Plan Review Details - Permit 07051154
Plan Review Stops For Permit 07051154
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-05 Cont ID  
Sent By shill Date 2007-09-05 Time 07:42 Rev Time 0.00
Received By shill Date 2007-09-05 Time 07:42 Sent To  
Notes
2007-09-05 07:53:25****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE PREVIOUS LIST IN REGARDS TO GOVERNING CODE,
 ASCE7 VERSION, AND SEALING 2ND SHEET.THE SAME
 ENGINEERING WAS SUBMITTED.DO YOU NEED ENGINEERING ON
 THIS JOB?
  
 2.)TWO DIFFERENT MIAMIDADE NOAS WERE SUBMITTED.ARE
 YOU INSTALLING BOTH?
  
 3.)PLEASE PROVIDE TWO IDENTICAL COLLATED SETS FOR
 PERMIT ISSUANCE.OLD SHEETS MAY BE SUBMITTED FOR
 REFERENCE; HOWEVER, THEY SHOULD BE SUBMITTED SEPARATELY
 FROM THE SETS FOR PERMIT ISSUANCE OR MARKED VOID.WITH
 THE PACKAGE IN THE CONDITION IT IS IN, I CANNOT
 DETERMINE WHICH PRODUCT(S) YOU ARE USING.WITH A
 CURRENT PRODUCT APPROVAL, ENGINEERING IS NOT REQUIRED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-05 Cont ID  
Sent By shill Date 2007-07-05 Time 14:47 Rev Time 0.00
Received By shill Date 2007-07-05 Time 14:47 Sent To  
Notes
2007-07-05 15:10:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72.IF A FLORIDA STATE PRODUCT APPROVAL OR A
 MIAMIDADE NOA IS NOT AVAILABLE, PLEASE COMPLETE THE
 ATTACHED LOCAL PRODUCT APPROVAL APPLICATION AND SUBMIT
 WITH ALL REQUIRED DOCUMENTS.THE RULE CAN BE VIEWED AT
 WWW.FLORIDABUILDING.ORG.
  
 2.)THE ENGINEERING SUBMITTED REFERS TO ASCE7-98,
 SHOULD BE ASCE7-02, FBC35.
  
 3.)GOVERNING CODE SHOULD INCLUDE 2005 & 2006
 AMENDMENTS.
  
 4.)PLEASE SEAL SHEET 2 OF 2.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 09:47 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 09:47 Sent To M
Notes
2007-08-27 09:47:20TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-25 Cont ID  
Sent By adarroug Date 2007-06-25 Time 12:52 Rev Time 0.00
Received By adarroug Date 2007-06-25 Time 12:52 Sent To M
Notes
2007-06-25 12:52:53TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-11 Cont ID  
Sent By tgordon Date 2007-06-11 Time 16:07 Rev Time 0.00
Received By tgordon Date 2007-06-01 Time 14:42 Sent To  
Notes
2007-06-01 14:42:53TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-09-04 Cont ID  
Sent By tgordon Date 2007-09-04 Time 16:14 Rev Time 0.20
Received By tgordon Date 2007-09-04 Time 16:14 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-25 Cont ID  
Sent By tgordon Date 2007-06-25 Time 16:23 Rev Time 0.20
Received By tgordon Date 2007-06-25 Time 16:23 Sent To B
Notes
2007-06-25 16:24:05SEE BUILDING REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By tgordon Date 2007-06-11 Time 15:53 Rev Time 0.30
Received By tgordon Date 2007-06-11 Time 15:53 Sent To  
Notes
2007-06-11 15:56:40*** DENIED ***
 1) MIAMI DADE NOC HAS EXPIRED 4-14-07 FOR A/C CONDENSER
 STAND. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.