Plan Review Details - Permit 07060347
Plan Review Stops For Permit 07060347
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-01-23 Cont ID  
Sent By jgomez Date 2008-01-23 Time 11:40 Rev Time 0.00
Received By jgomez Date 2008-01-23 Time 10:56 Sent To E
Notes
2008-01-23 11:40:35BUILDING REVISION RESUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-12-14 Cont ID  
Sent By jgomez Date 2007-12-14 Time 13:39 Rev Time 0.00
Received By jgomez Date 2007-12-14 Time 12:35 Sent To PC
Notes
2007-12-14 14:04:30BUILDING REVISION CHECKLIST:
  
 1- DRAWINGS NEED TO BE SIGNED, SEALED AND DATED BY THE
 ENGINEER OF RECORD AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE AND SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE
 CODE.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVEIN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS PRIOR
 TO SUBMITTAL TO THIS OFFICE AS REQUIRED BY SEC. 106.3
 CITY AMENDMENTS TO FBC 2004.
  
 3- REVISE STORM SHUTTERS INSTALLATION SCHEDULE:
 A) FOUR COLUMNREFERS TO THE SHUTTERS MOUNTING
 CONDITIONS. EG: WALL MOUNTED, BUILT OUT MOUNTED, ETC,
 NOT THE ANCHOR TYPE TO BE USED. REVISE AS REQUIRED.
  
 B) SHUTTER SPAN SHOWNDOESN'T RELATETO WINDOW
 HEIGHT SHOWN ON COLUMN #2. REVISE AS REQUIRED.
 ***NOTE: ALSO, KEEP IN CONSIDERATION THE EDGE DISTANCE
 REQUIRED. SEE SHUTTERS DRAWINGS TO SEE HOW THE PANEL
 SPAN IS MEASURED AND REVISE AS REQUIRED.
  
 C) CLARIFY WHICH ANCHOR TYPE IS GOING TO BE USED
 PANEL MATE PLUS OR TAPCON.INSTALLATION SCHEDULE SHOWS
 ONE ANCHOR ON COLUMN4 AND ANOTHER ANCHORON COLUMN
 #10. REVISE AS REQUIRED.
  
 D) REVISE MINIMUM EDGE DISTANCE REQUIRED. SEE STORM
 SHUTTERS DRAWINGS AND REVISE AS REQUIRED.
  
 4- CLEARLY MARK ON STORM SHUTTER DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE AND SPACING TO BE
 USED TO VERIFY IF INFORMATION SHOWN ON INSTALLATION
 SCHEDULE MATCHES. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 5- UPDATE TOTAL VALUATION TO INCLUDE ALL SCOPE OF WORK
 TO BE PERFORMED, INCLUDING THE CHANGE OUT OF ALL
 WINDOWS. INITIAL PERMIT APPLICATION CALLED FOR WINDOW
 REPLACEMENT OF A COUPLE OF WINDOWS ONLY,NOT ALL THE
 WINDOWS. SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 6- ENGINEER OF RECORD TO CERTIFY THAT ALLEXISTING
 WINDOWS ARESINGLE HUNG WINDOWS AND THAT THEY WILL BE
 REPLACEDFOR SAME TYPE OF WINDOW.AND,REPLACEMENT
 OF WINDOWS DON'TMAKE THE BUILDING LESS SAFER THAT IT
 WAS BEFORE AS REQUIRED BY SEC. 501.2 OF 2004 EXISTING
 BUILDING CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-10-03 Cont ID  
Sent By jgomez Date 2007-10-03 Time 16:32 Rev Time 0.00
Received By jgomez Date 2007-10-03 Time 16:32 Sent To PC
Notes
2007-10-03 16:33:21BUILDING REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-12 Cont ID  
Sent By jgomez Date 2007-09-12 Time 14:25 Rev Time 0.00
Received By jgomez Date 2007-09-12 Time 14:10 Sent To PC
Notes
2007-09-12 14:32:26RESIDENTIAL STRUCTURAL REPAIRS BUILDING REVIEW FIRST
 CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND
 2004 FBC 2004 WITH 2007 REVISIONS.
  
 1- NEW WALL AREA ON UNIT #2 NEED TO HAVE BEDROOM #1
 WINDOW THAT COMPLIES WITH EGRESS REQUIREMENTS OF SEC.
 R310.1.2 OF 2004 FLORIDA RESIDENTIAL CODE.NEW SINGLE
 HUNG WINDOW 37" X 50" SPECIFIED ON PLANS DOESN'T
 PROVIDE THE 24" MIN. CLEAR HEIGHT OPENING.REVISE
 WINDOW SIZE OR PROVIDE WINDOW CUT SHEETS SHOWING HOW
 THIS WINDOW SIZE PROVIDE THE MIN. CLEARANCE.
  
 2- PROVIDE ENLARGED DETAIL/SECTION SHOWING HOW SIMPSON
 HETAL 20CONNECTOR IS GOING TO BE INSTALLED OVER
 EXISTING 2" X 8" ROOF JOIST IF ROOF IS NOT GOING TO BE
 REMOVED. SEE TRUSS CATALOG FOR PROPER CONNECTOR
 INSTALLATION. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 3- TYP. WALL& BEAM ATTACHMENT DETAIL SPECIFIES #4
 BARS AT CORNERS WHILE BEAM IS REINFORCED WITH #5 BARS.
 PROVIDE COMPLETE ENGINEERING ANALYSIS SHOWING
 STRUCTURAL INTEGRITY AND CONTINUITY OF REINFORCEMENT
 WHEN USING DIFFERENT SIZE OF BARS.SEC. 106.1.2 CITY
 AMENDMENTS AND SEE ACI 318-02 SEC. 7.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)8057612

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-07-26 Cont ID  
Sent By jgomez Date 2007-07-26 Time 18:01 Rev Time 0.00
Received By jgomez Date 2007-07-26 Time 18:01 Sent To PC
Notes
2007-07-26 18:02:41APPROVAL FOR REPLACING DRYWALL, INSULATION AND WINDOWS
 AND DOORS ONLY. NO STRUCTURAL WORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By jgomez Date 2007-07-11 Time 10:01 Rev Time 0.00
Received By jgomez Date 2007-07-11 Time 10:00 Sent To PC
Notes
2007-07-11 10:16:44BUILDING REVIEW CHECKLIST:
 1-A) SINGLE HUNG WINDOWS NOA 01-0516.10 SUBMITTED
 EXPIRED ON 09/30/2006. NEED TO PROVIDE CURRENT NOA.
  
