Plan Review Details - Permit 07060606
Plan Review Stops For Permit 07060606
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-04 Cont ID  
Sent By amorse Date 2007-12-04 Time 17:05 Rev Time 0.00
Received By amorse Date 2007-12-04 Time 17:04 Sent To PC
Notes
2007-12-04 17:41:33DENIED
  
 THE FOLLOWING COMMENT WERE NOT ADDRESSED ON THE 1ST
 REVIEW:
  
 3)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 4) THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 6)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
 ********THE PERSONS RESPONSIBLE FOR THE DRAWINGS MUST
 REVIEW AND APPROVE THE PRODUCTS TO BE USED*********
  
 8)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR TO SUBMITTAL
 *********SUBMIT ENERGY CALCULATIONS BASED ON THE
 CONSTRUCTION OF THE ADDITION, NOTE THAT NO INSULATION
 VALUE WAS GIVEN TO THE ROOF********
  
 10)TO CONFORM TO THE ZONING (SEE ZONING REVIEW)
 **********ZONING REVIEW COMMENTS MUST BE ADDRESSED
 BEFORE PROJECT CAN BE PERMITTED*********
  
 11)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
 **********PROVIDE FULL FLOOR PLAN TO SHOW
 COMPLIANCE***********
  
 13)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 NEW REVIEW COMMENTS FROM PRODUCT APPROVALS:
  
 1)PRODUCT APPROVALS WERE SUBMITTED FOR BOTH SINGLE
 HUNG IMPACT WINDOWS AND FIXED NON-IMPACT, PLEASE
 PROVIDE LOCATION,TYPE AND SIZE OF WINDOWS ON THE
 DRAWINGS.
  
 2)CHOOSE A ROOFING SYSTEM FROM THE PRODUCT APPROVAL,
 NON INSULATED WOOD DECKS ARE ON PAGES 17 & 18. PLEASE
 NOTE THAT THE DESIGN PRESSURES LISTED IN THE NOA DO NOT
 MEET THE REQUIREMENTS FOR THE PERIMETER AND CORNER
 ZONES AND THEREFORE CALCULATION MUST BE PROVIDED BY AN
 ARCHITECT, ENGINEER OR ROOFING CONSULTANT. INCLUDE
 THESE CALCULATIONS WITH THE PRODUCT APPROVAL.
  
 3)THE SYMBOLS 2 & 2A ON THE FOOTING SCHEDULE SEEM TO
 BE THE OPPOSITE OF THE FOUNDATION PLAN AND WALL
 SECTIONS PLEASE CLARIFY
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By amorse Date 2007-07-11 Time 17:33 Rev Time 0.00
Received By amorse Date 2007-07-11 Time 17:33 Sent To PC
Notes
2007-07-11 17:57:38 
  
 DENIED
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES. NOTE FEES ARE DUE
 IN THE AMOUNT OF $ 1.44 FOR STATE OF FLORIDA RADON FEE
  
 3)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 4) THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 5)NO PRODUCT APPROVALS WERE SUBMITTED FOR ROOF
 MEMBRANE, AND CONSTRUCTION STRAPS/TIES
  
 6)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 7)ALTHOUGH THE DRAWINGS SHOW THE MINIMUM DEPTH OF
 FOUNDATION ON THE WALL SECTIONS PER R403.1.4 FBC RES.
 PLEASE SEE THAT THE ELEVATION DRAWINGS ON A/2 SHOWS THE
 FINISHED GRADE AT 36" BELOW FIN FLOOR AND THE
 MONOLITHIC FOUNDATION IS ONLY 20" DEEP.
  
 8)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 9)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES.
  
 10)TO CONFORM TO THE ZONING (SEE ZONING REVIEW)
 REGULATIONS THE ADDITION WALL THAT TIES INTO THE
 EXISTING BUILDING ON THE SOUTH SIDE WILL BE REQUIRED TO
 JOG OVER SO THAT THE BACK CORNER IS NOT ANY CLOSER TO
 THE PROPERTY LINE THAN THE EXISTING BUILDING 3.43 FEET.
 SEE THAT THE PROPOSED DISTANCE WOULD BE 3.31 THUS
 INCREASING THE NONCONFORMITY.
  
 11)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
  
 12)PROVIDE MIN ROOF SHEATHING ATTACHMENT
 PER R803.2.3.1 FBC RES. SHALL BE 8D RING SHANK AT 6"
 O/C EDGES AND FIELD AND 4" O/C EDGES AND FIELD IN ZONES
 2 & 3
  
 13)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-08 Cont ID  
Sent By btrobaug Date 2007-11-08 Time 16:20 Rev Time 0.00
Received By btrobaug Date 2007-11-08 Time 16:03 Sent To M
Notes
2007-11-08 16:20:32 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 COMMENTS FROM PREVIOUS REVIEW;
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.* NO SIGNATURES.
  
 2} INDICATE THAT THE BATHROOM CIRCUITS COMPLY WITH
 210.11(C)(3).* STILL NOT LISTED ON THE SCHEDULE.
  
 3} INDICATE WHAT THE APPLIANCE IN THE BATHROOM IS.
 THERE IS NO SYMBOL IN THE LEGEND INDICATING VOLTAGE OR
 AMPERAGE FOR THAT APPLIANCE.
  
 4} THE PANEL SCHEDULE IS INCOMPLETE. IF PROVIDING ONE
 IT MUST BE COMPLETE PER 106.3.5.4(8), FBC AS AMENDED.
  
 6} THERE IS A CONDENSING UNIT ON THE PLAN. LOCATE THE
 AHU IF THIS IS BEING INSTALLED UNDER THE SCOPE OF THIS
 PERMIT. SHOW COMPLIANCE WITH 210.63 FOR THE RECEPTACLE
 AND 110.26 FOR THE DISCONNECT.
  
 7} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT.
  
 NEW COMMENTS THIS REVIEW:
  
 1} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND RECORD RETENTION PER
 106.1.3 FBC AS AMENDED.
  
 2 ]SUBMIT WRITTEN RESPONSE TO THE COMMENTS MADE IN THIS
 REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-22 Cont ID  
Sent By btrobaug Date 2007-06-22 Time 07:46 Rev Time 0.00
Received By btrobaug Date 2007-06-22 Time 07:02 Sent To M
Notes
2007-06-22 07:46:10 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 2} INDICATE THAT THE BATHROOM CIRCUITS COMPLY WITH
 210.11(C)(3).
  
 3} INDICATE WHAT THE APPLIANCE IN THE BATHROOM IS.
 THERE IS NO SYMBOL IN THE LEGEND INDICATING VOLTAGE OR
 AMPERAGE FOR THAT APPLIANCE.
  
 4} THE PANEL SCHEDULE IS INCOMPLETE. IF PROVIDING ONE
 IT MUST BE COMPLETE PER 106.3.5.4(8), FBC AS AMENDED.
  
 5} INDICATE IF THE SERVICE IS NEW OR EXISTING. REMOVE
 NOTES AND SCHEMATICS THAT ARE NOT RELEVANT TO THE WORK
 TO BE PERMITTED. IF INSTALLED UNDER THIS PERMIT, PER
 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 6} THERE IS A CONDENSING UNIT ON THE PLAN. LOCATE THE
 AHU IF THIS IS BEING INSTALLED UNDER THE SCOPE OF THIS
 PERMIT. SHOW COMPLIANCE WITH 210.63 FOR THE RECEPTACLE
 AND 110.26 FOR THE DISCONNECT.
  
 7} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 09:24 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 09:24 Sent To Z
Notes
2007-11-06 09:24:19TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-11 Cont ID  
Sent By adarroug Date 2007-07-11 Time 09:22 Rev Time 0.00
Received By adarroug Date 2007-06-20 Time 11:26 Sent To  
Notes
2007-06-20 11:26:18TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-09 Cont ID  
Sent By tgordon Date 2007-11-09 Time 11:28 Rev Time 0.25
Received By tgordon Date 2007-11-09 Time 11:28 Sent To P
Notes
2007-11-09 11:37:05PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 6-22-07.MECHANICAL PERMIT
 #07060608 HAS BEEN APPLIED FOR BUT NO MECHANICAL PLANS
 WERE SUBMITTED FOR REVIEW. PLEASE SUBMIT MECHANICAL
 PLANS FOR REVIEW, PER 2004 FBC CITY OF WPB AMEND.
 106.3.5.4 (10).
  
 2) AS NOTED IN LAST REVIEW 6-22-07. SUBMIT ENERGY
 CALCULATIONS, PER 2004 FBC 13-101.2.2.
  
 3) AS NOTED IN LAST REVIEW 6-22-07. PLANS SHOW NO ATTIC
 INSULATION, SEE 2004 FBC 13-604.1.ABC.1 PLEASE COMPLY.
  
