Plan Review Details - Permit 07060602
Plan Review Stops For Permit 07060602
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-31 Cont ID  
Sent By jwitmer Date 2007-07-31 Time 20:11 Rev Time 0.77
Received By jwitmer Date 2007-07-31 Time 20:04 Sent To  
Notes
2007-07-31 20:57:15TEMP SALES 915 S DIXIE 07060602
 BUILDING PLAN REVIEW
 PERMIT: 07060602
 ADD: 915 S DIXIE HWY
 CONT: POPPER & ASSOCIATES AUTOMOTIVE
 TEL: (561)719-7131
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) THE PERMIT APPLICATION INDICATES THIS STRUCTURE IS
 TO BE TEMPORARY IN NATURE. BY DEFINITION THIS IS :
 107.1 GENERAL.THE BUILDING OFFICIAL IS AUTHORIZED TO
 ISSUE A PERMIT FOR TEMPORARY STRUCTURES AND TEMPORARY
 USES. SUCH PERMITS SHALL BE LIMITED AS TO TIME OF
 SERVICE, BUT SHALL NOT BE PERMITTED FOR MORE THAN 180
 DAYS. THE BUILDING OFFICIAL IS AUTHORIZED TO GRANT
 EXTENSIONS FOR DEMONSTRATED CAUSE.
 107.2 CONFORMANCE. TEMPORARY STRUCTURES AND USES SHALL
 CONFORM TO THE STRUCTURAL STRENGTH, FIRE SAFETY, MEANS
 OF EGRESS, ACCESSIBILITY, LIGHT, VENTILATION AND
 SANITARY REQUIREMENTS OF THIS CODE AS NECESSARY TO
 ENSURE THE PUBLIC HEALTH, SAFETY AND GENERAL WELFARE.
 PLEASE HAVE THE OWNER WRIGHT A NOTIRIZED LETTER
 INDICATING THAT THEY ARE AWARE A TEMPORARY STRUCTURE
 WILL BE ALLOWED FOR NO MORE THAN 180 DAYS.
  
 4) PLEASE PROVIDE A SITE PLAN PROVIDING THE FOLLOWING
 INFORMATION: AN ACCESSIBLE SITE SHALL MEET THE
 FOLLOWING MINIMUM REQUIREMENTS:
 (1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE BOUNDARY OF
 THE SITE FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE
 PARKING SPACES, PASSENGER LOADING ZONES IF PROVIDED,
 AND PUBLIC STREETS OR SIDEWALKS, TO AN ACCESSIBLE
 BUILDING ENTRANCE.
 (2)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS,
 ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND
 ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
 (3)ALL OBJECTS THAT PROTRUDE FROM SURFACES OR
 POSTS INTO CIRCULATION PATHS SHALL COMPLY WITH SECTION
 11-4.4 .
 (4)GROUND SURFACES ALONG ACCESSIBLE ROUTES AND IN
 ACCESSIBLE SPACES SHALL COMPLY WITH SECTION 11-4 (5)
 PLEASE PROVIDE THE DISABLED PARKING AND ACCESS AISLE.
  
 5) SITE PLAN THAT INDICATES THE TRAILER LOCATION ALSO
 INDICATES THE USE OF STAIRS, RAMPS AND LANDINGS PLEASE
 PROVIDE PLANS, DETAILS & DIMENSIONS FOR HOW THIS WILL
 BE ACCOMPLISHED.
 A) 11-4.8.2 SLOPE & RISE. THE LEAST POSSIBLE SLOPE
 SHALL BE USED FOR ANY RAMP. THE MAXIMUM SLOPE FOR A
 RAMP IN NEW CONSTRUCTION SHALL BE 1 TO 12. THE MAXIMUM
 RISE FOR RUN SHALL BE
 30" (SEE FIGURE 16).
 B) 11-4.8.3. CLEAR WIDTH. THE MINIMUMCLEAR WIDTH
 OF A RAMP SHALL BE 36". EXCEPTION: RAMPS THAT ARE PART
 OF A REQUIRED MEANS OF EGRESS SHALL NOT BELESS THAN
 44 INCHES WIDE.
 C) 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS
 SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH
 RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL
 CLEARENCE.
 D) 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE
 GREATER THAN 6" OR A HORIZONTAL PROJECTION GREATER THAN
 72", THEN IT SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 6) FOR THE SITE BUILT STAIRS LANDINGS AND RAMP PLEASE
 PROVIDE THE FOLLOWING DESIGN INFORMATION ON THE PLAN:
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF
  
