Plan Review Details - Permit 07060787
Plan Review Stops For Permit 07060787
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-16 Cont ID  
Sent By shill Date 2007-08-16 Time 19:02 Rev Time 0.00
Received By shill Date 2007-08-16 Time 19:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-31 Cont ID  
Sent By shill Date 2007-07-31 Time 15:22 Rev Time 0.00
Received By shill Date 2007-07-31 Time 15:22 Sent To  
Notes
2007-07-31 15:24:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)DESIGN PRESSURES ARE TOO LOW.NOTE THAT PRESSURES
 PREPARED USING THE SOFTWARE AS WITH PERMIT 07060573 ARE
 GENERALLY ACCEPTABLE.THIS SHEET WAS NOT PREPARED BY
 THAT SOFTWARE, AND DESIGN PRESSURES STATED DO NOT MEET
 THE MINIMUM REQUIRED BY FBC R TABLE 301.2(2), 301.2(3).
 PRESSURES MAY BE DESIGNED BY AN ARCHITECT OR ENGINEER
 USING ASCE7-02.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-06 Cont ID  
Sent By shill Date 2007-07-06 Time 16:55 Rev Time 0.00
Received By shill Date 2007-07-06 Time 16:55 Sent To  
Notes
2007-07-06 17:03:38****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.THE DESIGN PRESSURES SPECIFIED CANNOT BE LESS THAN
 FBC R TABLE 301.2(2), TABLE 301.2(3).
  
 2.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2), FBC
 R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE C
 HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.REVISE ANCHOR SPACING AS NECESSARY.
  
 3.PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 505.1.
  
 4.THE INSTALLATION SCHEDULE IS FOR SHUTTERS.
 OPENINGS 1 THROUGH 14 ARE IMPACT WINDOWS, BUT ARE
 INCLUDED ON THE INSTALLATION SCHEDULE.PLEASE CLARIFY
 SCOPE OF WORK.
  
 5.THE APPLICATION STATES THAT 2 S. PANELS (STORM
 PANELS?) WILL BE INSTALLED.PLEASE PROVIDE PRODUCT
 APPROVALS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-07 Cont ID  
Sent By mmiller Date 2007-08-07 Time 17:42 Rev Time 0.00
Received By mmiller Date 2007-08-07 Time 17:41 Sent To B
Notes
2007-08-07 17:42:14SENT TO SAMANTHA HILL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-26 Cont ID  
Sent By adarroug Date 2007-07-26 Time 10:48 Rev Time 0.00
Received By adarroug Date 2007-07-26 Time 10:48 Sent To B
Notes
2007-07-26 10:49:01TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-06 Cont ID  
Sent By shill Date 2007-07-06 Time 17:03 Rev Time 0.00
Received By shill Date 2007-06-26 Time 10:25 Sent To  
Notes
2007-06-26 10:26:34TO "MISC" BOX#1