Plan Review Details - Permit 07060292
Plan Review Stops For Permit 07060292
Review Stop AD ADDRESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-26 Cont ID  
Sent By jgomez Date 2007-10-26 Time 16:42 Rev Time 0.00
Received By jgomez Date 2007-10-26 Time 12:41 Sent To PC
Notes
2007-10-26 17:00:16NEW SINGLE FAMILY RESIDENCE BUILDING REVIEW THIRD
 CHECKLIST.
 REVIEW UNDER FLORIDA RESIDENTIAL CODE 2004 AND FBC 2004
 WITH 2006 REVISIONS.
  
 1- NEED TO GET APPROVAL FROM ZONING. SEE ZONING
 COMMENTS.
  
 2- SHEET 3.1 SPECIFIES CONSTRUCTION TYPE III.SPECIFY
 WHAT TYPE III.A OR B?.ALSO,BE AWARE THAT TYPE III
 CONSTRUCTION REQUIRES A TWO HOUR FIRE RATED WALL. SEE
 TABLE 601 AND TABLE 602 OF FBC 2004. NEED TO SPECIFY
 HOW ACHIEVING THE 2 HOUR FIRE RATING REQUIRED BY TABLES
 601 AND 602 FBC 2004.
  
 3- PROVIDE COMPLETE MANUFACTURER SPECS FOR 2 HOUR
 CONCRETE BLOCK AS REQUIRED BY ITEM 2 ABOVE.
  
 4- RE-SUBMITTAL FEEOF $193.10 WAS NOT PAID AT TIME OF
 SUBMITTAL.IN ADDITION, NEW RE-SUBMITTAL FEEWILL BE
 DUE AT TIME OF RE-SUBMITTAL.
  
 5- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2004
 FLORIDA RESIDENTIAL CODE.(REPEAT COMMENT).
  
 6- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 ***NOTE: REMEMBER THAT ENGINEER OF RECORD NEEDS TO
 REVIEW AND APPROVE ALL PRODUCT APPROVALS IN WRITING
 (NOT SIGNING AND SEALING) PRIOR TO SUBMITTAL TO THIS
 OFFICE.
  
 A) PRECAST LINTELS. PROVIDE CURRENT FLORIDA PRODUCT
 APPROVAL REPORT FL158-R2. THIS IS THE ONE THAT
 REFERENCES NOA 06-0222.01 SUBMITTED.ONE SUBMITTED IS
 FL158-R1 WHICH IS THE OLD ONE AND WAS REVISED.
  
 B) SINGLE HUNG WINDOWS. PROVIDE CURRENT FLORIDA
 PRODUCT APPROVAL REPORT FL239-R10 AND CORRESPONDING
 NOA.FL239-R4 IS OLD AND WAS REVISED.
  
 7- STORM SHUTTERS:
 A) INSTALLATION SCHEDULE SUBMITTED SHOWS 12.5"
 ANCHOR SPACING. LOOK AT STORM PANEL DETAIL #1 ON SHEET
 1 OF 6 OF STORM SHUTTERS DRAWINGS AND REVISE AS
 REQUIRED.
  
 B) REVISE MINIMUM PANEL LENGTH FOR THE FOLLOWING
 OPENINGS: #1, #3, #5 AND #8.SEE TABLE 2 ON PAGE 6 OF
 6 OF SHUTTERS DRAWINGS SUBMITTED.
  
 C) CLEARLY SPECIFYSHUTTER MOUNTING CONDITION ON
 THE 4TH COLUMN OF STORM SHUTTER INSTALLATIONSCHEDULE.
 EG:NEED TO SPECIFYIFWALL MOUNTED OR BUILT OUT,
 ETC.TO VERIFY COMPLIANCE WITH WIND LOADS SEC. 1609
 FBC 2004.(REPEAT COMMENT).
  
 D) PROVIDE KEY PLAN TO IDENTIFY OPENING LOCATION TO
 VERIFY COMPLIANCE WITH WIND LOADS SEC. 1609 FBC 2004.
 (REPEAT COMMENT).
  
 8- ROOF DESIGN LOADS ON SHEET 5.1 IS MISSING THE ATTIC
 LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 9- A) SURVEY SUBMITTED NEEDS THE SURVEYOR ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 472 FLORIDA STATUTE.
  
 B) SURVEY TO HAVE COMPLETE ADDRESS NUMBER.
  
 10- TRUSS PACKAGE:
 A) ENGINEER TO PROVIDE ORIGINAL SIGNATURE, NOT
 RUBBER STAMP SIGNATURE.SEC. 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
 NOTE: ONE OF OF TRUSS PACKAGE WILL BE HELD IN THIS
 OFFICE TO BE SUBMITTED TO THE BOARD OF ENGINEERS FOR
 THEIR REVIEW.
  
 B) TRUSS LOADING DOESN'T MATCH DESIGNCRITERIA
 SPECIFIED BY THE ENGINEER OF RECORD. REVISE AS
 REQUIRED.
  
 C) THERE IS AN ENGINEER OF RECORD IN THIS PROJECT.
 HIS NAME MUST BE INCLUDED IN THE TRUSS PACKAGE AS
 REQUIRED BY SEC. 61G15-31.003 FLORIDA ADMINISTRATIVE
 CODE.
  
 D) ENGINEER OF RECORD NEEDS TO REVIEW AND APPROVE
 TRUSS PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 E) CLARIFY WHY THE ATTIC LIVE LOAD IS NONCONCURRENT.
 TABLE R301.5OF 2004 FLORIDA RESIDENTIAL CODE REQUIRES
 THIS LOAD TO BE CALCULATED ON THE TRUSSES.CLEARLY
 SPECIFY WHAT SECTION OF THE CODE ALLOWS THIS LOAD TO BE
 NONCONCURRENT AND IS NONCONCURRENT WITH WHAT OTHER
 LOADS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-17 Cont ID  
Sent By jgomez Date 2007-08-17 Time 16:57 Rev Time 0.00
Received By jgomez Date 2007-08-17 Time 16:57 Sent To M
Notes
2007-08-17 16:59:11NEW SINGLE FAMILY RESIDENCE BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC
 2004 WITH 2006 REVISIONS.
  
 1- TYPE OF CONSTRUCTION SPECIFIED ON SHEET 3.1 IS
 WRONG. SEE SEC. 602.1 FBC 2004 AND REVISE AS REQUIRED.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5115) TO PAY IMPACT FEES.BRING BACK STAMPED
 PLANS AND COPY OF PAID RECEIPT.REPEATED COMMENT FROM
 PREVIOUS CHECKLIST.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE. REPEATED COMMENT FROM
 PREVIOUS CHECKLIST.
  
 4- PROVIDE DRAINAGE PLAN AS REQUIRED BY SEC. SEC.
 R401.3 OF 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE: WATER CAN'T BE DIRECTED TO NEIGHBOR'S
 PROPERTY. REPEATED COMMENT FROM PREVIOUS CHECKLIST.
  
 5- SHEET 1.1:
 A) REVISE PLYWOOD ROOF SHEATHING NOTE D.MINIMUM
 FASTENER PENETRATIONIS 1 3/4" AS REQUIRED BY ASTM
 C-926 AND ASTM C-1063.THEREFORE 1 3/4" NAILING AS
 SPECIFIED ON THIS NOTE IS NOT ADEQUATE. SEE ASTM
 STANDARDS AND REVISE AS REQUIRED.
  
 B) UPDATE ALL GENERAL NOTES. SEE CHAPTER 43 OF 2004
 FLORIDA RESIDENTIAL CODE FOR SPECIFIC STANDARDS AND
 SPECIFIC YEAR TO BE USED. REPEATED COMMENT FROM
 PREVIOUS CHECKLIST.
  
 6- OWES $415.47 FOR UPDATED VALUATION AND RADON FEES.
 REPEATED COMMENT FROM PREVIOUS CHECKLIST.
  
 7- PROVIDE SOIL TEST REPORT. REPEATED COMMENT-FROM
 PREVIOUS CHECKLIST.
  
 8- ENERGY CALCULATIONS NEED TO HAVE CORRECT BUILDER'S
 NAME. REPEATED COMMENT FROM PREVIOUS CHECKLIST.
  
 9- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) PRECAST LINTELS.NOA 03-0605.05 SUBMITTED
 EXPIRED ON 05/21/06. ON THE OTHER HAND NOA 03-0605.04
 IS FOR 4", 6" AND 12" WIDE LINTELS. THEREFORE IT CAN BE
 USED IN THIS PROJECT BECAUSE THIS LINTEL SIZE IS NOT
 SPECIFIED ON PLANS.
  
 B) SINGLE HUNG WINDOWS. NOA 05-0928.03 SUBMITTED
 DON'T CORRESPOND TO FL239-R4 SUBMITTED. GO THE THE DCA
 WEBSITE WWW.FLORIDABUILDING.ORG TO DOWNLOAD NOA THAT
 CORRESPONDS TO FL239.
  
 C) ENTRY DOOR AS SHOWN ON PLANS. REPEAT COMMENT FROM
 PREVIOUS CHECKLIST.
  
 D) FRENCH DOORS AS SHOWN ON PLANS.NOA 05-0107.01
 SUBMITTED DOESN'T CORRESPOND TO FL253-R2 SUBMITTED. GO
 TO DCA WEBSITE TO DOWNLOAD CORRESPONDING NOA.
 ***NOTE: THERE ARE TWO DIFFERENT PRODUCT APPROVALS
 SUBMITTED. PROVIDE ONLY ONE PRODUCT APPROVAL. ON THE
 OTHER HAND NOA 02-1216.09 EXPIRED ON 08/15/07.
 THEREFORE IT CAN'T BE USED.
  
 10- STORM SHUTTERS:
 A) COMPLETE ALL THE INFORMATION IN THE INSTALLATION
 SCHEDULE SUBMITTED. NEED TO SPECIFY SHUTTER MOUNTING
 CONDITION (EG: WALL MOUNTED, BUILT OUT MOUNTED, ETC.),
 SHUTTER SPAN, SPECIFIC ANCHOR AND SUBSTRATE (STRUCTURE
 TO BE ATTACHED TO: CONCRETE BLOCK).
  
 B) CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC ANCHOR
 TYPE. SEE SHEET 5 OF 6 OFSHUTTERS DRAWINGS.
  
 C) PROVIDE KEY PLAN TO IDENTIFY LOCATION OF
 OPENINGS.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 12- SHEET 2.1: REVISE WINDOW BUCK DETAIL. SEE SEC.
 R613.6.2 OF 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT
 WAY OF SHOWING BUCK DETAIL.BUCK NEEDS TO PROVIDE
 FULL FRAME SUPPORT. REPEAT COMMENT FROM PREVIOUS
 CHECKLIST.
  
 13- SHEET 5.1:ROOF DESIGN LOADS INFORMATION DOESN'T
 MATCH INFORMATION SHOWN ON SHEET. 1.1.REVISE AS
 REQUIRED. REPEATED COMMENT FROM PREVIOUS CHECKLIST.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By jgomez Date 2007-07-11 Time 17:28 Rev Time 0.00
Received By jgomez Date 2007-07-11 Time 17:14 Sent To PC
Notes
2007-07-11 17:59:31BUILDING REVIEW CHECKLIST:
 1- PLANS TO SPECIFY CONSTRUCTION TYPE AS REQUIRED BY
 SEC. 602.1 OF FBC 2004.
  
 2- GARAGE DOOR LEADING TO THE LIVING ROOM AREA NEEDS TO
 COMPLY WITH SEC. R309.1 OF 2004 FLORIDA RESIDENTIAL
 CODE. PROVIDE SPECS FOR DOOR THAT COMPLIES WITH THIS
 CODE SECTION.
  
 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD (561)233-5115)TO PAY IMPACT
 FEES. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT.
  
 4- BRING RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 5- PROVIDE DRAINAGE PLANS AS REQUIRED BY SEC. R401.3 OF
 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE:WATER CAN'T BE DIRECTED TO THE NEIGHBOR'S
 PROPERTY.
  
 6- REVISE ROOF SHEATHING NOTES ON SHEET 1.1,ROOF
 FRAMING PLANS AND PLYWOOD SHEATHING NAILING SCHEDULE.
 MINIMUM TYPE OF NAIL IS 8D RING SHANK NAIL AND SPACING
 AT ZONE 3IS 4" ON CENTER. SEESEC. R803.2.3.1 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 7-VALUATION DECLARED ON PERMIT APPLICATION WAS
 UPDATED AS REQUIRED BY SEC. 108.3 CITY AMENDMENTSTO
 FBC 2004.THEREFORE OWES $415.47 FOR VALUATION UPDATE
 AND RADON FEES.
  
 8- PROVIDE SOIL TEST REPORT.2 COPIES WITH ORIGINAL
 ENGINEER'S SEAL AND SIGNATURE.
  
 9- ENERGY CALCULATIONS:
 A) PROVIDECORRECT BUILDER INFORMATION. AND,
 COMPLETE ALL INFORMATION ON TOP OF FORM.
 B) CLARIFY ITEM 9 (B): WHERE IS THE EXTERIOR
 CONCRETE WALL WITH R11 INSULATION? ANDHOW IS THE R11
 VALUE ACHIEVED.
  
 10- ENERGY CALCULATIONS ARE TAKEN THE CEILING FANS
 CREDIT. THEREFORE, PLANS NEED TO SHOW SIZE OF CEILING
 FAN IN ALL ROOMS AS REQUIRED BY TABLE 13-607.1.A.1FBC
 2004.
  
 11- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED
 BY DCA RULE 9B-72 FOR:
 A) ENTRY DOOR.
 B) FRENCH DOORS AS SHOWN ON PLANS.
 C) SINGLE HUNG WINDOWS.
 D) STORM SHUTTERS IF SINGLE HUNG WINDOWS DON'T HAVE
 IMPACT GLASS.
 ***NOTE: NEED TO PROVIDE STORM SHUTTERS COMPLETE
 INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE.AND, MARK
 ON SHUTTERS DRAWINGS SPECIFIC SHUTTER MOUNTING
 CONDITIONS (EG: WALL MOUNTED)AND SPECIFIC ANCHOR TYPE
 AND SPACING TO BE USED ACCORDING TO DESIGN PRESSURES,
 EDGE DISTANCE, CONNECTION TYPE, PANEL SPAN AND
 STRUCTURE TO BE ATTACHED TO (CONCRETE BLOCK).SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 E) 8" PRECAST LINTELS AS SPECIFIED ON PLANS. CLARIFY
 WHY ENGINEER APPROVED PRODUCT APPROVAL FOR 4", 6" AND
 12" PRECAST LINTELS IF THEY WERE NOT USED?
  
 12- SHEET 1.1:
 A) REVISE DESIGN CRITERIAITEM (D). WHAT ARE THE
 WIND ZONES AVERAGE PRESSURES? WHERE ARE THESE TAKEN
 FROM?. IS THIS REALLY REQUIRED? ALL ZONES ARE MIXED UP?
 THESE WIND ZONES ARE FOR WHAT?. WALLS, ROOF?. WHAT'S
 THE CONSIDERED TRIBUTARY AREA ?.ARE THESE FOR
 COMPONENTS AND CLADDING? SEE 2006 REVISED TABLE
 1609.6.2.1(2).
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 B) REVIEW ALL NOTES AND UPDATE THE SPECIFIC STANDARD
 AND YEAR TO BE REFERENCED IN THE CODE. SEE CHAPTER 43
 OF 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT REFERENCE
 STANDARD AND YEAR TO BE USED FOR EACH CHAPTER OF THE
 CODE.
  
 C) MASONRY WALL NOTES:SEE SEC. R606.4 OF 2004
 FLORIDA RESIDENTIAL CODE AND REVISEMINIMUM NET AREA
 COMPRESSIVE STRENGTH OF CONCRETE BLOCK.
  
 13- SHEET 2.1: REVISE WINDOW BUCK DETAIL.SEE SEC.
 R613.6.2 OF 2004 FLORIDA RESIDENTIAL CODE FOR PROPER
 WAY OF INSTALLING THE BUCK.
 WINDOW/DOORFRAME NED TO HAVE FULL SUPPORT ON THE
 BUCK.
  
 14- SHEET 5.1:ROOF DESIGN LOADS INFORMATION DOESN'T
 MATCH INFORMATION GIVEN ON SHEET 1.1. REVISE AS
 REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-16 Cont ID  
Sent By btrobaug Date 2007-08-16 Time 17:07 Rev Time 0.00
Received By btrobaug Date 2007-08-16 Time 17:03 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-06-18 Cont ID  
Sent By btrobaug Date 2007-06-18 Time 08:18 Rev Time 0.00
Received By btrobaug Date 2007-06-18 Time 07:53 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-15 Cont ID  
Sent By adarroug Date 2007-10-15 Time 08:23 Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 08:23 Sent To Z
Notes
2007-10-15 08:23:51TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-09 Cont ID  
Sent By dpalmer Date 2007-08-09 Time 12:47 Rev Time 0.00
Received By dpalmer Date 2007-08-09 Time 12:47 Sent To Z
Notes
2007-08-09 12:48:07TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-11 Cont ID  
Sent By jgomez Date 2007-07-11 Time 17:59 Rev Time 0.00
Received By jgomez Date 2007-06-12 Time 08:51 Sent To  
Notes
2007-06-12 08:52:09TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-10-17 Cont ID  
Sent By tgordon Date 2007-10-17 Time 10:15 Rev Time 0.30
Received By tgordon Date 2007-10-17 Time 10:15 Sent To B
Notes
2007-10-17 10:25:35PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 15 IS TAKING A CREDIT FOR
 HF-WHOLE HOUSE FAN, PER 2004 FBC 13-607.1.A.3.2 THIS
 BUILDING DOES NOT QUALIFY FOR THAT CREDIT. PLEASE
 CORRECT.
 *** SEE SUBCHAPTER 13-2 DEFINITIONS WHOLE - HOUSE FAN .
 A MECHANICAL VENTILATION SYSTEM USUALLY INSTALLED IN
 THE CEILING OF A RESIDENCE WHICH IS USED TO EXHAUST AIR
 FROM THE INTERIOR OF A BUILDING TO AN ATTIC SPACE WITH
 SUFFICIENT VENTING AREA TO TRANSFER THE AIR TO THE
 OUTSIDE.
 ***13-607.1.A.3.2 WHOLE HOUSE FAN CREDIT.
 HOUSES FOR WHICH WHOLE HOUSE FAN CREDIT IS CLAIMED
 SHALL HAVE INSTALLED A WHOLE HOUSE FAN SIZED TO PROVIDE
 A MINIMUM OF 20 AIR CHANGES PER HOUR FOR THE ENTIRE
 HOUSE. THE FAN INSTALLED SHALL HAVE A FREE AIR CFM
 RATING OF AT LEAST THREE TIMES THE SQUARE FOOTAGE OF
 THE CONDITIONED AREA OF THE HOUSE. TO ENSURE ADEQUATE
 AIR EXHAUST, THE HOUSE ATTIC SHALL HAVE GABLE, RIDGE OR
 WIND TURBINE VENTS WHOSE TOTAL OPENING AREA IS EQUAL TO
 FOUR TIMES THE CEILING CUTOUT AREA FOR THE WHOLE HOUSE
 FAN. SOFFIT VENTS SHALL NOT BE INCLUDED IN THE EXHAUST
 VENT AREA.
  
