Plan Review Details - Permit 07060772
Plan Review Stops For Permit 07060772
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-05-05 Cont ID  
Sent By shill Date 2008-05-05 Time 14:58 Rev Time 0.00
Received By shill Date 2008-05-05 Time 14:58 Sent To  
Notes
2008-05-05 14:59:02REVISION, PARAPET REPAIR

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-04-29 Cont ID  
Sent By shill Date 2008-04-29 Time 15:10 Rev Time 0.00
Received By shill Date 2008-04-29 Time 15:10 Sent To  
Notes
2008-04-29 15:22:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.PLANS REFER TO A BUILDING CODE WHICH DOES NOT
 EXIST.PLEASE REVISE.
  
 2.PLANS REFER TO A CODE SECTION WHICH IS FOR HIGH
 VELOCITY.PLEASE REVISE CODE REFERENCE AS WEST PALM
 BEACH IS NOT IN THE HVHZ.
  
 3.A REVISION FEE WAS CHARGED AS THIS WORK WAS NOT
 INCLUDED IN THE INITIAL PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-11-20 Cont ID  
Sent By shill Date 2007-11-20 Time 18:00 Rev Time 0.00
Received By shill Date 2007-11-20 Time 18:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-11-06 Cont ID  
Sent By shill Date 2007-11-06 Time 14:01 Rev Time 0.00
Received By shill Date 2007-11-06 Time 14:01 Sent To  
Notes
2007-11-06 14:04:25****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LISTS:
  
 18.)SEE ATTACHED POLICY IN REGARDS TO HURRICANE
 SHUTTERS, ITEM 13.SUBMIT AN INSTALLATION PLAN.USE
 OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS MUST BE
 APPROVED BY THE BUILDING OFFICIAL.THIS MAY BE DONE
 INDEPENDENTLY FROM THE PLAN REVIEW PROCESS AND A
 PRELIMINARY PLAN CAN BE SUBMITTED VIA EMAIL TO
 [email protected] DO NOT SUBMIT THIS PLAN WITH THE
 PERMIT APPLICATION RESUBMITTAL AS THIS SHOULD BE
 RESOLVED PRIOR TO RESUBMITTAL.FAILURE TO ADDRESS THIS
 COMMENT WILL RESULT IN DELAYS IN PERMITTING.PLEASE
 CONTACT ME IF YOU NEED FURTHER INFORMATION.
  
 PLANS CANNOT BE APPROVED AS IS UNTIL THIS REQUIREMENT
 IS MET.ENGINEER STATED IN HIS RESPONSE LETTER THAT
 THE SHUTTERS WILL BE STORED "VIA STRAPPING".A DETAIL
 SHOULD BE PROVIDED WITH THE INSTALLATION PLAN.THE
 ATTACHED INSTALLATION SCHEDULE IS REQUIRED OR A
 SEPARATE PERMIT WILL BE REQUIRED FOR THE SHUTTERS.
  
 NEW COMMENTS:
  
 THE PLANS APPEAR TO BE A LEVEL 2 ALTERATION DUE TO THE
 CONSTRUCTION OF THE NEW STAIRS.IF THIS STAIRS ARE
 EXISTING AND BEING REBUILT (NO RECONFIGURATION OF
 SPACE), PLEASE NOTE THIS ON THE PLAN.THIS MAY BE
 WRITTEN AND INITIALED BY THE ENGINEER (NO NEW SHEETS
 REQUIRED).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-11 Cont ID  
Sent By shill Date 2007-09-11 Time 11:50 Rev Time 0.00
Received By shill Date 2007-09-11 Time 11:50 Sent To  
Notes
2007-09-11 11:52:46****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 ****HURRICANE SHUTTER INSTALLATION PLAN***
 ***NOT A PLAN REVIEW****
  
 1.)STATE WHEN THE SHUTTERS WILL BE INSTALLED AS PER
 THE STANDARD, ITEM 13.
  
 2.)WHO IS PROVIDING THE BOOM LIFT?THIS WILL REQUIRE
 APPROVAL BY THE BUILDING OFFICIAL.
  
 3.)PLEASE STATE HOW MANY EMPLOYEES 24TH STREET
 HOLDING, LLC HAS WHO HAVE THE KNOWLEDGE AND ABILITY TO
 INSTALL THE SHUTTERS.ALSO PLEASE STATE HOW MANY OTHER
 BUILDINGS THIS COMPANY IS RESPONSIBLE FOR, INCLUDING
 HOW MANY REQUIRE INSTALLATION OF HURRICANE SHUTTERS.
 WHERE ARE THE OTHER BUILDINGS LOCATED?

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-06 Cont ID  
Sent By shill Date 2007-09-06 Time 10:11 Rev Time 0.00
Received By shill Date 2007-09-06 Time 10:11 Sent To  
Notes
2007-09-06 10:13:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)ADDRESSED.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE NOA SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 2ND REVIEW, ENGINEER REQUESTED CLARIFICATION.PLEASE
 FIND THE FLORIDA STATE PRODUCT APPROVAL FOR EACH NOA.
 THIS CAN BE DONE BY SEARCHING BY MANUFACTURER AT THE
 WEBSITE REFERENCED, WWW.FLORIDABUILDING.ORG.IF A
 FLORIDA STATE PRODUCT APPROVAL IS NOT AVAILABLE, PLEASE
 ADVISE AND A LOCAL PRODUCT APPROVAL CAN BE ISSUED FOR
 FBC COMPLIANT PRODUCTS USING THE NOA.THE REVIEW FOR
 LOCAL PRODUCT APPROVAL WILL BE DONE IF IT IS DETERMINED
 THAT A FLORIDA STATE PRODUCT APPROVAL HAS NOT BEEN
 ISSUED.
  
 3.)GOVERNING CODE IS TO INCLUDE 2005 AND 2006
 AMENDMENTS.
  
 2ND REVIEW, PLANS WERE CHANGED SO THAT THE STAIR NOTES
 REFER TO 2005 AND 2006 LOCAL AMENDMENTS.THE REQUEST
 IS TO ESTABLISH GOVERNING CODE ON THE PLAN BASED ON
 APPLICATION DATE.2006 AMENDMENTS ARE APPLICABLE IN
 THIS CASE.THESE ARE NOT LOCAL AMENDMENTS; THEY ARE
 AMENDMENTS TO THE FLORIDA BUILDING CODE 2004 AT THE
 STATE LEVEL.
  
 4.)N/A
  
 5-10)ADDRESSED.
  
 11.)A1, THE ROOF IS A FLAT DECK WITH NO PARAPET WALL
 SHOWN; PROVIDE CALCULATIONS FOR THE CORNER PRESSURE OF
 -62.8.
  
 2ND REVIEW - ENGINEER RESPONDED WITH TWO STATEMENTS;
 ONE THAT THE NUMBER IS CONSERVATIVE (BUT NO
 CALCULATIONS PROVIDED) AND THAT SINCE ROOF WORK WAS
 REMOVED FROM THE PLAN, THE PRESSURE IS NOT NECESSARY.
  
 IF THE PRESSURES ARE ON THE PLAN, THEY ARE TO BE
 CORRECT.IT APPEARS THAT THE ENGINEER MAY BE USING THE
 TOTAL ZONE 3 AREA OF 16FEET (4X4) OR IS CALCULATING
 ROOF WIND PRESSURES USING MWRS.I WAS UNABLE TO LOCATE
 FBC TABLE 1609.6A WHICH THE ENGINEER REFERS TO IN HIS
 RESPONSE LETTER (THE TABLE NUMBER MAY HAVE BEEN
 MODIFIED WITH THE 2005/2006 AMENDMENTS) BUT IT APPEARS
 THAT YOU ARE REFERRING TO FBC TABLE 1609.6.2.1(1),
 SIMPLIFIED DESIGN WIND PRESSURE (MAIN
 WINDFORCE-RESISTING SYSTEM).PLEASE SEE FBC1609.2,
 DEFINITIONS, EFFECTIVE WIND AREA.FOR CLADDING
 FASTENERS, THE EFFECTIVE WIND AREA SHALL NOT BE GREATER
 THAN THE AREA THAT IS TRIBUTARY TO AN INDIVIDUAL
 FASTENER.SEE ALSO FBC TABLE 1609.6.2.1(2) NET DESIGN
 WIND PRESSURE (COMPONENT AND CLADDING), FLAT ROOF, ZONE
 3, LESS THAN 10SF, HAS A DESIGN PRESSURE OF -89.
  
 YOU MAY REMOVE THIS NUMBER, REVISE THE NUMBER, OR
 PROVIDE CALCULATIONS AS ORIGINALLY REQUESTED.
  
 12.)ADDRESSED.
  
 13.)EXTERIOR STAIRS TO COMPLY WITH ALL REQUIREMENTS
 OF FBC1022.SHOW FIRE RESISTANCE RATING FOR THE WALL
 AS WELL AS OPENINGS.
  
 2ND REVIEW, THE WINDOWS ARE ALSO REQUIRED TO BE
 PROTECTED (ONLY DOORS SHOWN AS RATED).HOWEVER, SEE
 THE EXCEPTION FBC1019.1 EXCEPTION 4, AND FBC1022.6.IF
 COMPLIANCE WITH FBC1019 CAN BE SHOWN FOR THE EXISTING
 STAIR, IT APPEARS THAT THE NEW STAIR MAY FALL UNDER THE
 EXCEPTION.
  
 14.)ADDRESSED.
  
 15-17)ADDRESSED.
  
 18.)SEE ATTACHED POLICY IN REGARDS TO HURRICANE
 SHUTTERS, ITEM 13.SUBMIT AN INSTALLATION PLAN.USE
 OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS MUST BE
 APPROVED BY THE BUILDING OFFICIAL.THIS MAY BE DONE
 INDEPENDENTLY FROM THE PLAN REVIEW PROCESS AND A
 PRELIMINARY PLAN CAN BE SUBMITTED VIA EMAIL TO
 [email protected] DO NOT SUBMIT THIS PLAN WITH THE
 PERMIT APPLICATION RESUBMITTAL AS THIS SHOULD BE
 RESOLVED PRIOR TO RESUBMITTAL.FAILURE TO ADDRESS THIS
 COMMENT WILL RESULT IN DELAYS IN PERMITTING.PLEASE
 CONTACT ME IF YOU NEED FURTHER INFORMATION.
  
 2ND REVIEW, DISCUSSED WITH CONTRACTOR BUT NOT
 ADDRESSED.NO PLAN WAS SUBMITTED.THIS IS REQUIRED.
 ENGINEER PLEASE NOTE THAT THE PLAN WILL BE REQUIRED TO
 SHOW WHERE THE SHUTTERS WILL BE STORED AND HOW THIS
 AREA WILL BE SECURED.THIS MAY AFFECT FIRE RESISTANCE
 REQUIREMENTS SHOWN ON THE PLAN.
  
 19-23.)ADDRESSED.
  
 24.)PROVIDE A DETAIL FOR PENETRATIONS THROUGH THE
 FIRE RATED WALLS AND FLOOR/CEILING ASSEMBLIES FBC7.
  
 2ND REVIEW, RESPONSE LETTER STATES THAT FIRE RATINGS
 FOR OPENINGS ARE SHOWN.THIS COMMENT REFERS TO
 PENETRATIONS.PLEASE ADDRESS.
  
 25-26.) ADDRESSED.
  
 27.)SEE ATTACHED INSTALLATION SCHEDULE.EITHER
 COMPLETE THIS FORM OR PROVIDE ALL REQUIRED INFORMATION
 IN ANOTHER FORMAT FOR THE HURRICANE SHUTTERS.THIS
 SHOULD CORRELATE WITH A KEY PLAN SHOWING SHUTTER
 LOCATIONS.THIS APPLIES TO FIRST FLOOR WINDOWS ONLY.
 SECOND FLOOR WINDOWS ARE REQUIRED TO BE IMPACT RATED
 (WITH THE POSSIBLE EXCEPTION OF THE NEW W4 WINDOWS
 WHICH HAVE ACCESS FROM THE BALCONY).
  
 2ND REVIEW, NOT ADDRESSED.
  
 28.)EXTERIOR CHANGES TO THE PLAN WILL REQUIRE
 HISTORIC REVIEW PRIOR TO RESUBMITTAL.
  
 29-33.) ADDRESSED.
  
 NEW COMMENTS:
  
 34.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 35.)THE SMOKE ALARMS SHOWN DO NOT COMPLY WITH
 FBC907.2.10.1.2(2).NO SMOKE ALARMS SHOWN IN THE
 SLEEPING ROOMS AS REQUIRED.
  
 36.)FOR THE NON IMPACT WINDOW, CIRCLE ON THE PRODUCT
 APPROVAL WHICH GLASS OPTION YOU ARE USING AS NOT ALL
 ARE COMPLIANT FOR THE DESIGN PRESSURE REQUIRED.
  
 37.)NON IMPACT AND IMPACT FIXED WINDOW PRODUCT
 APPROVALS SUBMITTED.WHERE WILL THEY BE INSTALLED? THE
 PLAN SHOWS SINGLE HUNG ONLY ON THE ELEVATIONS, AND THE
 WINDOW SCHEDULE DOES NOT DESIGNATE TYPE OF WINDOW. ALSO
 PLEASE REVISE PLAN TO DESIGNATE WHICH WINDOWS WILL BE
 IMPACT AND WHICH WINDOWS ARE PROPOSED AS NON IMPACT (TO
 BE APPROVED BY BUILDING OFFICIAL, SEE ITEM 18).
  
 38.)SEE FBC EB 704.1, FBC903.2.7 REGARDING FIRE
 SPRINKLER REQUIREMENTS.
  
 39.)WHEN RESUBMITTING, PROVIDE A RESPONSE LETTER
 INDICATING HOW EACH COMMENT WAS ADDRESSED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-25 Cont ID  
Sent By shill Date 2007-07-25 Time 10:54 Rev Time 0.00
Received By shill Date 2007-07-25 Time 10:54 Sent To I
Notes
2007-07-25 10:55:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE NOA SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 3.)GOVERNING CODE IS TO INCLUDE 2005 AND 2006
 AMENDMENTS.
  
 4.)N/A
  
 5.)FOR ALL OF THE FIRE RATED ASSEMBLIES, SHOW
 CALCULATED FIRE RESISTANCE OR TESTED ASSEMBLY FBC 7.
  
 6.)IN THE BUILDING CODE SUMMARY ON A1, PLEASE PROVIDE
 THE TOTAL SQUARE FOOT AREA PER FLOOR, FBC TABLE 503.
  
 7.)THE PLAN SHOWS THE EXTERIOR WALLS AND 2ND FLOOR
 CEILING AS RATED.PROVIDE A SITE PLAN AND SHOW
 COMPLIANCE WITH FBC TABLE 601, FBC TABLE 602, FBC TABLE
 704.8.ARE THEY REQUIRED TO BE RATED WALLS OR ARE YOU
 EXCEEDING CODE COMPLIANCE?IT IS NOT CLEAR IF THE
 OPENINGS IN THE RATED WALLS ARE TO BE PROTECTED.
  
 8.)ROOF FELT UNDERLAYMENT FASTENING IS SPECIFIED.IT
 IS NOT CLEAR WHERE THIS WILL BE USED.EITHER REMOVE OR
 SHOW LOCATION OF WORK AND PROVIDE PRODUCT APPROVAL FOR
 THE ROOF ON A2 AND CONFIRM COMPLIANCE WITH FASTENING
 REQUIRED BY THE PRODUCT APPROVAL.
  
 9.)SHOW ALL REQUIRED FIRE RESISTANCE RATED WALLS ON
 THE FLOOR PLAN.
  
 10.)PROVIDE INFORMATION IN REGARDS TO THE TENANT
 SEPARATION WALL.SHOW REQUIRED FIRE RESISTANCE AND HOW
 THAT IS ACCOMPLISHED.NOTE THAT EXTERIOR WALLS ARE
 SHOWN AS FIRE RATED BUT THE INT BEARING WALL IS NOT,
 BUT IT APPEARS THAT THE BEARING WALL IS THE TENANT
 SEPARATION WALL AND IS REQUIRED TO HAVE A 1 HOUR RATING
 FBC708.1.AS SHOWN THE WALL DOES NOT MEET THE
 CONTINUITY REQUIREMENTS OF FBC708.4.SEE ALSO FBC EB
 703.2.
  
 11.)A1, THE ROOF IS A FLAT DECK WITH NO PARAPET WALL
 SHOWN; PROVIDE CALCULATIONS FOR THE CORNER PRESSURE OF
 -62.8.
  
 12.)THE PLAN SHOWS THAT THE LANDING AND STAIRWAY ARE
 UNDER SEPARATE PERMIT.THIS IS IN CONFLICT WITH THE
 APPLICATION WHICH STATES THAT THE STAIRS AND LANDING
 ARE WITHIN THE SCOPE OF THIS PERMIT.
  
 13.)EXTERIOR STAIRS TO COMPLY WITH ALL REQUIREMENTS
 OF FBC1022.SHOW FIRE RESISTANCE RATING FOR THE WALL
 AS WELL AS OPENINGS.
  
 14.)SHOW THAT THE DOOR FOR THE SECOND FLOOR UNIT EXIT
 DOORS MEET WIDTH REQUREMENTS OF FBC1008.8.8 (MEASURE
 FROM EACH DOOR TO THE CORNER OF STAIR/GUARDRAIL).
  
 15.)ONLY ONE HANDRAIL IS SHOWN.A HANDRAIL ON EACH
 SIDE IS REQUIRED FBC1009.11.SHOW HANDRAILS AS
 REQUIRED, WITH EXTENSIONS FBC1009.11.5.
  
 16.)SHOW DIMENSIONS OF THE SLOPED HANDRAIL EXTENSION
 AT THE BOTTOM OF THE STAIR, FBC1009.11.5 (WEST
 ELEVATION).
  
 17.)ROOF NAILING PATTERN DOES NOT COMPLY WITH FBC
 TABLE 2304.9.1 (31) FOR 10D NAILS.
  
 18.)SEE ATTACHED POLICY IN REGARDS TO HURRICANE
 SHUTTERS, ITEM 13.SUBMIT AN INSTALLATION PLAN.USE
 OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS MUST BE
 APPROVED BY THE BUILDING OFFICIAL.THIS MAY BE DONE
 INDEPENDENTLY FROM THE PLAN REVIEW PROCESS AND A
 PRELIMINARY PLAN CAN BE SUBMITTED VIA EMAIL TO
 [email protected] DO NOT SUBMIT THIS PLAN WITH THE
 PERMIT APPLICATION RESUBMITTAL AS THIS SHOULD BE
 RESOLVED PRIOR TO RESUBMITTAL.FAILURE TO ADDRESS THIS
 COMMENT WILL RESULT IN DELAYS IN PERMITTING.PLEASE
 CONTACT ME IF YOU NEED FURTHER INFORMATION.
  
 19.)STAIR TREAD TO BE 11IN MINIMUM, FBC1009.3.
  
 20.)PROVIDE A HANDRAIL DETAIL FBC10 AND SPECIFY
 DESIGN STRENGTH FBC16.NOTE THAT THE STAIR AS DRAWN,
 WEST ELEVATION, DOES NOT MEET THE CONTINUITY
 REQUIREMENT FBC1009.11.4.
  
 21.)THE GUARD IS TO MEET THE HEIGHT REQUIREMENT OF
 FBC1012.2, INCLUDING THE GUARD AT THE STAIRS.THE
 EXTERIOR STAIRS DOES NOT FALL UNDER THE EXCEPTIONS.
 ALSO PLEASE SEE FBC1009.11.1, EXCEPTION REGARDING STAIR
 RAIL HEIGHT.
  
 22.)IT APPEARS THAT THIS IS S FOUR UNIT BUILDING, BUT
 THERE ARE ONLY TWO UNIT DESIGNATION NUMBERS (#1 AND #2,
 ON FIRST AND SECOND FLOORS).
  
 23.)A2 STATES THAT FRAMING WILL BE IN ACCORDANCE WITH
 CURRENT NDS CODE.THIS IS NOT REFERENCED IN THE FBC,
 SEE CHAPTER 35.PLEASE CHECK ALL REFERENCES ON THE
 PLAN FOR ANY WHICH MAY BE IN CONFLICT WITH FBC.
  
 24.)PROVIDE A DETAIL FOR PENETRATIONS THROUGH THE
 FIRE RATED WALLS AND FLOOR/CEILING ASSEMBLIES FBC7.
  
 25.)ELEVATIONS CONFLICT AS TO TYPE OF DOOR TO BE
 INSTALLED.ONE SHOWS A GLAZED DOOR, ANOTHER SHOWS
 OPAQUE.PLANS SHOULD BE CLEAR AS TO WHAT IS PROPOSED,
 AND PRODUCT APPROVALS ARE TO BE SUBMITTED FOR ALL
 COMPONENTS AND CLADDING.
  
 26.)THE DOOR PRODUCT APPROVALS ARE FOR INSWING DOUBLE
 OPAQUE DOORS.NONE ARE SHOWN ON THE PLAN.
  
 27.)SEE ATTACHED INSTALLATION SCHEDULE.EITHER
 COMPLETE THIS FORM OR PROVIDE ALL REQUIRED INFORMATION
 IN ANOTHER FORMAT FOR THE HURRICANE SHUTTERS.THIS
 SHOULD CORRELATE WITH A KEY PLAN SHOWING SHUTTER
 LOCATIONS.THIS APPLIES TO FIRST FLOOR WINDOWS ONLY.
 SECOND FLOOR WINDOWS ARE REQUIRED TO BE IMPACT RATED
  
 28.)EXTERIOR CHANGES TO THE PLAN WILL REQUIRE
 HISTORIC REVIEW PRIOR TO RESUBMITTAL.
  
 29.)PROVIDE SLIDING GLASS DOOR PRODUCT APPROVALS.
  
 30.)DOOR SWING CONFLICTS ON A1 AND A4.IF YOU ARE
 INSTALLING INSWING DOORS, PROVIDE PRODUCT APPROVALS.
  
 31,)SHOW ALL SAFETY GLAZING REQUIREMENTS ON THE FLOOR
 PLAN OR WINDOW SCHEDULE, FBC2406.
  
 32.)THE ISSUES REGARDING THE 4X FEE FOR THIS PROPERTY
 ARE TO BE ADDRESSED PRIOR TO PERMIT ISSUANCE.
  
 33.)WHEN RESUBMITTING, PROVIDE A RESPONSE LETTER
 INDICATING HOW EACH COMMENT WAS ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-05 Cont ID  
Sent By btrobaug Date 2007-11-05 Time 09:27 Rev Time 0.00
Received By btrobaug Date 2007-11-05 Time 08:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By btrobaug Date 2007-07-31 Time 11:01 Rev Time 0.00
Received By btrobaug Date 2007-07-30 Time 17:00 Sent To  
Notes
2007-07-31 11:03:52 
  
 DENIED/INCOMPLETE INFORMATION
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} NO ELECTRICAL PLANS THIS SET. PLANS MUST BE
 SUBMITTED INDICATING COMPLIANCE WITH SECTIOM 7.8
 NFPA-101 AND 210.70(2)(B) 2005 NEC FOR THE NEW STAIRWAY
 AND LANDING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-11-06 Cont ID  
Sent By mwennerg Date 2007-11-06 Time 12:54 Rev Time 0.00
Received By mwennerg Date 2007-11-06 Time 12:54 Sent To  
Notes
2007-11-06 12:57:27PROTECTION OF OPENINGS BENEATH OUTSIDE STAIRS TO COMPLY
 WITH NFPA 101, SEC. 7.2.2.6.4.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-19 Cont ID  
Sent By mwennerg Date 2007-09-19 Time 10:45 Rev Time 0.00
Received By mwennerg Date 2007-09-19 Time 10:45 Sent To  
Notes
2007-09-19 11:00:23***DENIED***
  
 MOST COMMENTS HAVE BEEN ADDRESSED HOWEVER PLEASE SEE
 THE FOLLOWING:
  
 1) COMMENT #7 WAS ACKNOWLEDGED. PLEASE INDICATE ON
 PLANS THAT NFPA 101, SEC. 7.2.2.2 WILL BE COMPLIED WITH
 REGARDING STAIRS. PLEASE PROVIDE MORE INFORMATION
 REGARDING OPENINGS EXPOSED TO THE OUTSIDE STAIRS.
  
 2) A NOTE ON SHEET A-1 MENTIONS SMOKE ALARMS AND THE
 PLANS INDICATE SMOKE DETECTORS. PLEASE CORRELATE AND
 PROVIDE COVERAGE BASED ON APARTMENT BUILDINGS NEW OR
 EXISTING.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-27 Cont ID  
Sent By mwennerg Date 2007-07-27 Time 13:42 Rev Time 0.00
Received By mwennerg Date 2007-07-27 Time 13:42 Sent To  
Notes
2007-07-27 14:11:16***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) PROJECT IS LISTED AS MULTI-FAMILY RESIDENCE. PLEASE
 CLEARLY DEFINE NUMBER OF LIVING UNITS UNDER ROOF. SEE
 ADDRESSING FOR POSSIBLE UNIT DESIGNATIONS.
  
 4) IF PROJECT MEETS REQUIREMENTS FOR MULTI-FAMILY,
 ADDRESS SHALL BE LOCATED ON BUILDING AND SHALL BE NOT
 LESS THAN SIX (6") IN HEIGHT AND CONTRASTING TO
 BACKGROUND. PLEASE ILLUSTRATE ON ELEVATIONS.
  
 5) 2A-10B,C RATED FIRE EXTINGUISHERS ARE REQUIRED.
  
 6) PLEASE PROVIDE LOCATION OF REQUIRED SMOKE ALARMS
 THAT SHALL BE HARD WIRED TO HOUSE ELECTRIC. ACTIVATION
 OF ONE (1) ALARM SHALL CAUSE OTHER ALARMS IN AREA TO
 ACTIVATE.
  
 7) STAIRS TO COMPLY WITH NFPA 101, SEC. 7.2.2.
  
 8) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-06-22 Cont ID  
Sent By swurafti Date 2007-06-22 Time 13:39 Rev Time 0.00
Received By swurafti Date 2007-06-22 Time 13:39 Sent To  
Notes
2007-06-22 13:40:10HISTORIC APPROVED BY GJUDGE

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 10:18 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 10:18 Sent To B
Notes
2008-05-02 10:18:55TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-25 Cont ID  
Sent By adarroug Date 2008-04-25 Time 11:26 Rev Time 0.00
Received By adarroug Date 2008-04-25 Time 11:26 Sent To B
Notes
2008-04-25 11:26:49TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-16 Cont ID  
Sent By adarroug Date 2007-11-16 Time 08:31 Rev Time 0.00
Received By adarroug Date 2007-11-16 Time 08:31 Sent To B
Notes
2007-11-16 08:32:26TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 11:14 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 11:14 Sent To  
Notes
2007-10-30 14:40:07TO "BOB"#11
2007-10-24 11:14:18WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 14:01 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 14:01 Sent To  
Notes
2007-09-05 11:04:07TO "BOB"#8
2007-08-29 11:28:46 
 8/29/07PLANS RETURNED TO LINE "WAITING FOR BOB"
2007-08-28 20:01:53 
 8/28/07PLANS WITH R BROWN FOR A MEETING ON 8/29/07.
2007-08-27 14:02:18WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-01 Cont ID  
Sent By jleech Date 2007-08-01 Time 07:14 Rev Time 0.00
Received By jleech Date 2007-06-25 Time 14:42 Sent To  
Notes
2007-07-26 08:27:347/26/07--ROUTED TO "BOB"#4
2007-06-25 14:46:38TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-07-31 Cont ID  
Sent By tgordon Date 2007-07-31 Time 15:59 Rev Time 0.25
Received By tgordon Date 2007-07-31 Time 15:59 Sent To  
Notes
2007-07-31 16:00:31NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-08-01 Cont ID  
Sent By jleech Date 2007-08-01 Time 07:13 Rev Time 0.00
Received By jleech Date 2007-08-01 Time 07:13 Sent To  
Notes
2007-08-01 07:14:41NO PLUMBING WORK SHOWN ON THIS SET OF PLANS. PLUMBING
 PLANS REQUIRED WITH PLUMBING APPLICATION.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-30 Cont ID  
Sent By choops Date 2007-10-30 Time 16:26 Rev Time 0.00
Received By choops Date 2007-10-30 Time 16:26 Sent To  
Notes
2007-10-30 16:26:54***APPROVED - RESUB #2***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-09-12 Cont ID  
Sent By choops Date 2007-09-12 Time 09:43 Rev Time 0.00
Received By choops Date 2007-09-12 Time 09:43 Sent To  
Notes
2007-09-12 09:56:33***FAILED - RESUB #1***
  
  
 1)DECLARED VALUE TOO LOW, FEES MUST BE ADJUSTED.
 ASSESS AN APPROPRIATE VALUE INCLUDING MATERIAL, LABOR,
 AND DESIGN COSTS.IF AN APPROPRIATE VALUE IS NOT
 DECLARED A VALUATION WILL BE MADE BY THE STRUCTURAL
 PLANS REVIEWER USING MARSHALL AND SWIFT.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By choops Date 2007-06-26 Time 16:56 Rev Time 0.00
Received By choops Date 2007-06-26 Time 16:56 Sent To B
Notes
2007-06-26 16:59:20***FAILED***
  
  
 1)PROVIDE 2 COPIES OF A CURRENT SURVEY SHOWING THE
 SCOPE OF WORK WITH DIMENSIONS AND SETBACK DIMENSIONS
 FROM THE PROPERTY LINES.
  
 2)REVISE PLANS THAT STATE, "STAIRWAY TO BE ON
 SEPERATE PERMIT." (INCLUDED IN SCOPE OF WORK FOR THIS
 PERMIT).
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720