Plan Review Details - Permit 07060070
Plan Review Stops For Permit 07060070
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-06-29 Cont ID  
Sent By shill Date 2007-06-29 Time 17:52 Rev Time 0.00
Received By shill Date 2007-06-29 Time 17:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By shill Date 2007-06-19 Time 07:35 Rev Time 0.00
Received By shill Date 2007-06-19 Time 07:35 Sent To  
Notes
2007-06-19 07:37:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)SHUTTER MOUNTING CONNECTION TYPE SHOULD REFER TO
 CONNECTIONS C1 THROUGH C5.
  
 2.)SEE OPENING 2 WHERE F/E IS SPECIFIED, 12" SPACING.
 DETAIL E, SHEET 5 OF THE PRODUCT APPROVAL, IS A
 CEILING/INSIDE MOUNT AND USES C4 CONNECTION TYPE.C4
 REQUIRES 11" SPACING.PLEASE CHECK ALL OPENINGS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-21 Cont ID  
Sent By adarroug Date 2007-06-21 Time 10:25 Rev Time 0.00
Received By adarroug Date 2007-06-21 Time 10:25 Sent To B
Notes
2007-06-21 10:25:24TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-19 Cont ID  
Sent By shill Date 2007-06-19 Time 07:37 Rev Time 0.00
Received By shill Date 2007-06-05 Time 16:17 Sent To  
Notes
2007-06-05 16:18:16TO "MISC" BOX#1