Plan Review Details - Permit 07060197
Plan Review Stops For Permit 07060197
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-07-25 Cont ID  
Sent By kconrad Date 2007-07-25 Time 18:14 Rev Time 0.00
Received By kconrad Date 2007-07-25 Time 16:54 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-18 Cont ID  
Sent By kconrad Date 2007-06-18 Time 19:17 Rev Time 0.00
Received By kconrad Date 2007-06-18 Time 15:47 Sent To I
Notes
2007-06-18 16:53:50 
 PROJECT: 777 SOUTH FLAGLER, WEST TOWER, SUITE #1701
 PLAN REVIEW: 2004 FLORIDABUILDING AND EXISTING
 BUILDING CODE WITH 2006 REVISIONS
 1ST REVIEW
 STATUS: DENIED
  
  
 PLAN REVIEW COMMENTS:
  
 1) PRIOR TO RE-SUBMITTING THE REVIEWED PLANS, PLEASE
 MAKE CERTAIN TO REVIEW AND ADDRESS EACH COMMENT AS
 NOTED BELOW AND MAKE ALL CORRECTIONS WHERE APPLICABLE.
 FAILURE TO DO SO WILL IMPEDE THE EXPEDITING OF THE
 PERMIT ISSUANCE.
  
 2) 105.8 NOTICE OF COMMENCEMENT.
  
 AS PER SECTION 713.135, FLORIDA STATUTES, WHEN ANY
 PERSON APPLIES FOR A BUILDING PERMIT, THE AUTHORITY
 ISSUING SUCH PERMIT SHALL PRINT ON THE FACE OF EACH
 PERMIT CARD IN NO LESS THAN 18-POINT, CAPITALIZED,
 BOLDFACED TYPE:"WARNING TO OWNER: YOUR FAILURE TO
 RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR
 PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU
 INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR
 AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF
 COMMENCEMENT."
  
 3)301.5 . A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 4) AS PER THE FBC 106.3.5, PLEASE PROVIDE THE FOLLOWING
 DATA:
  
 A) BUILDING CONSTRUCTION TYPE
 B) OCCUPANCY LOAD
 C) OCCUPANCY GROUP
 D) SPRINKLERED OR NON-SPRINKLERED.
  
 5) INDICATE EXIT SIGNS AS PER FBC 1006.3 ON SHEETS
 A-LS1 AND A-2, SAFETY AND REFLECTED CEILING PLAN
 RESPECTIVELY:
  
 1006.3 EXIT SIGNS.
  
 1006.3.1
 EXITS SHALL BE MARKED BY AN APPROVED SIGN READILY
 VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. EVERY EXIT
 SIGN SHALL BE SUITABLY ILLUMINATED BY A RELIABLE LIGHT
 SOURCE. EXTERNALLY AND INTERNALLY ILLUMINATED SIGNS
 SHALL BE VISIBLE IN BOTH NORMAL AND EMERGENCY
 LIGHTING.
 EXCEPTION: MAIN EXTERIOR EXIT DOORS THAT OBVIOUSLY AND
 CLEARLY ARE IDENTIFIABLE AS EXITS.
  
 6) PLEASE INDICATE TRAVEL DISTANCESAND THE OCCUPANCY
 LOAD ON THE LIFE SAFETY PLAN AS PER THE WEST PALM BEACH
 ADMINISTRATIVE CODE, SECTION 106.3.5.1.1(7).
  
 6A)605.4.1TWO EGRESS DOORWAYS REQUIRED.
  
 WORK AREAS SHALL BE PROVIDED WITH TWO EGRESS DOORWAYS
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTIONS
 605.4.1.1 AND 605.4.1.2.
 605.4.1.1
 OCCUPANT LOAD AND TRAVEL DISTANCE.
 IN ANY WORK AREA, ALL ROOMS AND SPACES HAVING AN
 OCCUPANT LOAD GREATER THAN 50 OR IN WHICH THE TRAVEL
 DISTANCE TO AN EXIT EXCEEDS 75 FEET (22 860 MM) SHALL
 HAVE A MINIMUM OF TWO EGRESS DOORWAYS.
 EXCEPTION: STORAGE ROOMS IN GROUP S1 AND S2 OCCUPANCIES
 HAVING A MAXIMUM OCCUPANT LOAD OF 10.
  
  
 7) PLEASE PROVIDE PRODUCT SPECIFICATIONS FOR THE
 FOLLOWING:
  
  
 A) NEW CARPET AS INDICATED ON SHEET A-ID1.
 B) WALL COVERING AS INDICATED BY MARK WC-2 ON SHEET
 A-ID1.
 C) NEW ENGINEERED WOOD FLOORING, MARK WF-1 ON SHEET
 A-ID1.
  
 PLEASE NOTE THAT ALL NEWLY INSTALLED INTERIOR
 FINISHES SHALL COMPLY WITH THE FLORIDA BUILDING CODE,
 SECTION 803.5:
  
 803.5 INTERIOR FINISH REQUIREMENTS BASED ON
 GROUP.
 INTERIOR WALL AND CEILING FINISH SHALL HAVE A FLAME
 SPREAD INDEX NOT GREATER THAN THAT SPECIFIED IN TABLE
 803.5 FOR THE GROUP AND LOCATION DESIGNATED. INTERIOR
 WALL AND CEILING FINISH MATERIALS, OTHER THAN TEXTILES,
 TESTED IN ACCORDANCE WITH NFPA 286 AND MEETING THE
 ACCEPTANCE CRITERIA OF SECTION 803.2.1, SHALL BE
 PERMITTED TO BE USED WHERE A CLASS A CLASSIFICATION IN
 ACCORDANCE WITH ASTM E 84 IS REQUIRED.
  
 8) PLEASE PROVIDE EXISTING/NEW DOOR SCHEDULE.
  
 9) PLEASE INDICATE THE EXISTING RATED WALL PARTITIONS
 AND FIRE RESISTIVITY ON THE OVERALL FLOOR PLAN, SHEET
 A-1.
  
 10) RAISED FLOORING SHALL CONFORM TO THE FOLLOWING
 REQUIREMENTS OF FBC 717.2.7
  
 717.2.7 CONCEALED SLEEPER SPACES.
  
 WHERE WOOD SLEEPERS ARE USED FOR LAYING WOOD FLOORING
 ON MASONRY OR CONCRETE FIRE-RESISTANCE-RATED FLOORS,
 THE SPACE BETWEEN THE FLOOR SLAB AND THE UNDERSIDE OF
 THE WOOD FLOORING SHALL BE FILLED WITH AN APPROVED
 MATERIAL TO RESIST THE FREE PASSAGE OF FLAME AND
 PRODUCTS OF COMBUSTION OR FIREBLOCKED IN SUCH A MANNER
 THAT THERE WILL BE NO OPEN SPACES UNDER THE FLOORING
 THAT WILL EXCEED 100 SQUARE FEET (9.3 M2) IN AREA AND
 SUCH SPACE SHALL BE FILLED SOLIDLY UNDER PERMANENT
 PARTITIONS SO THAT THERE IS NO COMMUNICATION UNDER THE
 FLOORING BETWEEN ADJOINING ROOMS.
 EXCEPTIONS:
  
 1.FIREBLOCKING IS NOT REQUIRED FOR SLAB-ON-GRADE FLOORS
 IN GYMNASIUMS.
 2.FIREBLOCKING IS REQUIRED ONLY AT THE JUNCTURE OF EACH
 ALTERNATE LANE AND AT THE ENDS OF EACH LANE IN A
 BOWLING FACILITY.
  
 11) ALL WOOD BUCKS AND BLOCKING TO BE FIRE RETARDANT
 TREATED LUMBER AS PER THE FOLLOWING:
  
 717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I
 OR II CONSTRUCTION.
 COMBUSTIBLES SHALL NOT BE PERMITTED IN CONCEALED SPACES
 OF BUILDINGS OF TYPE I OR II CONSTRUCTION. EXCEPTIONS:
 1. COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION
 603.
 2. COMBUSTIBLE MATERIALS COMPLYING WITH SECTION 602 OF
 THE FLORIDA BUILDING CODE, MECHANICAL.
 3. CLASS A INTERIOR FINISH MATERIALS. 4. COMBUSTIBLE
 PIPING WITHIN PARTITIONS OR ENCLOSED SHAFTS INSTALLED
 IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE.
 COMBUSTIBLE PIPING SHALL BEPERMITTED WITHIN
 CONCEALED CEILING SPACES WHERE INSTALLED IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE, MECHANICAL AND THE
 FLORIDA BUILDING CODE, PLUMBING.
  
  
 12) PROVIDE DETAILS FOR THE INSTALLATION OF THE NEW
 CLORESTORY WINDOWS:
  
 A) GLAZING SPECIFICATIONS.
 B) WALL FRAMING/ATTACHMENT DETAILS.
  
 13) PROVIDE NEW METAL WALL AND CEILING FRAMING DETAILS
 AS REFLECTED ON SHEET A-3 DETAIL 06 AND SECTION 05/A6.
  
 14) PLEASE PROVIDEAN OVERALL DEMOLITION FLOOR PLAN,
 SHEET A-D1 FOR CONSTRUCTION CLARIFICATION AS PER THE
 FOLLOWING:
  
 106.1 SUBMITTAL DOCUMENTS.
 CONSTRUCTION DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND OTHER DATA SHALL
 BE SUBMITTED IN ONE OR MORE SETS WITH EACH APPLICATION
 FOR A PERMIT. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A DESIGN PROFESSIONAL WHERE REQUIRED BY THE
 STATUTES. WHERE SPECIAL CONDITIONS EXIST, THE BUILDING
 OFFICIAL IS AUTHORIZED TO REQUIRE ADDITIONAL
 CONSTRUCTION DOCUMENTS TO BE PREPARED BY A DESIGN
 PROFESSIONAL.
  
  
 BUILDING PLANS EXAMINER: KEN CONRAD
 PHONE: 561.805.6666
 FAX: 561.805.6676

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-12 Cont ID  
Sent By btrobaug Date 2007-07-12 Time 17:26 Rev Time 0.00
Received By btrobaug Date 2007-07-12 Time 15:06 Sent To  
Notes
2007-07-12 15:23:39 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW, WITH
 ORIGINAL COMMENT NUMBER ATTACHED.
  
 2} NOTE: PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS
 SHALL BE BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR
 FOR THE CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE
 SEE ARTICLE.
 A)COMMENT TO RESPONSE. THIS ARTICLE DOES APPLY.AS
 THERE ARE NO EXEPTIONS LISTED IN THAT ARTICLE. SEE
 DETAIL #1, SHEET E7.1, DETAILS 02, 03, 04 AND 05, SHEET
 A-2.. A NOTE ON THE PLAN REFERENCING THIS ARTICLE WILL
 SUFFICE
  
 5} PROVIDE EMERGENCY ILLUMINATION PER
 NFPA-101 7.8 (2003), AND CIRCUITED PER
 700.12 NEC. INDICATE SAME ON PLANS.
 A) THIS IS REQUIRED IN THE PLAN REVIEW STAGE OF THE
 PERMITTING PROCESS, THE CIRCUITING MUST BE REVIEWED FOR
 COMPLIANCE.
  
 6} INDICATE CIRCUIT NUMBERS ON ALL ADDED DEVICES AND
 ALL DEVICES ON THAT CIRCUIT, SO THAT 220.14(I) MAY BE
 REVIEWED. NOTE #2 ON THE ELECTRICAL SHEETS REQUIRES A
 CALCULATION BEFORE ASSEMING MORE DEVICES MAY BE ADDED.
 A) SAME COMMENT AS ABOVE..
  
 7} SAME AS COMMENT #6 BUT FOR ADDED FIXTURE LOADS.
 INDICATE CIRCUIT NUMBERS.
  
 SEE 553.80(2)(B), ATTACHED, REGARDING DESIGN
 PROFESSIONALS DOCUMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By btrobaug Date 2007-06-20 Time 09:22 Rev Time 0.00
Received By btrobaug Date 2007-06-20 Time 07:32 Sent To  
Notes
2007-06-20 08:02:50 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 2} NOTE: PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS
 SHALL BE BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR
 FOR THE CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE
 SEE ARTICLE.
  
 3} THE "SIMPLEX LOCK" NOTED ON SHEET A-E1, MUST BE
 PERMITEDUNDER SEPARATE APPLICATION, WITH ALL
 EQUIPMENT SPECIFICATION.
  
 4} SHEET NOTES ON ELECTRICAL SHEETS INDICATE A SHEET
 E7.2, THIS SHEET IS MISSING.
  
 5} PROVIDE EMERGENCY ILLUMINATION PER
 NFPA-101 7.8 (2003), AND CIRCUITED PER
 700.12 NEC. INDICATE SAME ON PLANS.
  
 6} INDICATE CIRCUIT NUMBERS ON ALL ADDED DEVICES AND
 ALL DEVICES ON THAT CIRCUIT, SO THAT 220.14(I) MAY BE
 REVIEWED. NOTE #2 ON THE ELECTRICAL SHEETS REQUIRES A
 CALCULATION BEFORE ASSEMING MORE DEVICES MAY BE ADDED.
  
 7} SAME AS COMMENT #6 BUT FOR ADDED FIXTURE LOADS.
 INDICATE CIRCUIT NUMBERS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-07-24 Cont ID  
Sent By mawillia Date 2007-07-24 Time 19:04 Rev Time 0.00
Received By mawillia Date 2007-07-24 Time 18:16 Sent To  
Notes
2007-07-24 19:03:26*****UNSAT******
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 07.INDICATE THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIALS AS CLASS A, CLASS B, OR CLASS C.BE SPECIFIC
 IN TERMS OF CLASS A, CLASS B, OR CLASS C IN THE EXITS,
 EXIT ACCESS CORRIDORS, AND OTHER AREAS.
  
 08.INDICATE THE LOCATION OF THE EMERGENCY LIGHTS.
 EMERGENCY LIGHT(S) APPEAR TO BE LACKING IN THE SOUTH
 END OF CORRIDOR 001;SEE SHEETSA-2,E1.1
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE PLAN) EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-22 Cont ID  
Sent By mawillia Date 2007-06-22 Time 12:28 Rev Time 0.00
Received By mawillia Date 2007-06-22 Time 11:02 Sent To  
Notes
2007-06-22 12:28:18*****DENIED*****
  
  
 01.ON SHEET A-T1 UNDER APPLICABLE CODES, AMEND TO
 REFLECT THAT NFPA 1 (2003 EDITION) AND NFPA 101 (2003
 EDITION) SHALL BE REFERENCED.
  
 02.PLEASE EXPLAIN THE REFERENCES TO NFPA 45, NFPA
 88B-97, AND NFPA 102-95 UNDER THE APPLICABLE CODES. ARE
 THESE REFERENCES PERTINENT TO THE PROPOSED SCOPE OF
 WORK?
  
 03.THE TENANT SPACE SUITE NUMBER SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE PREMISES AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY FOR SAFE
 OPERATION.
  
 06.THE REMOVAL OF EXISTING AND/OR THE STOCKING OF NEW
 BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE OR
 HINDER ACCESS TO OR EGRESS FROM THE SAID TENANT SPACE
 OR OTHER TENANT SPACES ON THE 17TH FLOOR.
  
 07.INDICATE THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIALS AS CLASS A, CLASS B, OR CLASS C.BE
 SPECIFIC
  
 08.INDICATE THE LOCATION OF THE EMERGENCY LIGHTS.
  
 09.PLANS DO NOT STATE OR SHOW THE PRESENCE OF THE
 TENANT SPACE BEING SPRINKLERED.IF SPRINKLERED AND
 MODICATIONS TO THE SYSTEM IS NEEDED, SEPARATE PLANS AND
 PERMIT SHALL BE REQUIRED.
  
 10.PLANS DO NOTSTATE OR SHOW THE PRESENCE OF FIRE
 ALARM OR FIRE ALARM DEVICES FOR THIS TENANT SPACE.IF
 SO EQUIPPED AND MODICATIONS TO THE SYSTEM IS NEEDED,
 SEPARATE PLANS AND PERMIT WILL BE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE PLAN) EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 12:51 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 12:51 Sent To  
Notes
2007-08-06 12:51:20WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-03 Cont ID  
Sent By adarroug Date 2007-07-03 Time 08:09 Rev Time 0.00
Received By adarroug Date 2007-07-03 Time 08:09 Sent To  
Notes
2007-07-09 15:36:50TO "BOB"#11
2007-07-03 08:09:34WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-25 Cont ID  
Sent By jleech Date 2007-06-25 Time 15:06 Rev Time 0.00
Received By jleech Date 2007-06-08 Time 14:17 Sent To  
Notes
2007-06-11 15:29:24TO "BOB"#2
2007-06-08 14:18:38WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-07-10 Cont ID  
Sent By tgordon Date 2007-07-10 Time 11:47 Rev Time 0.25
Received By tgordon Date 2007-07-10 Time 11:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-14 Cont ID  
Sent By tgordon Date 2007-06-14 Time 12:11 Rev Time 0.30
Received By tgordon Date 2007-06-14 Time 12:11 Sent To  
Notes
2007-06-14 12:24:50*** DENIED ***
 1) SEE PLANS PAGE A-T1 APPLICABLE CODES ARE REFERENCING
 THE FBC SECOND EDITION WITH 2003 REVISIONS. THE CODE
 THAT IS IN USE AT THIS TIME IS THE 2004 FBC WITH THE
 2006 REVISIONS, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-07-12 Cont ID  
Sent By jleech Date 2007-07-12 Time 11:01 Rev Time 0.00
Received By jleech Date 2007-07-12 Time 11:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-25 Cont ID  
Sent By jleech Date 2007-06-25 Time 14:50 Rev Time 0.00
Received By jleech Date 2007-06-25 Time 14:50 Sent To  
Notes
2007-06-25 15:03:42DENIED;
 NOT ENOUGH INFORMATION TO DO A PLUMBING PLAN REVIEW;
 1. BREAK AREA,IS PLUMBING TO SINK NEW OR
 EXISTING?
 2. IS ICE MACHINE DRAIN THRU FLOOR DRAIN OR
 INDIRECT FITTING? PLEASE SHOW
 3. NEED MORE INFORMATION ON SODA MACHINE.
 PLEASE SEND CUT SHEET.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-07-24 Cont ID  
Sent By choops Date 2007-07-24 Time 11:30 Rev Time 0.00
Received By choops Date 2007-07-24 Time 11:30 Sent To  
Notes
2007-07-24 11:31:07*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.