Plan Review Details - Permit 07060235
Plan Review Stops For Permit 07060235
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-07-25 Cont ID  
Sent By mjacobs Date 2007-07-25 Time 09:08 Rev Time 0.00
Received By mjacobs Date 2007-07-25 Time 09:08 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-24 Cont ID  
Sent By mjacobs Date 2007-07-24 Time 06:06 Rev Time 0.00
Received By mjacobs Date 2007-07-23 Time 15:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-05 Cont ID  
Sent By mjacobs Date 2007-07-05 Time 11:05 Rev Time 0.00
Received By mjacobs Date 2007-07-05 Time 10:30 Sent To  
Notes
2007-07-05 11:05:32BUILDING PLAN REVIEW
 PERMIT: 07060235
 ADD: 917 N. FLAGLER DR.
 CONT: LARRY R CASTIGLIONE INC.
 TEL: (561)588-9375
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)AS NOTED PREVIOUSLY : THE PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RRECORD RETENTION PROGRAM. THIS
 POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT.
  
 3)ALL PLANS AND SPECIFICATIONS BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DRAWINGS. IF THE DESIGNER IS
 A PROFESSIONAL ARCHITECT OR ENGINEER, THAT PERSON SHALL
 AFFIX HIS/HER SEAT TO THE DRAWINGS AS REQUIRED PER
 FLORIDA STATUTESCH. 481 AND 471. FOR MORE INFORMATION
 SEE FBC.106.1.
  
 4)SHOW AN ELEVATION DETAIL OF THE PROPOSED NEW WALLS
 IN EACH AREA WHERE CHANGES WILL BE MADE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By mjacobs Date 2007-06-19 Time 12:56 Rev Time 0.00
Received By mjacobs Date 2007-06-19 Time 12:36 Sent To  
Notes
2007-06-19 12:42:24BUILDING PLAN REVIEW
 PERMIT: 07060235
 ADD: 917 N. FLAGLER DR. #412
 CONT: LARRY R. CASTILIONE INC.
 TEL: (561)588-9375
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FBC 106.1.3*BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE.
  
 3)ALL PLANS AND SPECIFICATIONS BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DRAWINGS. IF THE DESIGNER IS
 A PROFESSIONAL ARCHITECT OR ENGINEER, THAT PERSON SHALL
 AFFIX HIS/HER SEAL TO THE DRAWINGS AS REQUIRED PER
 FLORIDA STATUTES CH.481 AND 471.
  
 4)SHOW A DETAIL OF THE PROPOSED NEW WALLS LISTING THE
 MATERIALS WHICH WILL BE USED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-07-20 Cont ID  
Sent By btrobaug Date 2007-07-19 Time 13:13 Rev Time 0.00
Received By btrobaug Date 2007-07-19 Time 13:03 Sent To  
Notes
2007-07-19 13:13:26 
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-20 Cont ID  
Sent By btrobaug Date 2007-07-05 Time 08:21 Rev Time 0.00
Received By btrobaug Date 2007-07-05 Time 07:58 Sent To  
Notes
2007-07-19 13:11:42 
  
 NOTE
 CHANGED FROM PASS TO FAIL, NO ELECRTICAL PLANS
 SUBMITTED WITH 7/11/07 RESUB. SET OF DRAWINGS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-15 Cont ID  
Sent By btrobaug Date 2007-06-15 Time 15:41 Rev Time 0.00
Received By btrobaug Date 2007-06-15 Time 15:39 Sent To  
Notes
2007-06-15 15:41:22 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
  
 THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
  
 TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR REVIEW
 PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-07-24 Cont ID  
Sent By mawillia Date 2007-07-24 Time 17:54 Rev Time 0.00
Received By mawillia Date 2007-07-24 Time 17:47 Sent To B1
Notes
2007-07-24 17:59:50*****PROVISO*****
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE REMOVAL OF AND/OR THE STOCKING OF NEW BUIDLING
 MATERIALS & SUPPLIES SHALL NOT HINDER, INTERFERE, OR
 OBSTRUCT ACCESS TO OR EGRESS FROM THE PROPERTY
 INCLUDING THE FLOOR'S EXIT CORRIDORS.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-07-06 Cont ID  
Sent By mwennerg Date 2007-07-06 Time 13:58 Rev Time 0.00
Received By mwennerg Date 2007-07-06 Time 13:58 Sent To  
Notes
2007-07-06 14:08:45***DENIED***
  
 PLEASE NOTE THAT THERE IS NO RESPONSE TO THE FIRST FIRE
 REVIEW. PLEASE SEE REVIEW COMMENTS TAKEN FROM PREVIOUS
 FIRE REVIEW:
  
 1) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2) THE REMOVAL OF AND/OR THE STOCKING OF NEW BUILDING
 MATERIALS AND SUPPLIES SHALL NOT HINDER, INTERFERE OR
 OBSTRUCT ACCESS TO OR EGRESS FROM THE PROPERTY
 INCLUDING THE FLOOR'S EXIT CORRIDORS.
  
 3) PLEASE INDICATE IF THE ERECTION OF THE NEW PARTITION
 WALL IMPACTS FIRE SPRINKLER DEVICES. SEPARATE SHOP
 DRAWINGS AND PERMIT IS REQUIRED IF THE FIRE PROTECTION
 SYSTEM HAS TO BE MODIFIED.
 PLEASE RESPOND ON PLANS OR RESPONSE LETTER
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By mawillia Date 2007-06-20 Time 13:28 Rev Time 0.00
Received By mawillia Date 2007-06-20 Time 13:08 Sent To  
Notes
2007-06-20 13:26:50*****UNSAT*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE REMOVAL OF AND/OR THE STOCKING OF NEW BUIDLING
 MATERIALS & SUPPLIES SHALL NOT HINDER, INTERFERE, OR
 OBSTRUCT ACCESS TO OR EGRESS FROM THE PROPERTY
 INCLUDING THE FLOOR'S EXIT CORRIDORS.
  
 3.PLEASE INDICATE IF THE ERECTION OF THE NEW
 PARTITION WALL IMPACTS FIRE SPRINKLER DEVICES. SEPARATE
 PLANS AND PERMIT WILL BE REQUIRED IF THE THE FIRE
 PROTECTIONS SYSTEM HAS TO BE MODIFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-13 Cont ID  
Sent By adarroug Date 2007-07-13 Time 10:26 Rev Time 0.00
Received By adarroug Date 2007-07-13 Time 10:26 Sent To  
Notes
2007-07-17 14:23:32TO "BOB"#4
2007-07-13 10:27:03WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-02 Cont ID  
Sent By adarroug Date 2007-07-02 Time 11:03 Rev Time 0.00
Received By adarroug Date 2007-07-02 Time 11:03 Sent To  
Notes
2007-07-02 11:04:01TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-20 Cont ID  
Sent By mawillia Date 2007-06-20 Time 13:10 Rev Time 0.00
Received By mawillia Date 2007-06-11 Time 08:22 Sent To  
Notes
2007-06-12 08:25:57TO "BOB"#7
2007-06-11 08:23:08WAITING FOR "BOB"

Review Stop Z ZONING
Rev No 1 Status N Date 2007-07-24 Cont ID  
Sent By choops Date 2007-07-24 Time 10:51 Rev Time 0.00
Received By choops Date 2007-07-24 Time 10:51 Sent To  
Notes
2007-07-24 10:51:29*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved