2007-06-18 16:53:50 | |
| PROJECT: 777 SOUTH FLAGLER, WEST TOWER, SUITE #1701 |
| PLAN REVIEW: 2004 FLORIDABUILDING AND EXISTING |
| BUILDING CODE WITH 2006 REVISIONS |
| 1ST REVIEW |
| STATUS: DENIED |
| |
| |
| PLAN REVIEW COMMENTS: |
| |
| 1) PRIOR TO RE-SUBMITTING THE REVIEWED PLANS, PLEASE |
| MAKE CERTAIN TO REVIEW AND ADDRESS EACH COMMENT AS |
| NOTED BELOW AND MAKE ALL CORRECTIONS WHERE APPLICABLE. |
| FAILURE TO DO SO WILL IMPEDE THE EXPEDITING OF THE |
| PERMIT ISSUANCE. |
| |
| 2) 105.8 NOTICE OF COMMENCEMENT. |
| |
| AS PER SECTION 713.135, FLORIDA STATUTES, WHEN ANY |
| PERSON APPLIES FOR A BUILDING PERMIT, THE AUTHORITY |
| ISSUING SUCH PERMIT SHALL PRINT ON THE FACE OF EACH |
| PERMIT CARD IN NO LESS THAN 18-POINT, CAPITALIZED, |
| BOLDFACED TYPE:"WARNING TO OWNER: YOUR FAILURE TO |
| RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR |
| PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU |
| INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR |
| AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF |
| COMMENCEMENT." |
| |
| 3)301.5 . A DESIGN PROFESSIONAL OR AN |
| OWNER MUST ELECT ONE OR A COMBINATION OF |
| LEVELS OF ALTERATION PURSUANT TO SECTION |
| 303,304 & 305 OF THIS CODE. |
| |
| 4) AS PER THE FBC 106.3.5, PLEASE PROVIDE THE FOLLOWING |
| DATA: |
| |
| A) BUILDING CONSTRUCTION TYPE |
| B) OCCUPANCY LOAD |
| C) OCCUPANCY GROUP |
| D) SPRINKLERED OR NON-SPRINKLERED. |
| |
| 5) INDICATE EXIT SIGNS AS PER FBC 1006.3 ON SHEETS |
| A-LS1 AND A-2, SAFETY AND REFLECTED CEILING PLAN |
| RESPECTIVELY: |
| |
| 1006.3 EXIT SIGNS. |
| |
| 1006.3.1 |
| EXITS SHALL BE MARKED BY AN APPROVED SIGN READILY |
| VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. EVERY EXIT |
| SIGN SHALL BE SUITABLY ILLUMINATED BY A RELIABLE LIGHT |
| SOURCE. EXTERNALLY AND INTERNALLY ILLUMINATED SIGNS |
| SHALL BE VISIBLE IN BOTH NORMAL AND EMERGENCY |
| LIGHTING. |
| EXCEPTION: MAIN EXTERIOR EXIT DOORS THAT OBVIOUSLY AND |
| CLEARLY ARE IDENTIFIABLE AS EXITS. |
| |
| 6) PLEASE INDICATE TRAVEL DISTANCESAND THE OCCUPANCY |
| LOAD ON THE LIFE SAFETY PLAN AS PER THE WEST PALM BEACH |
| ADMINISTRATIVE CODE, SECTION 106.3.5.1.1(7). |
| |
| 6A)605.4.1TWO EGRESS DOORWAYS REQUIRED. |
| |
| WORK AREAS SHALL BE PROVIDED WITH TWO EGRESS DOORWAYS |
| IN ACCORDANCE WITH THE REQUIREMENTS OF SECTIONS |
| 605.4.1.1 AND 605.4.1.2. |
| 605.4.1.1 |
| OCCUPANT LOAD AND TRAVEL DISTANCE. |
| IN ANY WORK AREA, ALL ROOMS AND SPACES HAVING AN |
| OCCUPANT LOAD GREATER THAN 50 OR IN WHICH THE TRAVEL |
| DISTANCE TO AN EXIT EXCEEDS 75 FEET (22 860 MM) SHALL |
| HAVE A MINIMUM OF TWO EGRESS DOORWAYS. |
| EXCEPTION: STORAGE ROOMS IN GROUP S1 AND S2 OCCUPANCIES |
| HAVING A MAXIMUM OCCUPANT LOAD OF 10. |
| |
| |
| 7) PLEASE PROVIDE PRODUCT SPECIFICATIONS FOR THE |
| FOLLOWING: |
| |
| |
| A) NEW CARPET AS INDICATED ON SHEET A-ID1. |
| B) WALL COVERING AS INDICATED BY MARK WC-2 ON SHEET |
| A-ID1. |
| C) NEW ENGINEERED WOOD FLOORING, MARK WF-1 ON SHEET |
| A-ID1. |
| |
| PLEASE NOTE THAT ALL NEWLY INSTALLED INTERIOR |
| FINISHES SHALL COMPLY WITH THE FLORIDA BUILDING CODE, |
| SECTION 803.5: |
| |
| 803.5 INTERIOR FINISH REQUIREMENTS BASED ON |
| GROUP. |
| INTERIOR WALL AND CEILING FINISH SHALL HAVE A FLAME |
| SPREAD INDEX NOT GREATER THAN THAT SPECIFIED IN TABLE |
