2007-06-27 11:19:51 | DENIED |
| REFERENCE: |
| ** FBC-2004 FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| PLEASE REFERENCE THE CITY OF WEST PALM BEACH GAS PERMIT |
| APPLICATION REQUIREMENTS ATTACHED TO THE GAS COMMENTS |
| FOR FUTURE PERMITS: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND |
| DOES NOT INDICATE CORRESPONDING LENGTHS TO CUT |
| SECTIONS. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| NOTE: THE SUBMITTED DRAWING DOES NOT INDICATE THE ABOVE |
| GROUND PIPING MATERIAL. PLEASE INDICATE THIS ON THE |
| RESUBMITTAL. PIPING AND SHUT OFF VALVES MUST BE FULL |
| SIZE 1-1/2" TO PROPOSED POOL HEATER. PIPING CAN BE |
| REDUCED AT THE POOL HEATER CONNECTION. PLEASE INDICATE |
| THIS ON THE RESUBMITTED ISOMETRIC. |
| |
| 3. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| NOTE: THE TOTAL LENGTH INDICATED AS 110', IS THIS THE |
| LONGEST LENGTH OF THE SYSTEM INCLUDING THE EXISTING GAS |
| TO THE HOUSE APPLIANCES. PLEASE CLARIFY THIS ON THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |