Plan Review Details - Permit 07060328
Plan Review Stops For Permit 07060328
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-01 Cont ID  
Sent By btrobaug Date 2007-08-01 Time 17:08 Rev Time 0.00
Received By btrobaug Date 2007-08-01 Time 16:35 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-17 Cont ID  
Sent By btrobaug Date 2007-07-17 Time 12:07 Rev Time 0.00
Received By btrobaug Date 2007-07-17 Time 12:01 Sent To FIRE
Notes
2007-07-17 12:07:44 
  
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 SECOND REQUEST. PLEASE SEE "PRINT AND SIGN".
  
 THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-14 Cont ID  
Sent By btrobaug Date 2007-06-14 Time 14:30 Rev Time 0.33
Received By btrobaug Date 2007-06-14 Time 13:58 Sent To FIRE
Notes
2007-06-14 14:30:06 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-09-04 Cont ID  
Sent By mawillia Date 2007-09-04 Time 13:12 Rev Time 0.00
Received By mawillia Date 2007-09-04 Time 12:50 Sent To  
Notes
2007-09-04 13:01:47*****APPROVED*****
  
 BOTH PLAN SHEETS STAMPED, INITIALED, AND DATED;READY
 FOR PERMIT ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-07-17 Cont ID  
Sent By mawillia Date 2007-07-17 Time 14:31 Rev Time 0.00
Received By mawillia Date 2007-07-17 Time 13:58 Sent To  
Notes
2007-07-17 14:25:32*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEET(S)
 WILL BE FIRE-STAMPED WHEN ALL OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-25 Cont ID  
Sent By mawillia Date 2007-06-25 Time 12:19 Rev Time 0.00
Received By mawillia Date 2007-06-25 Time 11:26 Sent To  
Notes
2007-06-25 12:17:37*****UNSAT*****
  
  
 1.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS
 CONTROL SYSTEM PROVIDED THAT THE CRITERIA OF 7.2.1.6.2
 NFPA 101 (2003 EDITION) BE MET.
  
 2.ACCORDING TO SUBMITTED APPLICATION'S PROJECT
 DESCRIPTION, 21 READERS AND 21 DOOR STRIKES WERE
 DETAILED.THE SUBMITTED PLAN SHEETS, HOWEVER SHOW ONLY
 18 DOOR STRIKES.THREE (3) DOOR STRIKES (DS) APPEAR TO
 BE MISSING FROM THE MEZZANINE FLOOR PLAN.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-27 Cont ID  
Sent By adarroug Date 2007-07-27 Time 10:39 Rev Time 0.00
Received By adarroug Date 2007-07-27 Time 10:39 Sent To E
Notes
2007-07-27 10:39:31TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-05 Cont ID  
Sent By adarroug Date 2007-07-05 Time 09:58 Rev Time 0.00
Received By adarroug Date 2007-07-05 Time 09:58 Sent To E
Notes
2007-07-05 09:59:05TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-25 Cont ID  
Sent By mawillia Date 2007-06-25 Time 11:50 Rev Time 0.00
Received By mawillia Date 2007-06-13 Time 08:36 Sent To  
Notes
2007-06-13 08:36:27TO "E" BOX