 B) PROVIDE TWO COPIES.
  
 C) SPECIFY EXISTING WINDOW OPENING SIZEAND TYPE OF
 EXISTING WINDOW TO VERIFY COMPLIANCE WITH EGRESS
 REQUIREMENTS.
  
 2- IF WINDOWS TO BE REPLACED DON'T HAVE IMPACT GLAZING,
 THEN COMPLETE INFORMATION FOR STORM SHUTTERS NEED TO BE
 PROVIDED. PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED COPY.ALSO,CLEARLY MARK ON SHUTTER DRAWINGS
 SPECIFIC MOUNTING CONDITIONS ANDSPECIFIC ANCHORTYPE
 AND SPACING TO BE USED ACCORDING TO THE EDGE DISTANCE,
 DESIGN PRESSURES, CONNECTION TYPE AND SPECIFIC
 STRUCTURE TO BE ATTACHED TO (CONCRETE BLOCK).SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 3- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600.1.C.2OF FBC 2004.
 ***NOTE: MAKE SURE 2006 REVISED FORM IS USED.
  
 4- A/C CHANGE OUTS TO BE DONE UNDER A SEPARATE PERMIT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-01-24 Cont ID  
Sent By btrobaug Date 2008-01-24 Time 12:14 Rev Time 0.00
Received By btrobaug Date 2008-01-24 Time 12:01 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-12-13 Cont ID  
Sent By btrobaug Date 2007-12-13 Time 14:51 Rev Time 0.00
Received By btrobaug Date 2007-12-13 Time 14:49 Sent To B
Notes
2007-12-13 14:51:39 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-09-11 Cont ID  
Sent By btrobaug Date 2007-09-11 Time 12:38 Rev Time 0.00
Received By btrobaug Date 2007-09-11 Time 12:38 Sent To B
Notes
2007-09-11 12:39:41 
  
 REVISION AND FILE SET TO JULIO./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-19 Cont ID  
Sent By btrobaug Date 2007-07-19 Time 08:49 Rev Time 0.00
Received By btrobaug Date 2007-07-19 Time 08:38 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By btrobaug Date 2007-06-20 Time 16:37 Rev Time 0.00
Received By btrobaug Date 2007-06-20 Time 16:26 Sent To M
Notes
2007-06-20 16:37:42 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 1} THERE ARE ELECTRICAL PLANS PROVIDED BUT NO
 ELECTRICAL WORK IN THE DESCRIPTION ON THE APPLICATION
 AND NO CONTRACTOR SIGNED ON. INDICATE WHAT IS NEW AND
 WHAT IS EXISTING.IF NEW ELECTRICAL IS TO BE INSTALLED
 AN ELECTRICAL PERMIT WILL BE REQUIRED .
  
 2} PROVIDE A PANEL SCHEDULE TO INCLUDE NEW WORK.
 INDICATE AMPERAGE, OCP AND WIRE SIZE. SEE 408.4 CIRCUIT
 DIRECTORY.
  
 3} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE ON
 PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-01-15 Cont ID  
Sent By adarroug Date 2008-01-15 Time 10:37 Rev Time 0.00
Received By adarroug Date 2008-01-15 Time 10:37 Sent To E
Notes
2008-01-15 10:37:23TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-10 Time 11:52 Rev Time 0.00
Received By adarroug Date 2007-12-10 Time 11:52 Sent To E
Notes
2007-12-10 11:52:43TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-14 Cont ID  
Sent By adarroug Date 2007-09-14 Time 09:48 Rev Time 0.00
Received By adarroug Date 2007-09-14 Time 09:48 Sent To B
Notes
2007-09-14 09:48:20TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-06 Cont ID  
Sent By adarroug Date 2007-09-06 Time 11:53 Rev Time 0.00
Received By adarroug Date 2007-09-06 Time 11:53 Sent To E
Notes
2007-09-06 11:53:39TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-16 Cont ID  
Sent By adarroug Date 2007-07-16 Time 10:43 Rev Time 0.00
Received By adarroug Date 2007-07-16 Time 10:43 Sent To E
Notes
2007-07-16 10:43:35TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-11 Cont ID  
Sent By jgomez Date 2007-07-11 Time 10:56 Rev Time 0.00
Received By jgomez Date 2007-06-12 Time 16:19 Sent To  
Notes
2007-06-12 16:20:52TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-01-18 Cont ID  
Sent By tgordon Date 2008-01-18 Time 09:58 Rev Time 0.20
Received By tgordon Date 2008-01-18 Time 09:58 Sent To B
Notes
2008-01-18 09:59:10REVISION TO BUILDING PLANS. NO MECH. REVISION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-06-21 Cont ID  
Sent By tgordon Date 2007-06-21 Time 08:34 Rev Time 0.15
Received By tgordon Date 2007-06-21 Time 08:34 Sent To B
Notes
2007-06-21 08:39:13*** PROVISO ***
 1) A MECHANICAL PERMIT WILL BE NEEDED BEFORE REPLACING
 A/C SYSTEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.