Plan Review Details - Permit 07060724
Plan Review Stops For Permit 07060724
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-07-11 Cont ID  
Sent By mperson Date 2007-07-11 Time 13:41 Rev Time 0.45
Received By mperson Date 2007-07-11 Time 13:41 Sent To PC
Notes
2007-07-11 13:49:44****************PROVISO****************
 FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE
 GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF
 GENERATOR PLACEMENT.
 NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET
 CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES
 SHALL BE CAPPED GAS TIGHT.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 9,000 CUBIC FEET REQUIRED.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-11 Cont ID  
Sent By mperson Date 2007-07-11 Time 13:49 Rev Time 0.00
Received By mperson Date 2007-06-24 Time 14:55 Sent To  
Notes
2007-06-24 14:56:01TO "G" BOX