Plan Review Stops For Permit 07060347 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2008-01-23 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2008-01-23 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2008-01-23 |
Time |
10:56 |
Sent To |
E |
|
Notes |
2008-01-23 11:40:35 | BUILDING REVISION RESUBMITTAL. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2007-12-14 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-12-14 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-12-14 |
Time |
12:35 |
Sent To |
PC |
|
Notes |
2007-12-14 14:04:30 | BUILDING REVISION CHECKLIST: | | | | 1- DRAWINGS NEED TO BE SIGNED, SEALED AND DATED BY THE | | ENGINEER OF RECORD AS REQUIRED BY CHAPTER 471 FLORIDA | | STATUTE AND SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE | | CODE. | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVEIN WRITING | | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS PRIOR | | TO SUBMITTAL TO THIS OFFICE AS REQUIRED BY SEC. 106.3 | | CITY AMENDMENTS TO FBC 2004. | | | | 3- REVISE STORM SHUTTERS INSTALLATION SCHEDULE: | | A) FOUR COLUMNREFERS TO THE SHUTTERS MOUNTING | | CONDITIONS. EG: WALL MOUNTED, BUILT OUT MOUNTED, ETC, | | NOT THE ANCHOR TYPE TO BE USED. REVISE AS REQUIRED. | | | | B) SHUTTER SPAN SHOWNDOESN'T RELATETO WINDOW | | HEIGHT SHOWN ON COLUMN #2. REVISE AS REQUIRED. | | ***NOTE: ALSO, KEEP IN CONSIDERATION THE EDGE DISTANCE | | REQUIRED. SEE SHUTTERS DRAWINGS TO SEE HOW THE PANEL | | SPAN IS MEASURED AND REVISE AS REQUIRED. | | | | C) CLARIFY WHICH ANCHOR TYPE IS GOING TO BE USED | | PANEL MATE PLUS OR TAPCON.INSTALLATION SCHEDULE SHOWS | | ONE ANCHOR ON COLUMN4 AND ANOTHER ANCHORON COLUMN | | #10. REVISE AS REQUIRED. | | | | D) REVISE MINIMUM EDGE DISTANCE REQUIRED. SEE STORM | | SHUTTERS DRAWINGS AND REVISE AS REQUIRED. | | | | 4- CLEARLY MARK ON STORM SHUTTER DRAWINGS SPECIFIC | | MOUNTING CONDITIONS AND ANCHOR TYPE AND SPACING TO BE | | USED TO VERIFY IF INFORMATION SHOWN ON INSTALLATION | | SCHEDULE MATCHES. SEC. 106.1.2 CITY AMENDMENTS TO FBC | | 2004. | | | | 5- UPDATE TOTAL VALUATION TO INCLUDE ALL SCOPE OF WORK | | TO BE PERFORMED, INCLUDING THE CHANGE OUT OF ALL | | WINDOWS. INITIAL PERMIT APPLICATION CALLED FOR WINDOW | | REPLACEMENT OF A COUPLE OF WINDOWS ONLY,NOT ALL THE | | WINDOWS. SEC. 108.3 CITY AMENDMENTS TO FBC 2004. | | | | 6- ENGINEER OF RECORD TO CERTIFY THAT ALLEXISTING | | WINDOWS ARESINGLE HUNG WINDOWS AND THAT THEY WILL BE | | REPLACEDFOR SAME TYPE OF WINDOW.AND,REPLACEMENT | | OF WINDOWS DON'TMAKE THE BUILDING LESS SAFER THAT IT | | WAS BEFORE AS REQUIRED BY SEC. 501.2 OF 2004 EXISTING | | BUILDING CODE. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2007-10-03 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-10-03 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-10-03 |
Time |
16:32 |
Sent To |
PC |
|
Notes |
2007-10-03 16:33:21 | BUILDING REVISION. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2007-09-12 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-09-12 |
Time |
14:25 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-09-12 |
Time |
14:10 |
Sent To |
PC |
|
Notes |
2007-09-12 14:32:26 | RESIDENTIAL STRUCTURAL REPAIRS BUILDING REVIEW FIRST | | CHECKLIST. | | REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND | | 2004 FBC 2004 WITH 2007 REVISIONS. | | | | 1- NEW WALL AREA ON UNIT #2 NEED TO HAVE BEDROOM #1 | | WINDOW THAT COMPLIES WITH EGRESS REQUIREMENTS OF SEC. | | R310.1.2 OF 2004 FLORIDA RESIDENTIAL CODE.NEW SINGLE | | HUNG WINDOW 37" X 50" SPECIFIED ON PLANS DOESN'T | | PROVIDE THE 24" MIN. CLEAR HEIGHT OPENING.REVISE | | WINDOW SIZE OR PROVIDE WINDOW CUT SHEETS SHOWING HOW | | THIS WINDOW SIZE PROVIDE THE MIN. CLEARANCE. | | | | 2- PROVIDE ENLARGED DETAIL/SECTION SHOWING HOW SIMPSON | | HETAL 20CONNECTOR IS GOING TO BE INSTALLED OVER | | EXISTING 2" X 8" ROOF JOIST IF ROOF IS NOT GOING TO BE | | REMOVED. SEE TRUSS CATALOG FOR PROPER CONNECTOR | | INSTALLATION. SEC. 106.1.2 CITY AMENDMENTS TO FBC | | 2004. | | | | 3- TYP. WALL& BEAM ATTACHMENT DETAIL SPECIFIES #4 | | BARS AT CORNERS WHILE BEAM IS REINFORCED WITH #5 BARS. | | PROVIDE COMPLETE ENGINEERING ANALYSIS SHOWING | | STRUCTURAL INTEGRITY AND CONTINUITY OF REINFORCEMENT | | WHEN USING DIFFERENT SIZE OF BARS.SEC. 106.1.2 CITY | | AMENDMENTS AND SEE ACI 318-02 SEC. 7. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)8057612 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2007-07-26 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-07-26 |
Time |
18:01 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-07-26 |
Time |
18:01 |
Sent To |
PC |
|
Notes |
2007-07-26 18:02:41 | APPROVAL FOR REPLACING DRYWALL, INSULATION AND WINDOWS | | AND DOORS ONLY. NO STRUCTURAL WORK. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-07-11 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-07-11 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-07-11 |
Time |
10:00 |
Sent To |
PC |
|
Notes |
2007-07-11 10:16:44 | BUILDING REVIEW CHECKLIST: | | 1-A) SINGLE HUNG WINDOWS NOA 01-0516.10 SUBMITTED | | EXPIRED ON 09/30/2006. NEED TO PROVIDE CURRENT NOA. | | | | B) PROVIDE TWO COPIES. | | | | C) SPECIFY EXISTING WINDOW OPENING SIZEAND TYPE OF | | EXISTING WINDOW TO VERIFY COMPLIANCE WITH EGRESS | | REQUIREMENTS. | | | | 2- IF WINDOWS TO BE REPLACED DON'T HAVE IMPACT GLAZING, | | THEN COMPLETE INFORMATION FOR STORM SHUTTERS NEED TO BE | | PROVIDED. PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE | | ATTACHED COPY.ALSO,CLEARLY MARK ON SHUTTER DRAWINGS | | SPECIFIC MOUNTING CONDITIONS ANDSPECIFIC ANCHORTYPE | | AND SPACING TO BE USED ACCORDING TO THE EDGE DISTANCE, | | DESIGN PRESSURES, CONNECTION TYPE AND SPECIFIC | | STRUCTURE TO BE ATTACHED TO (CONCRETE BLOCK).SEC. | | 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | 3- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | 13-600.1.C.2OF FBC 2004. | | ***NOTE: MAKE SURE 2006 REVISED FORM IS USED. | | | | 4- A/C CHANGE OUTS TO BE DONE UNDER A SEPARATE PERMIT. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2008-01-24 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-01-24 |
Time |
12:14 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-01-24 |
Time |
12:01 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2007-12-13 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-12-13 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-12-13 |
Time |
14:49 |
Sent To |
B |
|
Notes |
2007-12-13 14:51:39 | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK | | MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 | | FAC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-09-11 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-09-11 |
Time |
12:38 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-09-11 |
Time |
12:38 |
Sent To |
B |
|
Notes |
2007-09-11 12:39:41 | | | | | REVISION AND FILE SET TO JULIO./WRT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2007-07-19 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-07-19 |
Time |
08:49 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-07-19 |
Time |
08:38 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-06-20 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-06-20 |
Time |
16:37 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-06-20 |
Time |
16:26 |
Sent To |
M |
|
Notes |
2007-06-20 16:37:42 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | 1} THERE ARE ELECTRICAL PLANS PROVIDED BUT NO | | ELECTRICAL WORK IN THE DESCRIPTION ON THE APPLICATION | | AND NO CONTRACTOR SIGNED ON. INDICATE WHAT IS NEW AND | | WHAT IS EXISTING.IF NEW ELECTRICAL IS TO BE INSTALLED | | AN ELECTRICAL PERMIT WILL BE REQUIRED . | | | | 2} PROVIDE A PANEL SCHEDULE TO INCLUDE NEW WORK. | | INDICATE AMPERAGE, OCP AND WIRE SIZE. SEE 408.4 CIRCUIT | | DIRECTORY. | | | | 3} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED | | IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A | | PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE ON | | PLANS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2008-01-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-15 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-15 |
Time |
10:37 |
Sent To |
E |
|
Notes |
2008-01-15 10:37:23 | TO "BTROBAUG" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-12-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-10 |
Time |
11:52 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-10 |
Time |
11:52 |
Sent To |
E |
|
Notes |
2007-12-10 11:52:43 | TO "BTROBAUG" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-09-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-14 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-14 |
Time |
09:48 |
Sent To |
B |
|
Notes |
2007-09-14 09:48:20 | TO "JGOMEZ" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-09-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-06 |
Time |
11:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-06 |
Time |
11:53 |
Sent To |
E |
|
Notes |
2007-09-06 11:53:39 | TO "BTROBAUG" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-07-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-16 |
Time |
10:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-16 |
Time |
10:43 |
Sent To |
E |
|
Notes |
2007-07-16 10:43:35 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-07-11 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-07-11 |
Time |
10:56 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-06-12 |
Time |
16:19 |
Sent To |
|
|
Notes |
2007-06-12 16:20:52 | TO "E" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2008-01-18 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-01-18 |
Time |
09:58 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2008-01-18 |
Time |
09:58 |
Sent To |
B |
|
Notes |
2008-01-18 09:59:10 | REVISION TO BUILDING PLANS. NO MECH. REVISION. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2007-06-21 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-06-21 |
Time |
08:34 |
Rev Time |
0.15 |
Received By |
tgordon |
Date |
2007-06-21 |
Time |
08:34 |
Sent To |
B |
|
Notes |
2007-06-21 08:39:13 | *** PROVISO *** | | 1) A MECHANICAL PERMIT WILL BE NEEDED BEFORE REPLACING | | A/C SYSTEM. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|