Plan Review Details - Permit 07060577
Plan Review Stops For Permit 07060577
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-08 Cont ID  
Sent By jgomez Date 2007-08-08 Time 10:49 Rev Time 0.00
Received By jgomez Date 2007-08-08 Time 10:43 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By jgomez Date 2007-07-12 Time 10:52 Rev Time 0.00
Received By jgomez Date 2007-07-12 Time 10:52 Sent To PC
Notes
2007-07-12 11:13:41BUILDING REVIEW CHECKLIST:
 1- ENGINEER IS MISSING ALL HIS INFORMATION IN ALL
 DRAWINGS AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE AND
 SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE CODE.
 ENGINEER TO REVIEW THIS SECTION AND PROVIDE TITLE BLOCK
 WITH ALL THE REQUIRED INFORMATION.
  
 2- PROVIDE 2 COPIES OF PRODUCT APPROVALSAS REQUIRED
 BY DCA RULE 9B-72 FOR:
 A) STORM SHUTTERS. AND, MARK ON SHUTTER DRAWINGS
 SPECIFIC MOUNTING CONDITIONS (EG: WALL MOUNTED) AND
 SPECIFIC ANCHOR TYPE AND SPACING TO USED.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 B) ALL SIMPSON CONNECTORS SPECIFIED ON PLANS BY THE
 ENGINEER.
 ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE
 AND PAGE WHERE CONNECTOR IS SHOWN TO SAAVE PAPER AND
 MONEY.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 4-DRAWING 2 OF 3 CALLS FOR NEW R19 INSULATION ON 2X4
 WALLS.R19 CAN'T BE INSTALLED IN 2X4 WALLS BECAUSE IT
 DOESN'T FIT.INSULATION CAN'T BE SQUEEZED.REVISE AS
 REQUIRED.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 5- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 6- ENERGY CALCULATIONS:
 A) WRONG FORM WAS USED. THIS IS NOT NEW CONSTRUCTION
 AND NO ALL THE WALL THROUGHOUT ENTIRE HOUSE ARE BEING
 CHANGED AND PROVIDED WITH INSULATION.PROVIDE REQUIRED
 FORM. SEE CHAPTER 13 FBC 2004 FOR ADEQUATE FORM TO BE
 USED.
 ***NOTE: MAKE SURE 2006 REVISED FORM IS USED.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER.
  
 C) WHICH CONCRETE EXTERIOR WALL IS GOING TO HAVE
 R4.1 INSULATION?
  
 C) OWNER/AGENTTO SIGN AND DATE AT BOTTOM OF FORM.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-07 Cont ID  
Sent By btrobaug Date 2007-08-07 Time 09:00 Rev Time 0.00
Received By btrobaug Date 2007-08-07 Time 07:43 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-22 Cont ID  
Sent By btrobaug Date 2007-06-22 Time 09:54 Rev Time 0.00
Received By btrobaug Date 2007-06-22 Time 08:24 Sent To M
Notes
2007-06-22 08:54:55 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC.
 THE ENGINEER HAVING DECLARED "STRUCTURAL ONLY" ON THIS
 SHEET, IS ASSUMED NOT RESPONSIBLE, AND SHOULD THEREFORE
 STRIKE OR REMOVE HIS SEAL AND SIGNATURE.
  
 2} } PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3}LOCATE THE SERVICE EQUIPMENT ON THE ELECTRICAL PLAN
 SO THAT COMPLIANCE WITH ARTICLE 230 CAN BE REVIEWED.
 INDICATE IF OVERHEAD OR UNDERGROUND ON THE RISER
 DIAGRAM.
  
 4} LOCATE THE A/C CONDENSER ON THE PLAN AND COMPLIANCE
 WITH 210.63.ALSO 110.26 FOR THE DOSCONNECT.
  
 5} PLEASE NOTE THAT THE DINING AREA IS REQUIRED TO BE
 ON A SMALL APPLIANCE CIRCUIT PER 210.52(B)(1). THE
 LIVING/DINING ROOMS MUST BE ON SEPERATE CIRCUITS.
  
 6} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), SEE REVIEWED SET.
  
 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1)
 AND 210.52 (A) (2), SEE FAMILY ROOM.
  
 8} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 15:03 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 15:03 Sent To E
Notes
2007-08-02 15:03:28TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-12 Cont ID  
Sent By jgomez Date 2007-07-12 Time 11:13 Rev Time 0.00
Received By jgomez Date 2007-06-20 Time 13:53 Sent To  
Notes
2007-06-20 13:54:12TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-08-08 Cont ID  
Sent By tgordon Date 2007-08-08 Time 10:56 Rev Time 0.30
Received By tgordon Date 2007-08-08 Time 10:56 Sent To P
Notes
2007-08-08 11:09:08*** PROVISO ***
 1) CLOTHES DRYER VENT TERMINATION MAY NOT DISCHARGE
 NEAR THE A/C CONDENSER UNIT, PER 2004 FBC/R R303.4.2.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-22 Cont ID  
Sent By tgordon Date 2007-06-22 Time 13:42 Rev Time 0.30
Received By tgordon Date 2007-06-22 Time 13:42 Sent To P
Notes
2007-06-22 13:52:56*** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK.
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. AS
 PLANS ARE SEALED BY AN ENGINEER.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) NEED SUPPLY AIR GRILL IN BEDROOM SIZED AND SHOW
 CFM'S.
  
 4) NEED ALL RETURN AIR TRANSFER DUCT 'GRILLS' SIZED.
  
 5) SEE A/C EQUIPMENT LISTING ON PLANS. MISSING MODEL
 NUMBERS FOR AIR HANDLER AND CONDENSER UNIT, HEATER
 SIZE, TOTAL AND SENSIBLE BTU'S.
  
 6) SHOW LOCATION OF A/C CONDENSER UNIT ON MECHANICAL
 PLANS.
  
 7) SHOW LOCATION OF CLOTHES DRYER VENT ON MECHANICAL
 PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-08 Cont ID  
Sent By jleech Date 2007-08-08 Time 13:36 Rev Time 0.00
Received By jleech Date 2007-08-08 Time 13:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-10 Cont ID  
Sent By jleech Date 2007-07-10 Time 08:01 Rev Time 0.00
Received By jleech Date 2007-07-10 Time 07:55 Sent To B
Notes
2007-07-10 08:11:16DENIED;
 INFORMATION MISSING FROM TITLE BLOCK. THE PRINTED NAME,
 ADDRESS, AND LICENSE NUMBER OF THE ENGINEER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695