Plan Review Details - Permit 07060015
Plan Review Stops For Permit 07060015
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-07-20 Cont ID  
Sent By mperson Date 2007-07-20 Time 09:13 Rev Time 0.33
Received By mperson Date 2007-07-20 Time 09:13 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-06-27 Cont ID  
Sent By mperson Date 2007-06-27 Time 11:00 Rev Time 0.45
Received By mperson Date 2007-06-27 Time 11:00 Sent To PC
Notes
2007-06-27 11:19:51DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
 PLEASE REFERENCE THE CITY OF WEST PALM BEACH GAS PERMIT
 APPLICATION REQUIREMENTS ATTACHED TO THE GAS COMMENTS
 FOR FUTURE PERMITS:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND
 DOES NOT INDICATE CORRESPONDING LENGTHS TO CUT
 SECTIONS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THE SUBMITTED DRAWING DOES NOT INDICATE THE ABOVE
 GROUND PIPING MATERIAL. PLEASE INDICATE THIS ON THE
 RESUBMITTAL. PIPING AND SHUT OFF VALVES MUST BE FULL
 SIZE 1-1/2" TO PROPOSED POOL HEATER. PIPING CAN BE
 REDUCED AT THE POOL HEATER CONNECTION. PLEASE INDICATE
 THIS ON THE RESUBMITTED ISOMETRIC.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THE TOTAL LENGTH INDICATED AS 110', IS THIS THE
 LONGEST LENGTH OF THE SYSTEM INCLUDING THE EXISTING GAS
 TO THE HOUSE APPLIANCES. PLEASE CLARIFY THIS ON THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-27 Cont ID  
Sent By adarroug Date 2007-06-27 Time 16:07 Rev Time 0.00
Received By adarroug Date 2007-06-27 Time 16:07 Sent To G
Notes
2007-06-27 16:07:39TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-27 Cont ID  
Sent By mperson Date 2007-06-27 Time 11:20 Rev Time 0.00
Received By mperson Date 2007-06-05 Time 08:46 Sent To  
Notes
2007-06-05 08:46:36TO "G" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved