2007-07-26 10:45:50 | BUILDING REVISION CHECKLIST: |
| 1- ROOF VENT: |
| A) ARCHITECT APPROVED ROOF VENT NOA 01-0614.05. THIS |
| NOA EXPIRED ON 08/16/2006.DADE COUNTY NOA'S SHALL |
| NOT BE VALID AFTER EXPIRATION DATE.SEE SECOND |
| PARAGRAPH ON COVER PAGE OF NOA SUBMITTED. |
| |
| B)ARCHITECT'S NOTE: "CONTRACTOR RESPONSIBLE FOR |
| PROVIDING REQ'D VENTING PER CALCULATIONS ON DRAWINGS". |
| IT'S THE ARCHITECT'S RESPONSIBILITY TO VERIFY IFTHE |
| NUMBER OFVENTS SHOWN ON PLANSMEET THE VENTING |
| CALCULATIONS USING THE REVISED VENT,NOT THE |
| CONTRACTOR.CONTRACTOR'SRESPONSIBILITYIS TO |
| INSTALLNUMBER OF VENTS VENTSAS SPECIFIED ON PLANS. |
| NOT TO MAKE CALCULATIONS.IF REVISEDVENT DOESN'T |
| MEET THE VENTING CALCULATIONS, THEN REVISE PLANS AS |
| REQUIRED. |
| |
| C) THERE ARE TWO DIFFERENT REVIEW STAMPS. ONE OF |
| THEM IS CLEAR THAT IS THE ARCHITECT'S REVIEW STAMP. |
| WHO'S REVIEW STAMP IS THE OTHER ONE.THE PURPOSE OF |
| THE REVIEW STAMP IS TO DISCLOSE WHO REVIEW IT. |
| OTHERWISE IT'S MEANINGLESS. |
| |
| ***NOTE: SAME COMMENT APPLIES TO SHINGLES PRODUCT |
| APPROVAL. |
| |
| 2- REVISION FEES ARE $50.00PLUS $10.00 PER ADDITIONAL |
| PAGE. OWES $80.00.INFORMATION SUBMITTED IS REVISED |
| SHEET A705, PLUS PRODUCT APPROVAL FOR SHINGLES, PLUS |
| PRODUCT APPROVAL FOR ROOF VENT. |
| |
| 3- PRODUCT APPROVAL FOR ROOF SHINGLES HAS THE |
| ARCHITECT'S REVIEW STAMP, BUT NOBODY SIGNED IT AND |
| DATED IT. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |