Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-18 Cont ID  
Sent By mjacobs Date 2007-12-18 Time 07:53 Rev Time 0.00
Received By mjacobs Date 2007-12-18 Time 06:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-26 Cont ID  
Sent By mjacobs Date 2007-10-26 Time 17:19 Rev Time 0.00
Received By mjacobs Date 2007-10-26 Time 07:35 Sent To  
Notes
2007-10-26 17:19:21 
 NOTE: THE PLANS SHALL BE REVIEWED AND APPROVED BY THE
 BASE BUILING ARCHITECT OF RECORD WITH AN APROVAL STAMP
 BY THAT ARCHITECTURAL FIRM. THIS IS REQUIRED DUE TO THE
 FACT THAT THIS BUILD OUT WILL AFFECT THE ORIGINAL PLANS
 OF THE BASE BUILDING INTERIOR DESIGN DESIGN. THE
 APPLICATION WILL HAVE A FAIL STATUS UNTIL THIS
 REQUIREMENT IS ACHIEVED. UNTIL THE BUILDING RECEIVE THE
 CERTIFICATE OF OCCUPANCY, IT IS THE RESPONSIBILITY OF
 THE ORIGINAL DESIGN TEAM PER FLORIDA STATUTES 471/481
 AND FAC 61G1-16 AND 61G15-23.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-02 Cont ID  
Sent By mjacobs Date 2007-07-02 Time 08:36 Rev Time 0.00
Received By mjacobs Date 2007-06-30 Time 15:44 Sent To  
Notes
2007-07-02 06:55:20BUILDING PLAN REVIEW
 PERMIT: 07060745
 ADD: 1641 WORTHINGTON RD
 CONT: HEDRICK BROTHERS CONST.
 TEL: (561)688-6282
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)THE SHOWER STALLS SHALL INDICATE ON THE FLOOR PLANS
 THE REQUIREMENTS OF FBC. SECTION 11-4.21. SHOW THE
 SHOWER CONTROLS IN RELATION TO THE SEAT ON THE FLOOR
 PLAN.
  
 3)INDICATE ON THE PLANS THE TYPE OF BACKING FOR THE
 SUPPORT OF THE GRAB BARS AND SHOWER SEATS WHICH WILL
 MEET THE 250LBS REQUIREMENTS OF FBC. SEC.11-4.26.
  
 NOTE:SHEET A4.0 DETAIL #8 THERE SHALL BE SOME TYPE OF
 FIRE RESISTANT SEALANT PLACE BETWEEN THE OBJECT AND THE
 DRYWALL. INDICATE ON THE DETAIL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-05-22 Cont ID  
Sent By btrobaug Date 2008-05-22 Time 09:01 Rev Time 0.00
Received By btrobaug Date 2008-05-22 Time 08:45 Sent To  
Notes
2008-05-22 09:01:45 
  
 THIS REVISION FOR AN ELECTRIC WATER HEATER./WRT.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-01-14 Cont ID  
Sent By dpalmer Date 2008-01-14 Time 13:40 Rev Time 0.00
Received By dpalmer Date 2008-01-14 Time 13:40 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-12-13 Cont ID  
Sent By dpalmer Date 2007-12-13 Time 11:42 Rev Time 0.00
Received By dpalmer Date 2007-12-13 Time 11:42 Sent To  
Notes
2007-12-13 11:42:13** DENIED/TEMPORARY **
  
 1) NOTE: PLEASE SEE THERE IS A MISSING SHEET E5.1 FROM
 ONE OF THE SETS. AS THIS PROJECT IS STILL A THRESHOLD
 PROJECT AND BASE BUILDING HAS NOT RECEIVED A
 CERTIFICATE OF OCCUPANCY AT THIS POINT THREE COMPLETE
 SETS ARE REQUIRED AND NEEDED.
 PLEASE KNOW THE ELECTRICAL IS OK AND ALL OTHER SHEETS
 IN ALL THREE SETS HAVE BEEN STAMPED.
 ** PLEASE BE SURE THE NEW SHEET CONTAINS STAMP FROM
 BASE BUILDING ELECTRICAL ENGINEER OF RECORD.
 ** NO RE-SUB FEE WILL BE REQUIRED FOR ONLY THIS ITEM.
 PLEASE KEEP IN MIND IF PLANS GO BACK FOR COMMENTS FROM
 OTHER TRADES THE RE-SUB MAY BE DUE.
 FBC ADMIN SECTION 106.1
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-20 Cont ID  
Sent By dpalmer Date 2007-10-20 Time 12:28 Rev Time 0.00
Received By dpalmer Date 2007-10-20 Time 11:34 Sent To  
Notes
2007-10-20 12:28:14** DENIED 2ND REVIEW **
  
 *** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE SEE NEW NOTE ALSO.
  
 1) NOTE: PLEASE SEE AS MENTION BY THE BASE BUILDING
 DESIGNER OF RECORD. THE NOTE ON E2.1 *SHEET NOTE #2*
 DOES MENTION THAT ALL RECEPTACLES ARE TO BE WIRED TO
 PANEL HL, YET ALL CIRCUITS FOR RECEPTACLES ON PLANS
 CALL FOR PANEL HL2. THIS IS AN ITEM WHICH COULD BE
 REDLINED HOWEVER PLANS ARE COMING BACK FOR COMMENTS
 FROM OTHER NOTES, PLEASE ADDRESS AT THIS TIME.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTE MENTIONED TO
 COORDINATE AND SEE ADDRESSING REVIEWER FOR SUITE/UNIT
 NUMBER. IT WAS MENTIONED TO PLEASE INDICATE ON
 APPLICATION ONCE THIS WAS DETERMINED BASED ON THE
 ADDRESSING REVIEWER HOWEVER APPLICATION STILL DOES NOT
 SHOW THIS.
 THIS HAS NOT BEEN ADJUSTED IN OUR SYSTEM AND THIS
 INFORMATION WAS E-MAILED TO THE ADDRESSING REVIEW FOR
 CORRECTION AND COORDINATION.
 THE TITLE BLOCKS WERE CHANGED TO SHOW SUITE/UNIT #110.
  
 3) NOTE: PLEASE SEE AS MENTIONED ON THE PREVIOUS REVIEW
 AND AS GONE OVER WITH BOTH DESIGNERS FROM ICE
 ENGINEERING THESE PLANS ARE BEING REQUIRED TO CONTAIN
 STAMPS FOR *SHOP DRAWING* REVIEW BY THE DESIGNERS OF
 RECORD FOR THE BASE BUILDING. PLEASE KNOW THIS IS NOT
 FOR THESE ENGINEERS TO SIGN AND SEAL PLANS, IT IS FOR
 SHOP DRAWING REVIEW STAMP WHICH WILL BE SIGNED AND
 ACKNOWLEDGES THE PLANS AND CHANGES WHICH WILL AFFECT
 THE BASE BUILDING ELECTRICAL AND OTHER SYSTEMS. THIS
 BUILDING IS STILL UNDER THE RESPONSIBILITY OF THE BASE
 BUILDING DESIGN TEAM UNTIL SUCH TIME A CERTIFICATE OF
 OCCUPANCY (CO) IS ISSUED. THIS INCLUDES THE
 ARCHITECTURAL AND ENGINEERING FIRMS.
 FS 471/481, FAC 61G1-16, 61G15-23
  
 ** THIS IS REQUIRED FOR ALL TRADES AND ALL REVIEWS
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. THIS
 WAS CLEARLY STATED ON THE PREVIOUS REVIEW.
 THIS WAS CONFIRMED WITH ASSISTANT BUILDING OFFICIAL MR.
 ROBERT BROWN.
  
 ** PLEASE BE SURE COORDINATION IS MADE WITH THE BASE
 BUILDING DESIGN TEAM.
  
 4) NOTE: PLEASE SEE PANEL HL ON PLANS AND PANEL
 SCHEDULES IS STILL BEING SHOWN AS CONTAINING NO MAIN
 CIRCUIT BREAKER. THIS IS SHOWN AS MAIN LUG ONLY (MLO)
 WHEN A MAIN IS REQUIRED ON THE SECONDARY SIDE OF THE
 TRANSFORMER AS REQUIRED PER 408.36, 240.21, 240.4,
 310.16 ETC.
 PLEASE SEE THE RESPONSE LETTER MENTIONS THIS WAS
 ADDRESSED HOWEVER BASED ON PLANS SUBMITTED THIS REMAINS
 THE SAME.
 ** BASE BUILDING PLANS DO CONTAIN A MCB ON THE
 SECONDARY SIDE OF ALL TRANSFORMERS. PLEASE COORDINATE
 WITH BASE BUILDING DESIGN TEAM AND MINIMUM CODE
 REQUIREMENTS.
  
  
 5) NOTE: PLEASE PROVIDE CALCULATIONS/FIGURES ON HOW THE
 LPD WAS DERIVED.
 BASED ON SOME CALCULATIONS AND FIGURES DONE BY THIS
 OFFICE THERE IS SOME DIFFERENCES.
 PLEASE PROVIDE FRO EXAMPLE, SQ FT ON AREAS BASED ON
 SPACE BY SPACE WHICH WAS SHOWN.
 PLEASE SEE 13-415.2.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO FBC
 11-4.28.1, .2 AND .3(4) FOR MINIMUM LEVELS FOR FIRE
 ALARMS DEVICES TO BE STATED. PLEASE SEE THE LOCATIONS
 APPEAR TO MEET ADA REQUIREMENTS, HOWEVER MINIMUM LEVELS
 NEED TO BE STATED. PLEASE SEE ONLY TWO OF THE DEVICES
 ON THE NEW FA SHEET CONTAIN THE MINIMUM LEVELS NEEDED.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-29 Cont ID  
Sent By dpalmer Date 2007-06-29 Time 17:47 Rev Time 0.00
Received By dpalmer Date 2007-06-29 Time 17:47 Sent To  
Notes
2007-06-29 17:49:40*** UNSAT ***
  
 *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME.
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS. THIS WAS DONE ON
 ARCHITECTURAL SHEETS HOWEVER THE ELECTRICAL SHEETS ARE
 BLANK AT THIS LOCATION.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE ALL MEP SHEETS IN ALL SETS ARE
 MISSING THE REQUIRED TITLE BLOCKS AND INFORMATION AS
 REQUIRED UNDER THE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002.
 PLEASE SEE MISSING INFORMATION IS ALSO REQUIRED UNDER
 FLORIDA STATUTES 471.023.
 ** THIS IS REQUIRED ON ALL MEP PLANS WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADE REVIEWER(S).
  
 3) NOTE: PLEASE KNOW THAT PERMIT APPLICATION WAS
 SUBMITTED WITHOUT ANY SUITE/UNIT/SPACE #. PLEASE KNOW
 THAT A COPY OF THE PERMIT APPLICATION HAS BEEN
 FORWARDED TO THE ADDRESSING REVIEWER. ONCE THE
 SUITE/UNIT/SPACE NUMBER HAS BEEN DETERMINED PLEASE BE
 SURE THIS INFORMATION IS PLACED ON PLANS/TITLE BLOCKS.
 FAC 61G15-23.002, 61G1-16.004
  
 4) NOTE: PLEASE KNOW PLANS ARE BEING REVISED WHILE
 THERE IS STILL AN ACTIVE PERMIT FOR THE SHELL BUILDING.
 THE BASE SHELL BUILDING IS OF A DIFFERENT MEP DESIGN
 PROFESSIONAL AND ANY AND ALL CHANGES AND REVISIONS MADE
 TO BUILDING BY THE BUILD OUT DESIGNS AND WORK SHALL BE
 REVIEWED BY THE BASE BUILDING ENGINEER OF RECORD.
 (EXAMPLE: AS SHOP DRAWINGS)
 *** IMPORTANT**
 PLEASEALSO KNOW AS THERE ARE MANY ITEMS WHICH NOW
 AFFECT THE BASE BUILDING PLANS, COORDINATION OFNOW
 KNOWN LOADS FOR REVISED LOAD CALCULATIONS, KNOWN
 CHANGES FOR ENERGY CALCULATIONS, RISER INFORMATION,
 PANEL SCHEDULES ETC WILL ALL NEED TO BE GIVEN TO THE
 BASE BUILDING ENGINEER OF RECORD TO REVISED THE BASE
 BUILDING PLANS AND ENERGY CALCULATIONS.
 THERE ARE ITEMS WHICH WILL NOW AFFECT THIS.
 FBC 106.1.2, 106.3.5.1.2,
 NEC 408.4, 215.5, 230, 220, 240, 310 ETC.
 FBC CHAPTER 13, 13-415.1.AB.1.1, 13-415.2 ETC
  
 5) NOTE: PLEASE SEE THE PANELS AS SHOWN ON PLANS ARE
 NOT ALL SHOWN ON THE SHEETS WHERE THE PANEL SCHEDULES
 ARE LOCATED. PLEASE CLARIFY THE MCB ON THE LOAD SIDE OF
 THE TRANSFORMER AS ON BASE BUILDING PLANS.
 240.21, 408.36, 240.4, 310.16 ETC.
 FBC 106.1.2 FOR COORDINATION OF PLANS.
  
 6) NOTE: PLEASE COMPLETE AND INDICATE ALL CIRCUITING ON
 PLANS WITH PANEL SCHEDULES.
 PLEASE SEE FOR EXAMPLE SOME OF THE EXIT LIGHTS WHICH
 ARE NOTED TO BE CIRCUITED TO THE LOCAL LIGHTING CIRCUIT
 DO NOT ACTUALLY SHOW THIS. THIS IS SHOWN FOR EMERGENCY
 LIGHTS AS REQUIRED PER 700.12F BUT NOT FOR ALL EXIT
 LIGHTS.
 PLEASE COMPLETE.
 FBC 106.1.2, 106.3.5.1.2.
 NEC 408.4.
  
 7)NOTE: PLEASE SUBMIT PLANS FOR LIGHTING WHICH SHOWS
 COMPLETED INFORMATION FOR CHAPTER 13 CODE COMPLIANCE.
 PLEASE SEE SOME OF THE DEVICES ON PLANS INDICATE A NOTE
 * TO BE CHOSEN BY MANUFACTURES RECOMMENDATION*. THIS IS
 TO BE CHOSEN, DESIGNED, AND SHOWN AT THIS POINT.
 DESIGNS FOR CODE COMPLIANCE ARE NOT LEFT TO THE
 MANUFACTURE.
 PLEASE STATE DEVICE TYPES.
 PLEAS INDICATE MAXIMUM TIMES ON DEVICES CHOSEN. PLEASE
 SEE AREAS WHICH CONTAIN FLOOR TO CEILING HEIGHT
 PARTITIONS AND ALSO ANY WALLS THAT EXCEED 80%.(EXAMPLE,
 PLEASE SEE THE BATHROOMS WHICH INDICATE THE ADA STALLS
 WHICH APPEAR TO HAVE WALLS AND THE DEVICES AS SHOWN MAY
 NOT PROVIDE COVERAGE INTO THESE TWO AREAS. LIGHTING
 WHICH TURNS OFF WHILE PERSONS ARE IN AREAS WHICH CREATE
 A SAFETY ISSUE SHOULD BE ADDRESSED.
 PLEASE PROVIDE REVISED ENERGY CALCULATIONS AND LIGHTING
 POWER DENSITIES AS REQUIRED. PLANS STATE THE CODE,
 WHICH IS NOT ACCEPTABLE IN LIEU OF REQUIRED DESIGNS FOR
 MINIMUM CODE COMPLIANCE.
 PLEASE SEE THE FOLLOWING SECTIONS AT A MINIMUM.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 13-415.1.AB.1.1, 13-415.2.
 ETC.
  
 8) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR
 MINIMUM LEVELS FOR FIRE ALARMS DEVICES TO BE STATED.
 PLEASE SEE THE LOCATIONS APPEAR TO MEET ADA
 REQUIREMENTS, HOWEVER MINIMUM LEVELS NEED TO BE
 STATED.
 IT IS KNOWN THAT THE FIRE ALARM SCOPE IS UNDER A
 SEPARATE PERMIT HOWEVER THE BASE PLANS ARE REQUIRED TO
 HAVE THE ADA COMPLIANCE SHOWN.
 ** PLEASE BE AWARE OF ANY CHANGES FROM BASE BUILDING
 AND BUILD OUT WHICH WILL NEED TO BE COORDINATED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-12-19 Cont ID  
Sent By mwennerg Date 2007-12-19 Time 13:22 Rev Time 0.00
Received By mwennerg Date 2007-12-19 Time 13:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-10-29 Cont ID  
Sent By mawillia Date 2007-10-29 Time 15:58 Rev Time 0.00
Received By mawillia Date 2007-10-29 Time 15:54 Sent To  
Notes
2007-10-29 15:58:20*****PROVISO*******
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;HOWEVER, THE APPROPIATE PLAN SHEET(S)
 TO BE FIRE-STAMPED PROVIDED THAT ALL OTHER PLAN REVIEWS
 HAVE BEEN SATISFIED.
  
  
 CAPT MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-03 Cont ID  
Sent By mwennerg Date 2007-07-03 Time 11:28 Rev Time 0.00
Received By mwennerg Date 2007-07-03 Time 11:28 Sent To  
Notes
2007-07-03 11:32:17***DENIED***
  
 1) PLEASE ADVISE IF EXIT DOOR THAT IS PART OF THE ONE
 (1) HOUR WALL IS RATED.
  
 2) IN ADDITION TO THE FIRE SPRINKLER REMODEL, SEPARATE
 SHOP DRAWINGS AND PERMIT IS REQUIRED FOR FIRE ALARM
 REMODEL.
  
 3) HANDRAILS ARE REQUIRED FOR BOTH SIDES OF RAMP WHERE
 HANDRAILS ARE REQUIRED.
  
 4) NEW FIRE/SMOKE DAMPERS TO BE TESTED FOR CLOSURE IN
 ACCORDANCE WITH UL 555 STANDARDS PRIOR TO FINAL
 INSPECTION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-06-05 Cont ID  
Sent By adarroug Date 2008-06-05 Time 10:27 Rev Time 0.00
Received By adarroug Date 2008-06-05 Time 10:27 Sent To M
Notes
2008-06-05 10:27:46TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-16 Cont ID  
Sent By adarroug Date 2008-05-16 Time 14:35 Rev Time 0.00
Received By adarroug Date 2008-05-16 Time 14:35 Sent To M
Notes
2008-05-16 14:35:41TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-16 Cont ID  
Sent By adarroug Date 2008-05-16 Time 14:31 Rev Time 0.00
Received By adarroug Date 2008-05-16 Time 14:30 Sent To  
Notes
2008-05-16 14:31:17TO "BOB"#1

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-10 Cont ID  
Sent By mmiller Date 2008-01-10 Time 16:25 Rev Time 0.00
Received By mmiller Date 2008-01-10 Time 16:24 Sent To  
Notes
2008-01-14 12:08:361/14/07---PLANS NEED AN ELECT. REV ONLY--TO "DPALMER
 DESK ADARROUGH
2008-01-10 16:25:06SENT TO BOB # 07 MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-12 Cont ID  
Sent By adarroug Date 2007-12-12 Time 16:39 Rev Time 0.00
Received By adarroug Date 2007-12-12 Time 16:39 Sent To  
Notes
2007-12-12 16:42:20TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 15:52 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 15:52 Sent To  
Notes
2007-10-19 08:38:54TO "BOB"#11
2007-10-11 15:52:51WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-03 Cont ID  
Sent By mwennerg Date 2007-07-03 Time 11:34 Rev Time 0.00
Received By mwennerg Date 2007-06-25 Time 10:14 Sent To AD
Notes
2007-06-25 13:20:19TO "BOB"#14
2007-06-25 10:15:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-06-06 Cont ID  
Sent By tgordon Date 2008-06-06 Time 08:25 Rev Time 0.45
Received By tgordon Date 2008-06-06 Time 08:25 Sent To  
Notes
2008-06-06 08:38:39**REVISION TO MECH. PLANS M1.1 AND M7.1**
  
 *** PROVISO ***
 1) RESTROOM CEILING TILES MUST FIT TIGHTLY TO PREVENT
 REST ROOM ODORS FROM ENTERING OPEN RETURN AIR PLENUM
 ABOVE CEILING, PER 2004 FBC 407.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-05-20 Cont ID  
Sent By tgordon Date 2008-05-20 Time 10:56 Rev Time 0.45
Received By tgordon Date 2008-05-20 Time 10:56 Sent To  
Notes
2008-05-20 11:00:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** REVISION TO MECHANICAL PLANS M1.1 AND M7.1 **
 *** DENIED ***
  
 1) THE SPACE ABOVE THE ACOUSTICAL CEILING IN THE LOCKER
 / RESTROOM CAN NOT BE USED AS AN OPEN RETURN AIR
 PLENUM, SEE 2004 FBC/M 407.1.
  
 2) 1641 WORTHINGTON RD. IS A SHELL BUILDING.IT DOES
 NOT YET HAVE A CO SO THE SHELL BUILDING DESIGN
 PROFESSIONALS (KAMM CONSULTING) WILL BE REQUIRED TO
 PROVIDE A SHOP DRAWING REVIEW STAMP ON ANY BUILD-OUT
 PLANS THAT ARE PREPARED BY DIFFERENT DESIGNERS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-12-13 Cont ID  
Sent By tgordon Date 2007-12-13 Time 09:02 Rev Time 0.30
Received By tgordon Date 2007-12-13 Time 09:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-10-24 Cont ID  
Sent By tgordon Date 2007-10-24 Time 11:50 Rev Time 0.45
Received By tgordon Date 2007-10-24 Time 11:50 Sent To  
Notes
2007-10-24 11:58:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NOT NOTED IN LAST REVIEW, PLEASE PROVIDE OUTDOOR AIR
 CALCULATIONS, PER FBC/M 403.2.
  
 2) NOTE: 1641 WORTHINGTON RD. IS A SHELL BUILDING.IT
 DOES NOT YET HAVE A CO SO THE SHELL BUILDING DESIGN
 PROFESSIONALS WILL BE REQUIRED TO PROVIDE A SHOP
 DRAWING REVIEW STAMP ON ANY BUILD-OUT PLANS THAT ARE
 PREPARED BY DIFFERENT DESIGNERS. SEE KAMM CONSULTING
 REVIEW DATED 9-17-07, PLEASE COMPLY.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-29 Cont ID  
Sent By tgordon Date 2007-06-29 Time 09:14 Rev Time 0.40
Received By tgordon Date 2007-06-29 Time 09:14 Sent To  
Notes
2007-06-29 09:48:14*** DENIED ***
 1) THE SPACE ABOVE THE ACOUSTICAL CEILING IN THE LOCKER
 / RESTROOM CAN NOT BE USED AS AN OPEN RETURN AIR
 PLENUM, SEE 2004 FBC/M 407.1.
  
 2) IF THAT SPACE COULD BE USED AS A PLENUM (BUT IT'S
 NOT) THEN TEF-1 EXHAUST DUCT COULD NOT BE IN THAT
 SPACE,SEE 2004 FBC/M 601.3.
  
 3) THE PRESSURIZED BATHROOM EXHAUST DUCT CAN NOT BE IN
 THE MECHANICAL ROOM DUE TO IT BEING AN OPEN PLENUM, SEE
 2004 FBC/M 601.4.
  
 4) THE BATHROOM EXHAUST DUCT ENTERING THE SHAFT IN THE
 MECHANICAL ROOM WILL NEED A FIRE AND SMOKE DAMPER, SEE
 2004 FBC/M 607.5.5.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-05-19 Cont ID  
Sent By jleech Date 2008-05-19 Time 09:30 Rev Time 0.00
Received By jleech Date 2008-05-19 Time 09:30 Sent To  
Notes
2008-05-19 09:31:33REVISED PLANS ADDED 30 GAL WATER HEATER

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-12-15 Cont ID  
Sent By jleech Date 2007-12-15 Time 11:49 Rev Time 0.00
Received By jleech Date 2007-12-15 Time 10:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-10-27 Cont ID  
Sent By jleech Date 2007-10-27 Time 08:12 Rev Time 0.00
Received By jleech Date 2007-10-27 Time 08:07 Sent To  
Notes
2007-10-27 08:26:37DENIED;
 1. SANITARY RISER DIAGRAM VENT FOR SHOWERS TO BE
 BETWEEN THE SHOWERS ON BRANCH DRAIN AS SHOWN ON THE
 FLAT DRAWING.
 2. HORIZONTAL DRY VENTS ARE NOT PERMITED IN THE
 DRAINAGE SYSTEM. FBC PLUMBING SECTION 905.3.
 3. WATER RISER DIAGRAM; ARE ALL TOILETS TO BE ON RRW OR
 JUST THE MEN'S ROOM TOILET AND URINAL? WOMAN'S ROOM
 TOILETS ARE ON POTABLE WATER.
 4. HANDICAP SHOWERS DO NOT HAVE THE CLEAR FLOOR SPACE
 REQUIRED. THE CLEAR FLOOR SPACE SHALL EXTEND 12" PAST
 THE SEAT. WALL IS IN THE WAY. SEE FBC BUILDING CHAPTER
 11, SECTION 11-4.21.2, AND FIGURE 35A.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-03 Cont ID  
Sent By jleech Date 2007-07-03 Time 08:04 Rev Time 0.00
Received By jleech Date 2007-07-03 Time 07:39 Sent To  
Notes
2007-07-03 08:20:11DENIED;
 1. MISSING REQUIRED ITEMS FROM PLANS, SEE ELECTRICAL
 PLAN REVIEW'S NOTES 1,2, AND 3.
 2. SHOW TURNING RADIUS IN THE HANDICAP STALLES ON FLOOR
 PLAN.
 3. HANDICAP URINAL NOT LISTED IN PLUMBING FIXTURE
 SCHEDULE. PLEASE LIST AN ELONGATED H/C APPROVED TYPE.
 4. PLEASE ADD NOTE ABOUT MARKING RECLAIMED WATER
 PIPING.
 5. SHOW HANDICAP SHOWERS ON FLOOR PLANS WITH SEAT,
 SHOWER HEAD ARM AND HAND RAILS.
 6. SANITARY RISER DIAGRAM IS MISSING VENT FOR THE
 SHOWERS. SEE FLAT DRAWING ON PAGE P1.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695