 7) SHEETS 1-3 OF THE GE CAPITAL MODULAR SPACE ARE
 REVIEWED BY THE STATE. SHEET 4 NOTE 4 INDICATES THAT
 THE MINIMUM SAFE BEARING VALUE IS TO BE 2000 PSF AND TO
 BE VARIFIED BY THE BUILDINGS OWNER. PLEASE PROVIDE(2)
 ORIGINAL SIGNED & SEALED SOILS REPORT.1802.2.1
 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 8) SHEET # 4 IS ALSO TO BE DESIGNED TO THE CURRENT 2004
 FBCWHICH RECONIZES ASCE 7-02 NOT THE 7-98. PLEASE
 CORRECT.
  
 9) PLANS INDICATE THE USE OF 4" THICK ABS PADS OR 4X16
 CONCRETE PADS. FOR TEMPORARY STRUCTURES THIS BUILDING
 IS STILL TO CONFORM TO THE FBC 107.2 CONFORMANCE.
 TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS,
 ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY
 REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE THE
 PUBLIC HEALTH, SAFETY AND GENERAL WELFARE. THE
 FOUNDATION SHALL BE 12" BELOW GRADE,1805.2 DEPTH OF
 FOOTINGS.
 THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED
 GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE
 APPLICABLE, THE DEPTH OF FOOTINGS SHALL ALSO CONFORM TO
 SECTIONS 1805.2.1 THROUGH 1805.2.3 .
  
 10) PLEASE INDICATE IF THE DESIGN PROFESSIONAL IS GOING
 TO PROVIDE A PERMANENT FOUNDATION AND STEM WALL OR IF
 OTHER MATERIALS AND METHODS ARE TO BE EMPLOYED? 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 12) THE PERMIT VALUATION APPEARS TO BE CONSIDERALLY
 LOW, IF NOT CORRECTED THE CITY WILL USE MARSHALL AND
 SWIFT TO EVALUATE WHAT THE PERMIT FEES WILL BE.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-02 Cont ID  
Sent By dpalmer Date 2007-07-02 Time 07:18 Rev Time 0.00
Received By dpalmer Date 2007-07-01 Time 12:03 Sent To I
Notes
2007-07-02 07:18:29 
  
 *** UNSAT ***
  
  
 *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME.
  
  
 1) NOTE: PLEASE SUBMIT AN ELECTRICAL RISER DIAGRAM FOR
 HOOK UP OF OFFICE TRAILERS.
 PLEASE INDICATE SERVICE SIZE, CONDUCTOR SIZES, CONDUIT
 SIZES, GROUNDING, AIC RATINGS, GROUNDING AT TRAILERS,
 DISCONNECTS MAY ALSO BE REQUIRED AT THE TRAILERS
 DEPENDING ON THE LOCATION OF SERVICE AND UNITS. PLEASE
 SEE 215.5,230.70,230.72,240.4,310.16,250.50, 550 NEC.
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE SEE POSSIBLE BUILDING/ZONING REVIEW
 COMMENTS AS THE LOCATION OF THE TRAILER SEEMS TO BE ON
 A SEPARATE PROPERTY THAN THE APPLIED LOCATION. IF
 ADDRESS CHANGES PLEASE BE SURE TO ADJUST TITLES BLOCKS
 AND PERMIT APPLICATION.
  
 3) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT,
 DESIGN COST ETC EVEN IF ANY OF THESE ARE WONER
 SUPPLIED. FBC 108.3. PLEASE ADJUST APPLIED VALUATION.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-01 12:04:132007-07-01 12:04:13
 REMOVED FROM INCOMING, WILL RETURN ONCE ELEC REVIEW IS
 COMPLETED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-08-09 Cont ID  
Sent By mawillia Date 2007-08-09 Time 08:58 Rev Time 0.00
Received By mawillia Date 2007-08-08 Time 22:27 Sent To  
Notes
2007-08-08 23:05:55*****DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.THE ERECTING AND/OR INSTALLATION OF THE STRUCTURE
 SHALL IN NO WAY INTERFERE OR HINDER EMERGENCY RESPONSE
 ACCESS TO THE SAID PROPERTY, THE BUILDING(S), OR
 VICINITY THEREOF (INCLUDING STREETS, FIRE LANES, ETC).
  