 4) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-22 Cont ID  
Sent By tgordon Date 2007-06-22 Time 10:51 Rev Time 0.25
Received By tgordon Date 2007-06-22 Time 10:51 Sent To P
Notes
2007-06-22 11:04:48*** DENIED ***
 1) MECHANICAL PERMIT #07060608 HAS BEEN APPLIED FOR BUT
 NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY
 OF WPB AMEND. 106.3.5.4 (10).
  
 2) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.2.
  
 3) PLANS DO NOT SHOW ANY ATTIC INSULATION, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-11-28 Cont ID  
Sent By jleech Date 2007-11-28 Time 07:52 Rev Time 0.00
Received By jleech Date 2007-11-28 Time 07:28 Sent To B
Notes
2007-11-28 07:58:37DENIED;
 SANITARY RISER DIAGRAM DOES NOT MATCH FLOOR PLAN.
 AUTOMATIC CLOTHES WASHER REQUIRES A VENT WITH A
 CLEANOUT AT 48" AFF.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-10 Cont ID  
Sent By jleech Date 2007-07-10 Time 08:28 Rev Time 0.00
Received By jleech Date 2007-07-10 Time 08:28 Sent To B
Notes
2007-07-10 08:36:56DENIED;
 1. RISER DIAGRAM DOES NOT MATCH FLOOR PLAN.
 2. AUTOMATIC CLOTHES WASHER NOT SHOWN ON RISER DIAGRAM.
 BRANCH DRAIN IS REQUIRED TO BE 3" WITH A CLEANOUT ON
 VENT STACK AT 48" ABOVE FINISH FLOOR.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status F Date 2007-11-08 Cont ID  
Sent By choops Date 2007-11-08 Time 08:44 Rev Time 0.00
Received By choops Date 2007-11-08 Time 08:44 Sent To E
Notes
2007-11-08 08:50:46***FAILED - RESUB #1***
  
  
 1)A MISINTERPRETATION OF THE CODE WAS MADE ON THE
 PREVIOUS REVIEW.PURSUANT TO THE CITY OF WEST PALM
 BEACH ZONING AND LAND DEVELOPMENT REGULATIONS, SECTION
 94-513(A)(2):
 NONCONFORMING STRUCTURES OR BUILDINGS SHALL NOT BE
 IMPROVED, CONSTRUCTED, ENLARGED, OR ALTERED IN ANY
 MANNER TO CREATE A NEW NONCONFORMITY OR TO INCREASE AN
 EXISTING NONCONFORMITY, BUT MAY BE IMPROVED,
 CONSTRUCTED, ENLARGED, OR ALTERED AS LONG AS NO NEW
 NONCONFORMITY IS CREATED OR AN EXISTING NONCONFORMITY
 INCREASED.
  
 THE PROPOSED ADDITION MUST MEET CURRENT SETBACK
 REQUIREMENTS SET FORTH IN SECTION 94-72(A)(2):
 MINIMUM SETBACK REQUIREMENTS:SIDE = FIVE FEET MINIMUM
 WITH A TOTAL OF FIFTEEN FEET BETWEEN THE TWO SIDES.
 REAR = 15 FEET OR 10% OF THE LOT DEPTH WHICHEVER IS
 LESS.
  
 NOTE:MAY NOT BUILD ANYTHING OUTSIDE OF PROPERTY
 LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-21 Cont ID  
Sent By choops Date 2007-06-21 Time 08:44 Rev Time 0.00
Received By choops Date 2007-06-21 Time 08:44 Sent To E
Notes
2007-06-21 08:55:33***FAILED***
  
  
 1)IS THE A/C UNIT SHOWN, NEW OR EXISTING?IF NEW,
 IT MUST BE RELOCATED TO REAR OF PROPERTY, IT MAY NOT
 SIT DIRECTLY ON SIDE PROPERTY LINE.
  
 2)AS THIS IS AN EXISTING NON-CONFORMING BUILDING, AS
 PER THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION 94-513(A)(2):
 NONCONFORMING STRUCTURES OR BUILDINGS SHALL NOT BE
 IMPROVED, CONSTRUCTED, ENLARGED, OR ALTERED IN ANY
 MANNER TO CREATE A NEW NONCONFORMITY OR TO INCREASE AN
 EXISTING NONCONFORMITY, BUT MAY BE IMPROVED,
 CONSTRUCTED, ENLARGED, OR ALTERED AS LONG AS NO NEW
 NONCONFORMITY IS CREATED OR AN EXISTING NONCONFORMITY
 INCREASED.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720