 2) PLEASE SHOW THE SIZE OF THE RETURN AIR GRILL TO THE
 AIR HANDLER, SEE W.P.B 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-20 Cont ID  
Sent By tgordon Date 2007-08-20 Time 16:08 Rev Time 0.30
Received By tgordon Date 2007-08-20 Time 16:08 Sent To  
Notes
2007-08-20 16:21:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 11A STATES AIR HANDLER
 INTERIOR, MECHANICAL PLANS SHOW THE AIR HANDLER IS IN
 THE GARAGE, PLEASE CORRECT ENERGY CALCULATIONS.
  
 2) MECHANICAL PLANS NOTES STATE "ACCORDING TO
 F.M.C.2004. AS THIS IS A SINGLE FAMILY DWELLING IT
 NEEDS TO COMPLY WITH THE 2004 FBC/RESIDENTIAL, SEE
 R101.2. PLEASE CORRECT.
  
 3) MECHANICAL PLANS EQUIPMENT SCHEDULE, CAN NOT READ
 THE CONDENSER UNIT MODEL NUMBER, SEE 2004 FBC 106.1.1.
 PLEASE CORRECT.
  
 4) PLEASE SHOW THE A/C SYSTEM'S SEER IN THE EQUIPMENT
 SCHEDULE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By tgordon Date 2007-06-19 Time 08:29 Rev Time 0.30
Received By tgordon Date 2007-06-19 Time 08:29 Sent To P
Notes
2007-06-19 08:34:48*** DENIED ***
 1) CLOTHES DRYER VENT TERMINATION MAY NOT DISCHARGE
 NEAR A/C CONDENSER UNIT, SEE 2004 BC/M 501.2 .
  
 2) SEE MECHANICAL PLANS A/C NOTES STATES ACCORDING TO
 PALM BEACH COUNTY, PERMIT IS BEING APPLIED FOR IN THE
 CITY OF WEST PALM BEACH, PLEASE CORRECT A/C NOTES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-07-05 Cont ID  
Sent By jleech Date 2007-07-05 Time 08:27 Rev Time 0.00
Received By jleech Date 2007-07-05 Time 08:27 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2007-10-16 Cont ID  
Sent By choops Date 2007-10-16 Time 11:54 Rev Time 0.00
Received By choops Date 2007-10-16 Time 11:54 Sent To M
Notes
2007-10-16 11:57:17***FAILED - RESUB #2***
  
 REPEAT COMMENT:
  
 1)PROVIDED LETTER REGARDING SUBDIVISION IS
 INSUFFICIENT, PROPERTY CONTROL NUMBERS ARE ISSUED BY
 THE COUNTY REGARDLESS OF A LEGAL SUBDIVISION.
  
 THE PLANNING AND ZONING DEPARTMENT HAS NO RECORD THAT
 THE CITY OF WEST PALM BEACH APPROVED THIS SUBDIVISION.
 THE PROPERTY OWNER SWOULD BE REQUIRED TO APPLY FOR A
 MINOR SUBDIVISION THROUGH THE PLANNING AND ZONING
 DEPARTMENT.HOWEVER THE MINOR SUBDIVISION WILL NOT BE
 APPROVED, AS IT WOULD CREATE A DIMENSIONAL
 NONCONFORMITY AND INCREASE THE NONCONFORMITY WITH
 RESPECT TO DENSITY.
  
 ***LOTS MUST BE UNIFIED AS ONE PARCEL, BACK TO ORIGINAL
 FORM*** ***THIS LOT IS NOT BUILDABLE***
  
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720
  
  
  
 SENT TO "AD"

Review Stop Z ZONING
Rev No 2 Status F Date 2007-08-10 Cont ID  
Sent By choops Date 2007-08-10 Time 14:25 Rev Time 0.00
Received By choops Date 2007-08-10 Time 14:25 Sent To E
Notes
2007-08-10 14:35:16***FAILED******RESUB. #1***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM A/C EQUIPMENT TO
 THE PROPERTY LINES. (REPEAT COMMENT)
  
 2)SHOW ELEVATION DIMENSIONS FROM GRADE TO THE
 MIDPOINT OF THE ROOF'S PITCH (REPEAT COMMENT)
  
