Plan Review Details - Permit 07060052
Plan Review Stops For Permit 07060052
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-24 Cont ID  
Sent By mjacobs Date 2007-08-24 Time 17:35 Rev Time 0.00
Received By mjacobs Date 2007-08-24 Time 17:22 Sent To PC
Notes
2007-08-24 17:23:41PROCESSING PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-15 Cont ID  
Sent By mjacobs Date 2007-08-15 Time 13:52 Rev Time 0.00
Received By mjacobs Date 2007-08-15 Time 13:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By mjacobs Date 2007-06-19 Time 12:19 Rev Time 0.00
Received By mjacobs Date 2007-06-19 Time 12:19 Sent To  
Notes
2007-06-19 12:19:35BUILDING PLAN REVIEW
 PERMIT:07060052
 ADD:560 VILLAGE BLVD
 CONT:FISHER CONTRACTING CORP
 TEL: (561)619-4716
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) THIS A LEVEL 2 ALTERATION.FLORIDA EXISTING
 BUILDING CODE. SEC.304.1 : LEVEL 2 ALTERATION INCLUDE
 THE RECONFIGURATION OF SPACE, THE ADDITION OR
 ELIMINIATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION
 OR EXTENSION OF ANY SYSTEM, OR THE INSTALLATION OF ANY
 ADDITIONAL EQUIPMENT.
  
 3)FBC. 11-4.17EXCEPTION: NEW CONSTRUCTION.
 (1)THE STANDARD ACCESSIBLE RESTROOM STALL SHALL
 CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF
 SUCH LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 [SEE FIGURE 30 (A) AND FIGURE 30 (E)] AND TO
 COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH
 LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED
 FIXTURE COUNT FOR THE BUILDING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 17:30 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 17:30 Sent To  
Notes
2007-08-10 17:31:07** REDLINED PLANS.
  
 THE LIGHTING CONTROL DEVICE MUST BE A COMBINATION
 DEVICE SUCH AS AN ULTRASONIC OCCUPANCY SENSOR AS A
 MOTION DEVICE WILL NOT DETECT MOTION IN MULTIPLE STALLS
 WITH PARTITIONS.
 PLEASE SEE THIS IS MORE OF A LIFE SAFETY ISSUE.
 PLEASE VERIFY AND ADJUST DEVICE IN FIELD.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-10 Cont ID  
Sent By dpalmer Date 2007-06-10 Time 12:19 Rev Time 0.00
Received By dpalmer Date 2007-06-10 Time 12:01 Sent To  
Notes
2007-06-10 12:20:06** UNSAT **
  
 1) NOTE: PLEASE SEE THE MINOR MISPRINT FOR CODE ON
 FRONT SHEETS. SHOWS BOTH THE 2005 NFPA_70 AND THE 2002
 NEC.
  
 2) NOTE: PLEASE SEE SHEET A-3 WHICH MENTIONS NEW DEVICE
 FOR AUTO-SHUT OFF PER CHAPTER 13, HOWEVER PLEASE
 ELABORATE ON DEVICE FOR TYPE. IS THIS ULTRASONIC? IF
 ONLY MOTION, THEN WALL/STALL PARTITIONS WILL NOT
 PROVIDE NEEDED COVERAGE.
 PLEASE ALSO STATE MAXIMUM TIME FOR DEVICE.
 13-415.1.ABC.1.1
  
 3) NOTE: PLEASE SEE MISSING EMERGENCY BATTERY BACK UP
 OF SOME TYPE FOR EACH RESTROOM PER LS 101 7.8, 7.9
 WIRED TO LOCAL LIGHTING CIRCUIT PER 700.12F OF THE 2005
 NEC>
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-20 Cont ID  
Sent By mawillia Date 2007-08-20 Time 15:41 Rev Time 0.00
Received By mawillia Date 2007-08-20 Time 14:57 Sent To  
Notes
2007-08-20 15:41:25*****APPROVED*****
  
  
 AS PER THE EXCEPTION LISTED IN FBC 907.9.1.1, THE
 PREVIOUS FIRE PLAN REVIEW COMMENT REGARDING VISIBLE
 ALARM NOTIFICATION APPLIANCES IN THESE RESTROOM DOES
 NOT APPLY.PLAN SHEET A-3 STAMPED, INTIALED, AND
 DATED;READY FOR PERMIT ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-23 Cont ID  
Sent By mawillia Date 2007-06-23 Time 23:04 Rev Time 0.00
Received By mawillia Date 2007-06-23 Time 23:01 Sent To  
Notes
2007-06-23 23:01:47*****UNSAT*****
  
  
 1.AS PER FLORIDA BUILDING CODE 907.9.1.1, VISIBLE
 ALARM NOTIFICATION APPLIANCES SHALL BE PROVIDED IN
 PUBLIC AREAS(I.E. THE RESTROOMS) AND COMMON AREAS.
 SEPARATE PLAN AND PERMIT TO BE PROVIDED FOR FIRE ALARM
 REMODEL.
  
  
 CAPT. MICHAEL A.WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-27 Cont ID  
Sent By adarroug Date 2007-07-27 Time 08:35 Rev Time 0.00
Received By adarroug Date 2007-07-27 Time 08:35 Sent To  
Notes
2007-08-07 17:57:53SENT TO BOB # 14 AS OF 08/07/2007
2007-07-27 08:35:59WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-25 Cont ID  
Sent By jleech Date 2007-06-25 Time 08:53 Rev Time 0.00
Received By jleech Date 2007-06-06 Time 08:35 Sent To  
Notes
2007-06-10 12:09:27TO BOB #6
2007-06-06 08:36:26WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-06-12 Cont ID  
Sent By tgordon Date 2007-06-12 Time 14:23 Rev Time 0.15
Received By tgordon Date 2007-06-12 Time 14:23 Sent To  
Notes
2007-06-12 14:23:59NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-13 Cont ID  
Sent By jleech Date 2007-08-13 Time 07:26 Rev Time 0.00
Received By jleech Date 2007-08-13 Time 07:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-25 Cont ID  
Sent By jleech Date 2007-06-25 Time 08:39 Rev Time 0.00
Received By jleech Date 2007-06-25 Time 08:39 Sent To  
Notes
2007-06-25 08:46:03DENIED;
 1. FBC-2004 EXISTING BUILDING; LEVEL 2,
 SECTION 606 REQUIREDS COMPLIANCE TO FBC-2004
 BUILING CHAPTER 11, ACCESSIBILTY CODE
 SECTION 11-4.17 THRU 11-4.17.6.
 2. SHOW ON PLAN COMPLIANCE WITH FBC-2004
 (MINIMUM NUMBER OF FIXTURES REQUIRED).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695