 3.THE PROJECT ADDRESS (OR ASSIGNED ADDRESS) SHALL BE
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 4.DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE
 EXTERIOR ELEVATION TO BE PLAINLY VISIBLE FROM SOUTH
 DIXIE HIGHWAY.AS PER WEST PALM BEACH CODE, THE
 NUMBERS SHALL BE NO LESS THAN SIX INCHES IN HEIGHT AND
 NO LESS THAN ONE INCH IN WIDTH.
  
 5.NO EMERGENCY LIGHTING AND ONLY ONE EXIT LIGHT SHOWN
 ALTHOUGH IT APPEARS THAT THERE ARE TWO EXIT DOORS.
 PLEASE EXPLAIN.
  
 6.PROVIDE PRESCIPTIVE STRENGHT FOR STAIR
 HANDRAILS/GUARDRAILS.
  
 7.OUTSIDE STAIRS, RAMPS, AND LANDINGS SHALL BE SLIP
 RESISTANT AND ALSO SHALL BE DESIGNED TO MINIMIZE WATER
 ACCUMULATION ON THEIR SURFACES.
  
 8.SHOW/DISPLAY THE LOCATION OF THE 2A:10BC FIRE
 EXTINGUISHER(S) WHICH SATIFIES THE 75' TRAVEL
 DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED;PLEASE BE ADVISED THAT AS ADDITIONAL
 INFORMATION IS RECEIVED, ADDITIONAL COMMENTS MAY APPEAR
 THAT WERE NOT PART OF THIS REVIEW.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-09 Cont ID  
Sent By mawillia Date 2007-08-09 Time 09:00 Rev Time 0.00
Received By mawillia Date 2007-06-20 Time 13:20 Sent To  
Notes
2007-07-03 11:00:58TO "COMM" BD#51
2007-06-20 13:20:46WAITING FOR "COMM" BD

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-17 Cont ID  
Sent By kstevens Date 2007-07-17 Time 06:49 Rev Time 0.00
Received By kstevens Date 2007-07-16 Time 19:06 Sent To  
Notes
2007-07-17 06:54:29DENIED
 REFERENCE: FBC-2004 W/2006 AMENDMENTS
 FBC-2004 CHAPTER 1
  
 1. SURVEY/SITE PLANS SHALL SHOW THE WATER METER, RPZV
 BACKFLOW ON THE WATER SERVICE, WATER SERVICE, SANITARY
 SEWER FROM THE OFFICE TRAILERS & SEWER CONNECTION.
 SECTIONS 106.1.1 & 106.1.2.--IF A HOLDING TANK FOR
 THE SANITARY WASTE/SOIL, THEN A PERMIT FROM THE HEALTH
 DEPT IS REQUIRED AND SHALL BE SUBMITTED WHEN
 RESUBMITTING FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-27 Cont ID  
Sent By lfranco Date 2007-07-30 Time 15:40 Rev Time 0.00
Received By lfranco Date 2007-07-23 Time 18:41 Sent To  
Notes
2007-07-30 17:10:44PLANNING AND ZONING:**** FAILED ****
  
 1.PROVIDE RESPONSES TO COMMENTS IN WRITING.
  
 2.THE PROPERTY ON THE APPLICATION IS PART OF THE PALM
 BEACH MOTORCARS, ACCORDING TO THE PROPERTY APPRAISER'S
 OFFICE AND OUR RECORDS, THESE PROPERTIES ARE NOT
 UNIFIED.THE OWNER SHALL PROVIDE A COPY OF A RECORDED
 UNITY OF TITLE, PRIOR TO APPROVAL BY THE PLANNING AND
 ZONING DEPARTMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL:(561) 822-1443
 EMAIL: [email protected]