| 803.5 FOR THE GROUP AND LOCATION DESIGNATED. INTERIOR |
| WALL AND CEILING FINISH MATERIALS, OTHER THAN TEXTILES, |
| TESTED IN ACCORDANCE WITH NFPA 286 AND MEETING THE |
| ACCEPTANCE CRITERIA OF SECTION 803.2.1, SHALL BE |
| PERMITTED TO BE USED WHERE A CLASS A CLASSIFICATION IN |
| ACCORDANCE WITH ASTM E 84 IS REQUIRED. |
| |
| 8) PLEASE PROVIDE EXISTING/NEW DOOR SCHEDULE. |
| |
| 9) PLEASE INDICATE THE EXISTING RATED WALL PARTITIONS |
| AND FIRE RESISTIVITY ON THE OVERALL FLOOR PLAN, SHEET |
| A-1. |
| |
| 10) RAISED FLOORING SHALL CONFORM TO THE FOLLOWING |
| REQUIREMENTS OF FBC 717.2.7 |
| |
| 717.2.7 CONCEALED SLEEPER SPACES. |
| |
| WHERE WOOD SLEEPERS ARE USED FOR LAYING WOOD FLOORING |
| ON MASONRY OR CONCRETE FIRE-RESISTANCE-RATED FLOORS, |
| THE SPACE BETWEEN THE FLOOR SLAB AND THE UNDERSIDE OF |
| THE WOOD FLOORING SHALL BE FILLED WITH AN APPROVED |
| MATERIAL TO RESIST THE FREE PASSAGE OF FLAME AND |
| PRODUCTS OF COMBUSTION OR FIREBLOCKED IN SUCH A MANNER |
| THAT THERE WILL BE NO OPEN SPACES UNDER THE FLOORING |
| THAT WILL EXCEED 100 SQUARE FEET (9.3 M2) IN AREA AND |
| SUCH SPACE SHALL BE FILLED SOLIDLY UNDER PERMANENT |
| PARTITIONS SO THAT THERE IS NO COMMUNICATION UNDER THE |
| FLOORING BETWEEN ADJOINING ROOMS. |
| EXCEPTIONS: |
| |
| 1.FIREBLOCKING IS NOT REQUIRED FOR SLAB-ON-GRADE FLOORS |
| IN GYMNASIUMS. |
| 2.FIREBLOCKING IS REQUIRED ONLY AT THE JUNCTURE OF EACH |
| ALTERNATE LANE AND AT THE ENDS OF EACH LANE IN A |
| BOWLING FACILITY. |
| |
| 11) ALL WOOD BUCKS AND BLOCKING TO BE FIRE RETARDANT |
| TREATED LUMBER AS PER THE FOLLOWING: |
| |
| 717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I |
| OR II CONSTRUCTION. |
| COMBUSTIBLES SHALL NOT BE PERMITTED IN CONCEALED SPACES |
| OF BUILDINGS OF TYPE I OR II CONSTRUCTION. EXCEPTIONS: |
| 1. COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION |
| 603. |
| 2. COMBUSTIBLE MATERIALS COMPLYING WITH SECTION 602 OF |
| THE FLORIDA BUILDING CODE, MECHANICAL. |
| 3. CLASS A INTERIOR FINISH MATERIALS. 4. COMBUSTIBLE |
| PIPING WITHIN PARTITIONS OR ENCLOSED SHAFTS INSTALLED |
| IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE. |
| COMBUSTIBLE PIPING SHALL BEPERMITTED WITHIN |
| CONCEALED CEILING SPACES WHERE INSTALLED IN ACCORDANCE |
| WITH THE FLORIDA BUILDING CODE, MECHANICAL AND THE |
| FLORIDA BUILDING CODE, PLUMBING. |
| |
| |
| 12) PROVIDE DETAILS FOR THE INSTALLATION OF THE NEW |
| CLORESTORY WINDOWS: |
| |
| A) GLAZING SPECIFICATIONS. |
| B) WALL FRAMING/ATTACHMENT DETAILS. |
| |
| 13) PROVIDE NEW METAL WALL AND CEILING FRAMING DETAILS |
| AS REFLECTED ON SHEET A-3 DETAIL 06 AND SECTION 05/A6. |
| |
| 14) PLEASE PROVIDEAN OVERALL DEMOLITION FLOOR PLAN, |
| SHEET A-D1 FOR CONSTRUCTION CLARIFICATION AS PER THE |
| FOLLOWING: |
| |
| 106.1 SUBMITTAL DOCUMENTS. |
| CONSTRUCTION DOCUMENTS, SPECIAL INSPECTION AND |
| STRUCTURAL OBSERVATION PROGRAMS, AND OTHER DATA SHALL |
| BE SUBMITTED IN ONE OR MORE SETS WITH EACH APPLICATION |
| FOR A PERMIT. THE CONSTRUCTION DOCUMENTS SHALL BE |
| PREPARED BY A DESIGN PROFESSIONAL WHERE REQUIRED BY THE |
| STATUTES. WHERE SPECIAL CONDITIONS EXIST, THE BUILDING |
| OFFICIAL IS AUTHORIZED TO REQUIRE ADDITIONAL |
| CONSTRUCTION DOCUMENTS TO BE PREPARED BY A DESIGN |
| PROFESSIONAL. |
| |
| |
| BUILDING PLANS EXAMINER: KEN CONRAD |
| PHONE: 561.805.6666 |
| FAX: 561.805.6676 |