Plan Review Details - Permit 07060182
Plan Review Stops For Permit 07060182
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-09 Cont ID  
Sent By jjohnsto Date 2007-11-09 Time 10:53 Rev Time 1.00
Received By jjohnsto Date 2007-11-09 Time 10:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-11 Cont ID  
Sent By jjohnsto Date 2007-09-11 Time 10:38 Rev Time 0.00
Received By jjohnsto Date 2007-09-11 Time 08:00 Sent To  
Notes
2007-09-11 10:37:02CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON,CBO PERMIT NO 07060182
 BUILDING PLAN EXAMINERII PROJECT COOLING TOWER
 REPLACEMENT
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS 515 N. FLAGLER
 DRIVE
  CONTRACTOR AIRSTRON, INC.
  DATE SEPTEMBER 11, 2007
 STRUCTURALPLANREVIEW (2) F.S.
 713.13 NOTICE OF COMMENCEMENT TO BE FILED WITH THE
 CLERK OF COURT
 F.S.713.13 (2) IF THE WORK DESCRIBED
 IN THE NOTICE OF COMMENCEMENT IS NOT COMMENCED WITHIN
 90 DAYS AFTER RECORDING THEREOF, SUCH NOTICE IS NULL
 AND VOID
 RESUBMIT A NEWLY RECORDED NOTICE OF COMMENCEMENT PRIOR
 TO PERMIT ISSUANCE.
  
 (4) SHEETS-1 PROVIDE WIND IMPORTANCE FACTOR ON DATA
  
  
 (5) SHEET S-2 SUBMIT DETAIL OFCOOLING TOWER WITH ALL
 SUPPORTS. IDENTIFY HIGHEST POINT OF
  
 TOWER FROM ROOF SLAB
  
 (6) SHEET S-1 INFORMATION ON ARBAB ENGINEERING, INC.
 SHEET 10 OF 25 DOES NOT MATCH
  
 SHEET S-1DRAWINGS
  
 (7) SHEET S-2 FBC 1905.1.1STRENGTH OF CONCRETE
  STATE DESIGN STRENGTH FOR FORMED CONCRETE COLUMN
  
 (8) SHEET S-1 PROVIDE INFORMATION STATING?
 MODIFICATION ? OF STUB COLUMN
  
 (9) SHEET S-2 SEE PROTECTION OF METALS AS
 SPECIFIED ON SHEET M-2 ?TYPICAL ROOF MOUNTED
  
 PIPING SERVICE SUPPORT INSTALLATION?PROVIDE
 PROTECTION FOR STRUCTURAL SUPPORTS
  
 COMPATIBLE WITH THAT SPECIFIED ON SHEET M-2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-18 Cont ID  
Sent By jwitmer Date 2007-07-18 Time 20:47 Rev Time 0.77
Received By jwitmer Date 2007-07-18 Time 20:47 Sent To PC
Notes
2007-07-18 21:08:27515 N. FLAGLER DR 07060182
  
 BUILDING PLAN REVIEW
 PERMIT: 07060182
 ADD: 515 N FLAGLER DR
 CONT: AIRSTRON, INC
 TEL: (954)923-1654
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3 ) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED. 2004 FBC BUILDING W/ 2006 REVISIONS
  
 4 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING INFORMATION
 RELATED TO WIND SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 S-2 INDICATES THAT THE DESIFN IS TO ASCE 7-02 BUT
 AFTEWARDS COMPLIES TO THE 2001 FBC, PLEASE CORRECT.
 MISSING THE WIND EXOOSURE, AND THE BUILDING CATEGORY,
 HOW HIGH ABOVE GRADE IS THE COOLING TOWER? THERE MAY BE
 ADJUSTMENT FACTORS.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-31 Cont ID  
Sent By dpalmer Date 2007-08-31 Time 16:30 Rev Time 0.00
Received By dpalmer Date 2007-08-31 Time 16:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-21 Cont ID  
Sent By dpalmer Date 2007-06-21 Time 20:00 Rev Time 0.00
Received By dpalmer Date 2007-06-21 Time 20:00 Sent To  
Notes
2007-06-21 20:01:16*** UNSAT ***
  
 1) NOTE:PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE
 THE CODES TO BE STATED ON PLANS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
  
 2) NOTE: PLEASE PROVIDE INFORMATION FOR ANY INCREASE OF
 LOADS FROM EXISTING EQUIPMENT TO NEW EQUIPMENT. THIS
 INFORMATION SHOULD BE STATED ON PLANS.
 220.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE RISER MENTIONS FOR GUTTER TO BE
 REPLACE PER NEC HOWEVER NO SIZE OR DIMENSIONS ARE SHOWN
 AS NEEDED PER NEC 366.
 FBC 106.1.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-05 Cont ID  
Sent By adarroug Date 2007-11-05 Time 12:10 Rev Time 0.00
Received By adarroug Date 2007-11-05 Time 12:10 Sent To  
Notes
2007-11-05 12:11:01WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-07 Cont ID  
Sent By btrobaug Date 2007-08-07 Time 12:50 Rev Time 0.00
Received By btrobaug Date 2007-08-07 Time 12:50 Sent To  
Notes
2007-08-31 10:16:04TO "COMM" BD#1
2007-08-07 12:50:52 
  
 WAITING FOR COM BOARD./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-18 Cont ID  
Sent By jwitmer Date 2007-07-18 Time 20:48 Rev Time 0.00
Received By jwitmer Date 2007-06-08 Time 14:24 Sent To  
Notes
2007-06-21 14:58:47TO "COMM" BD#36
2007-06-08 14:26:28WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-09-07 Cont ID  
Sent By rregueir Date 2007-09-07 Time 18:00 Rev Time 0.00
Received By rregueir Date 2007-09-07 Time 17:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-02 Cont ID  
Sent By rregueir Date 2007-07-02 Time 17:38 Rev Time 0.00
Received By rregueir Date 2007-07-02 Time 17:30 Sent To  
Notes
2007-07-02 17:38:52---------------DENIED-------------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
 NFPA 214-96
  
 1. SCHEMATIC AND INLET DETAILS SECTION IS NOT LEGIBLE.
 PLEASE PROVIDE MARLEY SCHEMATIC THAT IS OF LEGIBLE
 SIZE, QUALITY AND CLARITY. FBC 106.1.3
  
 2. DETAILS FOR PIPE STANDS AND CLAMPS: SUFFICIENT
 INFORMATION IS NOT PROVIDED WITH DETAILS AS SHOWN ON
 PLAN. PROVIDE ALL RELEVANT INFORMATION ON PLANS, SUCH
 AS SIZE, FASTENERS TO BE USED, SPACING OF SUPPORTS,
 ETC. RATHER THAN REFERRING TO A CATALOG WHICH WAS NOT
 PROVIDED WITH THE APPLICATION. FBC 106.1.1, 106.1.3
  
 3. PROVIDE MANUFACTURER'S SUBMITTAL DATA AND
 INSTALLATION INSTRUCTIONS FOR THE COOOLING TOWER. FBC,M
 908.1
  
 4. PROVIDE WIND LOAD CALCULATIONS FOR THE COOLING
 TOWER, SUPPORTS AND ANCHORING SHOWING THE DESIGN TO BE
 ADEQUATE FOR THE WIND ZONE AND EXPOSURE CATEGORY OF THE
 JOB LOCATION PER FBC,M 301.13 AND FBC CH.16.
  
 5. PLEASE REFERENCE CODES IN EFFECT AT TIME OF PERMIT
 APPLICATION: FBC 2004 W/2006 REVISIONS, NFPA 214-96.
  
 NOTE: ADDITIONAL COMMENTS ARE POSSIBLE PENDING THE
 INCLUSION OF INFORMATION WHICH IS MISSING AT THIS
 TIME.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-11-09 Cont ID  
Sent By kstevens Date 2007-11-09 Time 13:43 Rev Time 0.00
Received By kstevens Date 2007-11-09 Time 13:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-21 Cont ID  
Sent By kstevens Date 2007-09-21 Time 06:51 Rev Time 0.00
Received By kstevens Date 2007-09-20 Time 18:56 Sent To  
Notes
2007-09-21 07:03:40DENIED
 REFERENCE: FBC-2004 PLUMBING
 CITY MUNICIPAL CODE
  
 1. NEW P-1 SHEET SHOWS THE COOLING TOWER DRAIN AND
 OVERFLOW DRAINING TO THE SAME SANITARY RISER STACK. THE
 DRAIN SHALL DRAIN TO THE SANITARY, BUT THE OVERFLOW
 SHALL DRAIN TO STORM. IT CAN BE PIPED TO THE NEAREST
 ROOF DRAIN. ARTICLE III SECTION 90-125(5). PLEASE
 CORRECT THE PLUMBING SHEET TO REFLECT THESE
 REQUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-07-14 Cont ID  
Sent By kstevens Date 2007-07-14 Time 08:40 Rev Time 0.00
Received By kstevens Date 2007-07-14 Time 08:40 Sent To  
Notes
2007-07-14 08:40:42PLUMBING PERMIT REQUIRED

Review Stop Z ZONING
Rev No 1 Status N Date 2007-06-26 Cont ID  
Sent By mflis Date 2007-06-26 Time 10:20 Rev Time 0.00
Received By mflis Date 2007-06-26 Time 10:20 Sent To  
Notes
2007-06-26 10:20:54ZONING REVIEW: NOT REQUIRED
  
 * MECH REPLACEMENT ONLY; NO EXTERIOR MODS
  
 MATT FLIS - 822-1445