Plan Review Details - Permit 07060649
Plan Review Stops For Permit 07060649
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-09 Cont ID  
Sent By mjacobs Date 2007-08-09 Time 13:44 Rev Time 0.00
Received By mjacobs Date 2007-08-09 Time 10:44 Sent To PC
Notes
2007-08-09 13:43:59BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
  
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRNGTH
 ASTM D3787 150 LB BALL BURST STRENGTH
  
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-31 Cont ID  
Sent By mjacobs Date 2007-07-31 Time 12:14 Rev Time 0.00
Received By mjacobs Date 2007-07-31 Time 11:31 Sent To PC
Notes
2007-07-31 12:14:08BUILDING PLAN REVIEW
 PERMIT: 07060649
 ADD: 2172 TIGRIS DR
 CONT: CUSHING POOLS
 TEL: (561)198-1441
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1) FBC 106.1.1ALL INFORMATION SHALL BE OF SUFFICIENT
 CLARITY. THE INFORMATION SUBMITTED HAS CONFLICTING
 INFORMATION ABOUT THE SIZE OF THE POOL.SUBMIT TWO NEW
 COMPLETE SETS OF DRAWINGS AND ONE OLD SET FOR REVIEW.
 REMOVE THE OLD SHEET AND REPLACE IT WITH THE NEW
 SHEET.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-13 Cont ID  
Sent By mjacobs Date 2007-07-13 Time 17:54 Rev Time 0.00
Received By mjacobs Date 2007-07-13 Time 17:14 Sent To PC
Notes
2007-07-13 17:54:31BUILDING PLAN REVIEW
 PERMIT: 07060649
 ADD: 2172 TIGIS DR.
 CONT: CUSHING POOLS CONST. INC.
 TEL: (561)798-1441
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1) ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE WITH 2006 FBC REVISIONS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-06-26 Cont ID  
Sent By choops Date 2007-06-22 Time 13:30 Rev Time 0.00
Received By btrobaug Date 2007-06-26 Time 11:37 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-07-10 Cont ID  
Sent By mperson Date 2007-07-10 Time 14:56 Rev Time 0.00
Received By mperson Date 2007-07-10 Time 14:56 Sent To B
Notes
2007-07-10 14:56:53NOTE: THERE IS NO POOL HEATER.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 16:05 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 16:05 Sent To Z
Notes
2007-08-02 16:05:51TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-24 Cont ID  
Sent By adarroug Date 2007-07-24 Time 15:33 Rev Time 0.00
Received By adarroug Date 2007-07-24 Time 15:33 Sent To Z
Notes
2007-07-24 15:33:29TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-07-13 Time   Rev Time 0.00
Received By adarroug Date 2007-06-22 Time 09:44 Sent To  
Notes
2007-06-22 09:45:04TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-07-10 Cont ID  
Sent By mperson Date 2007-07-10 Time 14:55 Rev Time 0.33
Received By mperson Date 2007-07-10 Time 14:55 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2007-08-06 Cont ID  
Sent By choops Date 2007-08-06 Time 10:48 Rev Time 0.00
Received By choops Date 2007-08-06 Time 10:48 Sent To B
Notes
2007-08-06 10:49:16SENT TO MJ

Review Stop Z ZONING
Rev No 2 Status F Date 2007-07-24 Cont ID  
Sent By choops Date 2007-07-24 Time 16:54 Rev Time 0.00
Received By choops Date 2007-07-24 Time 16:54 Sent To B
Notes
2007-07-24 16:56:24***FAILED***
  
  
 1)AS THE POOL EQUIPMENT LOCATION HAS CHANGED AND NO
 SETBACK DIMENSION PROVIDED...PLANS SHALL SHOW SETBACK
 DIMENSION FROM PROPOSED POOL EQUIPMENT TO THE PROPERTY
 LINES.
  
 2)(REPEAT COMMENT) AS THE SURVEY DOES NOT SHOW AN
 EXISTING FENCE COMPLETELY SURROUNDING THE POOL, A FENCE
 PERMIT SHALL BE SUBMITTED CONCURRENTLY AND SHALL
 CONFORM TO THE MINIMUM STANDARDS PROVIDED BELOW.
  
 AS PER THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
  
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 3)PLEASE PROVIDE AN ACC (ARCHITECTURAL CONTROL
 COMMITTEE) APPROVAL FROM RIVERWALK HOA.
  
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-22 Cont ID  
Sent By choops Date 2007-06-22 Time 13:30 Rev Time 0.00
Received By choops Date 2007-06-22 Time 13:30 Sent To E
Notes
2007-06-22 13:37:50***FAILED***
  
  
 1)SETBACKS ARE INSUFFICIENT.MEASURED FROM WATER'S
 EDGE, THERE MUST BE A 5' SETBACK TO BOTH THE SIDES AND
 THE REAR PROPERTY LINE.ALSO, PLEASE INDICATE DISTANCE
 FRO PRINCIPAL STRUCTURE TO WATER'S EDGE (MUST BE A
 MINIMUM OF 4').
  
 2)AS THE SURVEY DOES NOT SHOW AN EXISTING FENCE
 SURROUNDING THE POOL, A FENCE PERMIT SHALL BE SUBMITTED
 CONCURRENTLY AND SHALL CONFORM TO THE MINIMUM STANDARDS
 PROVIDED BELOW.
  
 AS PER THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION 94-304(D)(2)(B)+(C):
  
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720