 3)PROPOSED DRIVEWAY EXCEEDS MAXIMUM IMPERMEABLE
 SURFACE ALLOWABLE WITHIN THE FRONT YARD.PROPOSED =
 331.5 SQ. FT. (NOT INCLUDING WALKWAY)ALLOWABLE =
 318.75 SQ.FT. (INCLUDING FRONT OF WALKWAY THAT EXTENDS
 PAST FRONT EDGE OF GARAGE).PURSUANT TO THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS, SECTION 94-482(A):
  
 LOCATION AND SURFACE.REQUIRED OFF-STREET PARKING
 SPACES FOR LESS THAN FOUR RESIDENTIAL DWELLING UNITS
 SHALL BE LOCATED ON THE PROPERTY ON WHICH THE UNITS ARE
 CONSTRUCTED. REQUIRED PARKING MAY BE LOCATED IN A FRONT
 YARD; HOWEVER, THE LESSER OF 1,000 SQUARE FEET OR 75
 PERCENT OF THE FRONT YARD AREA MUST BE LANDSCAPED.
 PARKING AREAS LOCATED IN THE FRONT YARD SHALL BE
 SURFACED WITH A SMOOTH, NONDUSTING SURFACE IN
 COMPLIANCE WITH SUBSECTION 33-485(E). IT SHALL BE A
 VIOLATION OF THIS CHAPTER TO PARK ON ANY UNPAVED AREAS
 AS DESCRIBEDIN THIS ARTICLE.
  
 4)PROVIDE A DATA TABLE ON THE LANDSCAPE PLAN SHOWING
 THE OPEN SPACE CALCULATIONS, HOW MANY TREES/SHRUBS ARE
 REQUIRED AND HOW MANY ARE PROVIDED.
  
 5)PROVIDED DEEDS DO NOT PROVIDE PROOF OF A LEGAL
 SUBDIVISION, THEY SIMPLY SHOW THAT THE LOTS WERE INDEED
 SOLD. ***PARCEL APPEARS TO BE ILLEGALLY SUBDIVIDED***
 EITHER PROVIDE PROOF OF A LEGAL SUBDIVISION OR CONTACT
 THE PLANNING DEPARTMENT (561)822-1435 TO POTENTIALLY
 SUBDIVIDE LEGALLY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-12 Cont ID  
Sent By choops Date 2007-06-12 Time 10:26 Rev Time 0.00
Received By choops Date 2007-06-12 Time 10:26 Sent To E
Notes
2007-06-12 10:33:44***FAILED***
  
  
 1)***PARCEL APPEARS TO BE ILLEGALLY SUBDIVIDED***
 EITHER PROVIDE PROOF OF A LEGAL SUBDIVISION OR CONTACT
 THE PLANNING DEPARTMENT (561)822-1435 TO POTENTIALLY
 SUBDIVIDE LEGALLY.ONCE THIS PROCESS IS COMPLETE OR
 PROOF IS SHOWN...THE FOLLOWING COMMENTS NEED
 ADDRESSED.
  
 2)PLEASE PROVIDE A LANDSCAPE PLAN THAT INDICATES
 COMPLIANCE WITH SECTION 94-442 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 3)PLEASE PROVIDE ELEVATION DIMENSIONS FROM GRADE TO
 THE MIDPOINT OF THE ROOF'S PITCH.
  
 4)PLEASE PROVIDE 2 COPIES OF AN UPDATED SURVEY
 SHOWING THE SCOPE OF WORK WITH DIMENSIONS AND SETBACK
 DIMENSIONS TO PROPERTY LINES.
  
 5)SHOW ANY PROPOSED A/C OR MECHANICAL EQUIPMENT ON
 SURVEYS AND SITE PLANS WITH SETBACK DIMENSIONS TO
 PROPERTY LINES.
  
 6)IS THE DRIVEWAY PROPOSED ON THIS PERMIT?IF SO,
 PROVIDE DIMENSIONS IN DETAIL.IF NOT, DRIVEWAY TO BE
 ON A SEPERATE PERMIT.
  
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720