 2007-08-27 Time 13:58 Rev Time 0.00
Received By choops Date 2007-08-27 Time 13:58 Sent To E
Notes
2007-08-27 13:52:08***FAILED******RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)PLEASE PROVIDE A LANDSCAPE PLAN SHOWING COMPLIANCE
 WITH THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION 94-442.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-28 Cont ID  
Sent By choops Date 2007-06-28 Time 09:16 Rev Time 0.00
Received By choops Date 2007-06-28 Time 09:16 Sent To M
Notes
2007-06-28 09:20:23***FAILED***
  
  
 1)PROVIDE A LANDSCAPE PLAN SHOWING COMPLIANCE WITH
 SECTION 94-442 OF THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS.
  
 2)SHOW A/C UNIT ON SURVEYS WITH SETBACK DIMENSIONS
 TO PROPERTY LINES.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720