Plan Review Stops For Permit 07060328 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-08-01 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-08-01 |
Time |
17:08 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-08-01 |
Time |
16:35 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-07-17 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-07-17 |
Time |
12:07 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-07-17 |
Time |
12:01 |
Sent To |
FIRE |
|
Notes |
2007-07-17 12:07:44 | | | | | | | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | SECOND REQUEST. PLEASE SEE "PRINT AND SIGN". | | | | THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 | | FS, RESPECTIVELY. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-06-14 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-06-14 |
Time |
14:30 |
Rev Time |
0.33 |
Received By |
btrobaug |
Date |
2007-06-14 |
Time |
13:58 |
Sent To |
FIRE |
|
Notes |
2007-06-14 14:30:06 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 | | FS, RESPECTIVELY. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-09-04 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-09-04 |
Time |
13:12 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-09-04 |
Time |
12:50 |
Sent To |
|
|
Notes |
2007-09-04 13:01:47 | *****APPROVED***** | | | | BOTH PLAN SHEETS STAMPED, INITIALED, AND DATED;READY | | FOR PERMIT ISSUANCE. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2007-07-17 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-07-17 |
Time |
14:31 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-07-17 |
Time |
13:58 |
Sent To |
|
|
Notes |
2007-07-17 14:25:32 | *****PROVISO***** | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEET(S) | | WILL BE FIRE-STAMPED WHEN ALL OTHER REVIEWERS HAVE BEEN | | SATISFIED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-06-25 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-06-25 |
Time |
12:19 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-06-25 |
Time |
11:26 |
Sent To |
|
|
Notes |
2007-06-25 12:17:37 | *****UNSAT***** | | | | | | 1.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO | | BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS | | CONTROL SYSTEM PROVIDED THAT THE CRITERIA OF 7.2.1.6.2 | | NFPA 101 (2003 EDITION) BE MET. | | | | 2.ACCORDING TO SUBMITTED APPLICATION'S PROJECT | | DESCRIPTION, 21 READERS AND 21 DOOR STRIKES WERE | | DETAILED.THE SUBMITTED PLAN SHEETS, HOWEVER SHOW ONLY | | 18 DOOR STRIKES.THREE (3) DOOR STRIKES (DS) APPEAR TO | | BE MISSING FROM THE MEZZANINE FLOOR PLAN. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-07-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-27 |
Time |
10:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-27 |
Time |
10:39 |
Sent To |
E |
|
Notes |
2007-07-27 10:39:31 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-07-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-05 |
Time |
09:58 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-05 |
Time |
09:58 |
Sent To |
E |
|
Notes |
2007-07-05 09:59:05 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-06-25 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-06-25 |
Time |
11:50 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-06-13 |
Time |
08:36 |
Sent To |
|
|
Notes |
2007-06-13 08:36:27 | TO "E" BOX |
|
|