Plan Review Details - Permit 07060709
Plan Review Stops For Permit 07060709
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-06 Cont ID  
Sent By shill Date 2007-08-06 Time 18:24 Rev Time 0.00
Received By shill Date 2007-08-06 Time 18:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-27 Cont ID  
Sent By shill Date 2007-07-27 Time 13:29 Rev Time 0.00
Received By shill Date 2007-07-27 Time 13:29 Sent To  
Notes
2007-07-27 13:32:12****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 2.)SEE OPENING 12, DESIGN PRESSURE OF -31.8.FBC
 R301.2(2) REQUIRES A DEISGN PRESSURE OF -34.6 FOR 50SF,
 -36.7 FOR 20SF.THIS OPENING IS 45 SF.DESIGN
 PRESSURES CANNOT BE LESS THAN THE TABLE UNLESS YOU USE
 ENGINEERING.CHECK ALL OPENINGS AND REVISE ANCHORING
 AS NECESSARY.
  
 2ND REVIEW - THE PRESSURE ON THE INSTALLATION SCHEDULE
 WAS REVISED TO -32.2, SOFTWARE WIND PRESSURES IS STILL
 -31.8.BOTH PRESSURES ARE LESS THAN FBC R TABLE
 301.1.2.ALSO NOTE THAT THE DESIGN PRESSURE
 CALCULATIONS APPEAR TO USE THE PANEL SIZE RATHER THAN
 THE OPENING SIZE.PLEASE HAVE THE QUALIFIER CONTACT ME
 IF YOU NEED ASSISTANCE IN DETERMINING DESIGN PRESSURES.
 THIS COMMENT APPLIES TO ALL OF THE OPENINGS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-06 Cont ID  
Sent By shill Date 2007-07-06 Time 15:23 Rev Time 0.00
Received By shill Date 2007-07-06 Time 15:23 Sent To  
Notes
2007-07-06 15:26:12****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)CLARIFY HOW THE SPAN COULD BE THE SAME SIZE AS THE
 OPENING.
  
 2.)SEE OPENING 12, DESIGN PRESSURE OF -31.8.FBC
 R301.2(2) REQUIRES A DEISGN PRESSURE OF -34.6 FOR 50SF,
 -36.7 FOR 20SF.THIS OPENING IS 45 SF.DESIGN
 PRESSURES CANNOT BE LESS THAN THE TABLE UNLESS YOU USE
 ENGINEERING.CHECK ALL OPENINGS AND REVISE ANCHORING
 AS NECESSARY.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-03 Cont ID  
Sent By adarroug Date 2007-08-03 Time 14:39 Rev Time 0.00
Received By adarroug Date 2007-08-03 Time 14:39 Sent To B
Notes
2007-08-03 14:40:15TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 14:16 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 14:16 Sent To B
Notes
2007-07-18 14:16:53TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-06 Cont ID  
Sent By shill Date 2007-07-06 Time 15:26 Rev Time 0.00
Received By shill Date 2007-06-24 Time 12:30 Sent To  
Notes
2007-06-24 12:30:29TO "MISC" BOX#1