Plan Review Details - Permit 07051146
Plan Review Stops For Permit 07051146 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2007-08-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-08-09 |
Time |
17:35 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-08-09 |
Time |
17:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2007-07-25 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-07-25 |
Time |
13:49 |
Rev Time |
|
Received By |
shill |
Date |
2007-07-24 |
Time |
16:50 |
Sent To |
|
|
Notes |
2007-07-25 13:52:12 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)TWO INSTALLATION METHODS WERE INCLUDED IN THE | | PRODUCT APPROVAL.SELECT WHICH ONE YOU ARE USING. | | NOTE THAT METHOD 1 IS NOT COMPLIANT FOR THE CORNER | | ZONE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-06-14 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-06-14 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-06-14 |
Time |
09:23 |
Sent To |
|
|
Notes |
2007-06-14 14:05:28 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)ZONE 3 HAS A DESIGN PRESSURE REQUIREMENT OF -83.1 | | IF IT IS IN EXPOSURE B; SEE FBC TABLE 1609.6.2.1(2). | | THE ASSEMBLY HAS A LIMITATION OF -75, NO ENHANCED | | FASTENING ALLOWED PER SYSTEM LIMITATION #1. | | | | 2.)PROVIDE A SITE PLAN SHOWING BUILDING LOCATION. | | SEE FBC1609.6.2.1(2), DEFINITION OF EXPOSURE C.IF | | THIS BUILDING IS EXPOSURE C, DESIGN PRESSURE OF -100.56 | | IS REQUIRED FOR ZONE 3. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-05-31 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-05-31 |
Time |
10:18 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-05-31 |
Time |
10:18 |
Sent To |
|
|
Notes |
2007-05-31 10:21:58 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FACFLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)ENHANCED FASTENING FOR THE CORNER AND PERIMETER | | ZONES ARE TO BE PREPARED BY AN ARCHITECT, ENGINEER, OR | | REGISTERED ROOF CONSULTANT. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-07-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-24 |
Time |
13:36 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-24 |
Time |
13:36 |
Sent To |
B |
|
Notes |
2007-07-24 13:36:54 | TO "SHILL" DESK/RESUB |
|
|
|
Account Summary | Usage Policy | Privacy Policy