2007-06-29 17:49:40 | *** UNSAT *** |
| |
| *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET |
| SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE |
| REVIEWED AT THIS TIME. |
| |
| |
| 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE |
| CODES TO BE STATED ON PLANS. THIS WAS DONE ON |
| ARCHITECTURAL SHEETS HOWEVER THE ELECTRICAL SHEETS ARE |
| BLANK AT THIS LOCATION. |
| PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL |
| AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE |
| KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE |
| 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70. |
| PLEASE LIST THE FOLLOWING |
| 2004 FBC W/ 2006 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLEASE SEE ALL MEP SHEETS IN ALL SETS ARE |
| MISSING THE REQUIRED TITLE BLOCKS AND INFORMATION AS |
| REQUIRED UNDER THE FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.002. |
| PLEASE SEE MISSING INFORMATION IS ALSO REQUIRED UNDER |
| FLORIDA STATUTES 471.023. |
| ** THIS IS REQUIRED ON ALL MEP PLANS WHETHER OR NOT |
| COMMENT IS MADE BY OTHER TRADE REVIEWER(S). |
| |
| 3) NOTE: PLEASE KNOW THAT PERMIT APPLICATION WAS |
| SUBMITTED WITHOUT ANY SUITE/UNIT/SPACE #. PLEASE KNOW |
| THAT A COPY OF THE PERMIT APPLICATION HAS BEEN |
| FORWARDED TO THE ADDRESSING REVIEWER. ONCE THE |
| SUITE/UNIT/SPACE NUMBER HAS BEEN DETERMINED PLEASE BE |
| SURE THIS INFORMATION IS PLACED ON PLANS/TITLE BLOCKS. |
| FAC 61G15-23.002, 61G1-16.004 |
| |
| 4) NOTE: PLEASE KNOW PLANS ARE BEING REVISED WHILE |
| THERE IS STILL AN ACTIVE PERMIT FOR THE SHELL BUILDING. |
| THE BASE SHELL BUILDING IS OF A DIFFERENT MEP DESIGN |
| PROFESSIONAL AND ANY AND ALL CHANGES AND REVISIONS MADE |
| TO BUILDING BY THE BUILD OUT DESIGNS AND WORK SHALL BE |
| REVIEWED BY THE BASE BUILDING ENGINEER OF RECORD. |
| (EXAMPLE: AS SHOP DRAWINGS) |
| *** IMPORTANT** |
| PLEASEALSO KNOW AS THERE ARE MANY ITEMS WHICH NOW |
| AFFECT THE BASE BUILDING PLANS, COORDINATION OFNOW |
| KNOWN LOADS FOR REVISED LOAD CALCULATIONS, KNOWN |
| CHANGES FOR ENERGY CALCULATIONS, RISER INFORMATION, |
| PANEL SCHEDULES ETC WILL ALL NEED TO BE GIVEN TO THE |
| BASE BUILDING ENGINEER OF RECORD TO REVISED THE BASE |
| BUILDING PLANS AND ENERGY CALCULATIONS. |
| THERE ARE ITEMS WHICH WILL NOW AFFECT THIS. |
| FBC 106.1.2, 106.3.5.1.2, |
| NEC 408.4, 215.5, 230, 220, 240, 310 ETC. |
| FBC CHAPTER 13, 13-415.1.AB.1.1, 13-415.2 ETC |
| |
| 5) NOTE: PLEASE SEE THE PANELS AS SHOWN ON PLANS ARE |
| NOT ALL SHOWN ON THE SHEETS WHERE THE PANEL SCHEDULES |
| ARE LOCATED. PLEASE CLARIFY THE MCB ON THE LOAD SIDE OF |
| THE TRANSFORMER AS ON BASE BUILDING PLANS. |
| 240.21, 408.36, 240.4, 310.16 ETC. |
| FBC 106.1.2 FOR COORDINATION OF PLANS. |
| |
| 6) NOTE: PLEASE COMPLETE AND INDICATE ALL CIRCUITING ON |
| PLANS WITH PANEL SCHEDULES. |
| PLEASE SEE FOR EXAMPLE SOME OF THE EXIT LIGHTS WHICH |
| ARE NOTED TO BE CIRCUITED TO THE LOCAL LIGHTING CIRCUIT |
| DO NOT ACTUALLY SHOW THIS. THIS IS SHOWN FOR EMERGENCY |
| LIGHTS AS REQUIRED PER 700.12F BUT NOT FOR ALL EXIT |
| LIGHTS. |
| PLEASE COMPLETE. |
| FBC 106.1.2, 106.3.5.1.2. |
| NEC 408.4. |
| |
| 7)NOTE: PLEASE SUBMIT PLANS FOR LIGHTING WHICH SHOWS |
| COMPLETED INFORMATION FOR CHAPTER 13 CODE COMPLIANCE. |
| PLEASE SEE SOME OF THE DEVICES ON PLANS INDICATE A NOTE |
| * TO BE CHOSEN BY MANUFACTURES RECOMMENDATION*. THIS IS |
| TO BE CHOSEN, DESIGNED, AND SHOWN AT THIS POINT. |
| DESIGNS FOR CODE COMPLIANCE ARE NOT LEFT TO THE |
| MANUFACTURE. |
| PLEASE STATE DEVICE TYPES. |
| PLEAS INDICATE MAXIMUM TIMES ON DEVICES CHOSEN. PLEASE |
| SEE AREAS WHICH CONTAIN FLOOR TO CEILING HEIGHT |
| PARTITIONS AND ALSO ANY WALLS THAT EXCEED 80%.(EXAMPLE, |
| PLEASE SEE THE BATHROOMS WHICH INDICATE THE ADA STALLS |
| WHICH APPEAR TO HAVE WALLS AND THE DEVICES AS SHOWN MAY |
| NOT PROVIDE COVERAGE INTO THESE TWO AREAS. LIGHTING |
| WHICH TURNS OFF WHILE PERSONS ARE IN AREAS WHICH CREATE |
| A SAFETY ISSUE SHOULD BE ADDRESSED. |
| PLEASE PROVIDE REVISED ENERGY CALCULATIONS AND LIGHTING |
| POWER DENSITIES AS REQUIRED. PLANS STATE THE CODE, |
| WHICH IS NOT ACCEPTABLE IN LIEU OF REQUIRED DESIGNS FOR |
| MINIMUM CODE COMPLIANCE. |
| PLEASE SEE THE FOLLOWING SECTIONS AT A MINIMUM. |
| 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| 13-415.1.AB.1.1, 13-415.2. |
| ETC. |
| |
| 8) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR |
| MINIMUM LEVELS FOR FIRE ALARMS DEVICES TO BE STATED. |
| PLEASE SEE THE LOCATIONS APPEAR TO MEET ADA |
| REQUIREMENTS, HOWEVER MINIMUM LEVELS NEED TO BE |
| STATED. |
| IT IS KNOWN THAT THE FIRE ALARM SCOPE IS UNDER A |
| SEPARATE PERMIT HOWEVER THE BASE PLANS ARE REQUIRED TO |
| HAVE THE ADA COMPLIANCE SHOWN. |
| ** PLEASE BE AWARE OF ANY CHANGES FROM BASE BUILDING |
| AND BUILD OUT WHICH WILL NEED TO BE COORDINATED. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |