Plan Review Details - Permit 07050998
Plan Review Stops For Permit 07050998
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-20 Cont ID  
Sent By mjacobs Date 2007-10-20 Time 13:22 Rev Time 0.00
Received By mjacobs Date 2007-10-20 Time 12:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-11 Cont ID  
Sent By mjacobs Date 2007-09-11 Time 08:22 Rev Time 0.00
Received By mjacobs Date 2007-09-10 Time 15:36 Sent To  
Notes
2007-09-11 08:22:47BUILDING PLAN REVIEW
 PERMIT: 07050998
 ADD: 550 S.ROSEMARY AVE
 CONT: RCC ASSOCIATES, INC.
 TEL: (954)429-3700
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)F.A.C. 61G15-23.002ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET, IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. SEE 61G1-16.004 /
 F.S. 471.023 / 481.219.
 **THE NEW ARCHITECTURAL SHEETS ARE MISSING THE SEAL OF
 THE ARCHITECT AND THE DATE WHICH THEY WERE SEALED. ONE
 SET OF NEW PLANS IS MISSING THE ELECTRICAL SHEETS. OUR
 OFFICE SHALL RETAIN ON SET AS PROOF THE PLANS WERE NOT
 SEALED.
  
 3)INDICATE HOW WALL DETAIL # 2 ON SHEET A-4.0 WILL BE
 ATTATCH TO THE EXISTING STRUCTURE?
  
 4)OK
  
 5)OK
  
 6)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
 [email protected].

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-27 Cont ID  
Sent By mjacobs Date 2007-06-27 Time 18:37 Rev Time 0.00
Received By mjacobs Date 2007-06-27 Time 17:10 Sent To  
Notes
2007-06-27 18:37:49BUILDING PLAN REVIEW
 PERMIT:07050998
 ADD:550 S.ROSEMARY AVE
 CONT: RCC ASSOCIATES, INC.
 TEL: (954)429-3700
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)F.A.C. 61G15-23.002ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET, IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. SEE 61G1-16.004 /
 F.S. 471.023 / 481.219.
  
 3)INDICATE HOW WALL DETAIL # 2 ON SHEET A-4.0 WILL BE
 ATTATCH TO THE EXISTING STRUCTURE?
  
 4)FBC SEC 11-7.2(1) IN DEPARTMENT STORES AND
 MISSCELLANEAUS RETAIL STORES WHERE COUNTERS HAVE CASH
 REGISTERS AND ARE PROVIDED FOR SALES OR DISTRIBUTION OF
 GOODS OR SERVICES TO THE PUBLIC, AT LEAST ONE OF EACH
 TYPE SHALL HAVE A PORTION OF THE COUNTER WHICH IS AT
 LEAST 36 INCHES IN LENGTH WITH A MAXIMUM HEIGHT OF 36
 INCHES ABOVE THE FINISH FLOOR. SHOW COMPLIANCE WITH
 DETAIL ELEVATION DRAWINGS.
  
 5)FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OFTHIS
 CODE.
  
 6)ENERGY CALCULATIONS NEED TO BE SIGNED BY
 OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-11-09 Cont ID  
Sent By dpalmer Date 2007-11-09 Time 09:03 Rev Time 0.00
Received By dpalmer Date 2007-11-09 Time 08:57 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-11-03 Cont ID  
Sent By dpalmer Date 2007-11-03 Time 11:50 Rev Time 0.00
Received By dpalmer Date 2007-11-03 Time 11:08 Sent To PC
Notes
2007-11-03 11:54:28** TEMP FAILED STATUS**
  
 1) NOTE: NEW ELECTRICAL PLANS IN BOTH SETS NEED TO HAVE
 THE CITY PLACE STAMP BY CITY PLACE MANAGMENT.
 THE SECOND SET OF PLANS CONTAINS NEW MECHANICAL SHEETS
 WHICH ALSO REQUIRE CP STAMPS. MECHANICAL REVIEWER WILL
 STAMP SECOND SET ONCE CP STAMPS ARE PRESENT BEFORE
 ISSUANCE.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-11-01 Cont ID  
Sent By dpalmer Date 2007-11-01 Time 10:02 Rev Time 0.00
Received By dpalmer Date 2007-11-01 Time 09:00 Sent To PC
Notes
2007-11-01 10:02:23 
 ** DENIED 4TH REVIEW**
  
  
 1) NOTE: THE NEW SHEET E1.1 IS SIGNED WITH A SIGNATURE
 WHICH IS DIFFERENT THAN OTHER ELECTRICAL SHEETS
 SIGNED.
 PLEASE SEE FS 471.025 AS ONLY THE SEAL HOLDER MAY SIGN,
 DATE AND SEAL PLANS.
 SETS NEED NEW ELECTRICAL SHEETS IN BOTH SETS SO THAT
 THE SIGNATURE MATCH AND COORDINATE. ALSO NEED A
 SIGNATURE VERIFICATION LETTER AS THIS OFFICE HAS
 RECEIVED TWO SEPARATE SIGNATURES AND IS NOT CLEAR WHICH
 ONE IS THE ENGINEER OF RECORD. THE LETTER IS REQUIRED
 TO BE ORIGINAL, SIGNED DATED AND SEALED ALONG WITH A
 NOTARY.
  
 PLACED CALL TO THE ENGINEER'S OFFICE AND NEW SHEETS
 WILL BE SENT.
 PLANS ARE ON HOLD UNDER "R", WAITING FOR NEW SHEETS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-22 Cont ID  
Sent By dpalmer Date 2007-10-22 Time 08:46 Rev Time 0.00
Received By dpalmer Date 2007-10-21 Time 16:22 Sent To FIRE
Notes
2007-10-22 08:46:16*** DENIED 3RD REVIEW ***
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED WHICH ARE RUN THROUGH THE FLA/COM PROJECT MAY
 NOT BE ALTERED BY TYPING IN INFORMATION ETC BY HAND.
 PLEASE ALSO SEE THAT THE DESIGN WATTAGE IS BEING SHOWN
 MUCH HIGHER THAN THE EFFECTIVE OR ALLOWANCE WATTAGE.
 HOW IS THIS POSSIBLE?
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS, THESE
 MAY BE ON THE PLANS SET UP IN SOME SORT OF TABLE FORM.
 RESPONSE LETTER MENTIONS THIS WAS DONE PER 13-415.2.B,
 PLEASE SHOW THIS ON PLANS.
  
 ** PLEASE CALL TO GO OVER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-22 08:06:172007-10-22 08:06:17
  
 IN PROGRESS

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-07 Cont ID  
Sent By dpalmer Date 2007-09-07 Time 18:51 Rev Time 0.00
Received By dpalmer Date 2007-09-07 Time 17:36 Sent To  
Notes
2007-09-07 18:52:12** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
  
 1) NOTE:THIS IS THE SAME COMMENT AS PREVIOUS REVIEW.
 THE RESPONSE MENTIONS THIS WAS UPDATED ON SHEET A-0.1
 HOWEVER IT WAS ASKED FOR THE RELEVANT CODES TO BE
 PLACED ON ELECTRICAL SHEETS HOWEVER THIS WAS NOT DONE.
 PLANS ONLY STATE THE *LATEST ADOPTED CODES*.
 AS PLANS ARE COMING BACK FOR OTHER COMMENTS AND
 CORRECTION PLEASE INCLUDE ON ELECTRICAL PLANS.
 ** PREVIOUS REVIEW NOTE**
 PLEASE BE SURE TO STATE ALL THE RELEVANT CODES AS
 ADOPTED BY THE STATE OF FLORIDA AS OF DECEMBER 8TH,
 2006.
 PLEASE SEE THE FOLLOWING AT A MINIMUM MUST BE STATED.
 SOME CODES STATED NEVER EXISTED.(2003 NEC)
  
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101 (DONE ON COVER ALTHOUGH REQUIRED ON
 ELECTRICAL SHEETS)
 2002 NFPA-72
  
 ** PLEASE BE AWARE OF ANY POSSIBLE CODES FROM OTHER
 TRADES.
  
 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR THE ARCHITECTURAL FIRM ON E-SHEETS. AS THESE SHEET
 ARE BEING CORRECTED FOR OTHER COMMENTS, PLEASE SEE THE
 PRINTED FIRM CERTIFICATE OF AUTHORIZATION NUMBER IS THE
 ONLY ITEM THAT IS MISSING. 61G1-16.004 FOR ARCHITECT
 FIRM.
  
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT THIS COMMENT IS MADE BY ANY OTHER TRADE
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE COMPLIANCE WITH CHAPTER 13 OF THE
 FBC HAS NOT BEEN MET.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED ONCE
 AGAIN DO NOT CORRELATE WITH PLANS OR THE FIXTURE LEGEND
 AS SUBMITTED. PLEASE SEE THERE ARE IN FACT SEVERAL HAND
 PRINTED ITEMS ON THE INPUT DATA REPORT WHICH MUST BE
 PLACED INTO THE IDR WHEN RUNNING REPORT.
 PLEASE CORRELATE.
 PLEASE SEE THE LIGHTING FIXTURE TYPES DO NOT MATCH.
 PLEASE SEE THE WATTAGE ON FIXTURES DOES NOT MATCH.
 PLEASE SEE THE NUMBER OF EACH FIXTURE ALSO DOES MATCH.
 PLEASE SEE 13-415.2.ABC.1.2 FOR REQUIRED TRACK
 LIGHTING CALCULATIONS AND FIGURES.
 ** PLEASE SEE THE FBC 13-415.1.B.1.1, 13-415.2 AND
 TABLES FOR METHOD *B*.
 PLEASE SEE THE REQUIRED LIGHTING CONTROLS ARE NOT
 SHOWN ON PLANS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2.
 PLEASE INDICATE TIME FOR SCHEDULING IF A LIGHTING
 CONTROL SYSTEM IS INSTALLED ALONG WITH ALL OVER RIDE
 DEVICE TIMES.
 PLEASE PROVIDE MORE INFORMATION/DETAIL FOR THE TIME
 CLOCK BEING NOTED.
 AT THIS TIME.
  
 4) NOTE: PLEASE SEE NOTE #10 ON SHEET E-2.0 MENTIONS
 THE FIRE ALARM PANEL IS TO BE CIRCUITED TO PANEL *A*
 41, YET THIS SPACE IS BEING SHOWN AS SPARE?
 PLEASE COORDINATE.
 FBC 106.3.5.1.2, 106.1.2
 NEC 408.4.
  
 5) NOTE: PLEASE SEE 220.53 FOR MINIMUM LOADS TO BE
 FIGURED FOR SHOW WINDOW RECEPTACLES. PLEASE ADJUST
 SERVICE CALCULATIONS.
 RESPONSE MENTIONS TO REFER TO REVISED CALCULATIONS
 HOWEVER HOW THE SHOW WINDOW LOAD WAS DERIVED OR SHOWN
 IN THESE CALCULATIONS IS NOT CLEAR.
  
 6) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
 TWO SETS OF ELECTRICAL PLANS AND ENERGY CALCULATIONS
 ARE BEING RETAINED BY THIS OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** AS STATED IN THE PREVIOUS REVIEW,:
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By dpalmer Date 2007-06-20 Time 21:03 Rev Time 0.00
Received By dpalmer Date 2007-06-20 Time 20:31 Sent To  
Notes
2007-06-20 21:03:50*** UNSAT***
  
  
 1) NOTE: PLEASE BE SURE TO STATE ALL THE RELEVANT CODES
 AS ADOPTED BY THE STATE OF FLORIDA AS OF DECEMBER 8TH,
 2006.
 PLEASE SEE THE FOLLOWING AT A MINIMUM MUST BE STATED.
 SOME CODES STATED NEVER EXISTED.(2003 NEC)
  
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101 (DONE ON COVER ALTHOUGH REQUIRED ON
 ELECTRICAL SHEETS)
 2002 NFPA-72
  
 ** PLEASE BE AWARE OF ANY POSSIBLE CODES FROM OTHER
 TRADES.
  
 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR BOTH THE ARCHITECT, FIRM AS WELL AS THE ENGINEER
 AND ENGINEERING FIRM.
 PLEASE SEE MISSING THE PRINTED NAMES FOR DESIGNERS.
 PLEASE SEE THE PRINTED LICENSE NUMBERS FOR DESIGNERS.
 PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBERS FOR BOTH FIRMS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 FOR
 ENGINEERS AND 61G1-16.004 FOR ARCHITECT FIRM.. PLEASE
 SEE FLORIDA STATUTES 471.023 FOR ENGINEERS AND 481.219
 FOR ARCHITECT FIRM.
  
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT THIS COMMENT IS MADE BY ANY OTHER TRADE
 REVIEWER(S).
  
 2) NOTE: PLEASE SEE COMPLIANCE WITH CHAPTER 13 OF THE
 FBC HAS NOT BEEN MET.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED ARE
 NOTE SEALED BY THE DESIGNER OF RECORD. PLEASE BE SURE
 TO SIGN, DATE AND SEAL CALCULATIONS.
 13-103.1.1.1
 ** PLEASE ALSO SEE THE OWNER AGENT IS NOT SIGNED ON
 SECOND SHEET AS REQUIRED.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO NOT
 CORRELATE WITH PLANS.
 PLEASE SEE THE LIGHTING FIXTURE TYPES DO NOT MATCH.
 PLEASE SEE THE WATTAGE ON FIXTURES DOES NOT MATCH
 PLEASE SEE THE NUMBER OF EACH FIXTURE ALSO DOES MATCH.
 PLEASE SEE 13-415.2.ABC.1.2 FOR REQUIRED TRACK LIGHTING
 CALCULATIONS AND FIGURES.
 ** PLEASE SEE THE FBC 13-415.1.AB.1.1, 13-415.2 AND
 TABLES FOR METHOD *B*. PLEASE VERIFY METHOD *B*. PLEASE
 SEE THE REQUIRED LIGHTING CONTROLS ARE NOT SHOWN ON
 PLANS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE INDICATE TIME FOR SCHEDULING IF A LIGHTING
 CONTROL SYSTEM IS INSTALLED ALONG WITH ALL OVER RIDE
 DEVICE TIMES.
 PLEASE SEE OF OCCUPANCY SENSOR TYPE DEVICES ARE USED,
 PLEASE LIST THE MAXIMUM TIMES PER SECTIONS ABOVE. IF
 TIMER TYPE DEVICES ARE USED PLEASE LIST MAXIMUM
 TIMES.(4HRS).
 ** AS DESIGNS WERE NOT SHOWN ON PLANS FOR REVIEW A
 COMPLETE REVIEW OF THESE ITEMS CAN NOT BE DONE AT THIS
 TIME.
  
 3) NOTE: PLEASE SEE ELECTRICAL EQUIPMENT IS BEING NOTED
 IN STORAGE ROOM WHICH IS NOT PERMITTED. PLEASE SEE
 110.26, 408.7, 240.24 ETC.
 THIS MAY NOT BE STORAGE ROOM.
  
 4) NOTE: PLEASE SEE RISER SHOWS A NEW PANEL ON THE
 SECONDARY SIDE OF THE TRANSFORMER HOWEVER THE NOTE ON
 THE RISER MENTIONS EXISTING CONDUCTORS TO REMAIN. AS
 THE EXISTING PANEL, MAIN CIRCUIT BREAKER SIZE AND
 CONDUCTORS WAS NOT GIVEN IT CAN NOT BE DETERMINED IF
 THE EXISTING CONDUCTORS ARE OF SUFFICIENT SIZE TO
 TERMINATE IN THE 100AMP BREAKER AS SHOWN ON NEW PANEL.
 PLEASE SEE 240.21, 310.16, 240.4.
 PLEASE PROVIDE MORE INFORMATION.
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SEE 220.53 FOR MINIMUM LOADS TO BE
 FIGURED FOR SHOW WINDOW RECEPTACLES. PLEASE ADJUST
 SERVICE CALCULATIONS.
  
 6) NOTE: PLEASE SEE THE EMERGENCY AND EXIT LIGHTS SHALL
 BE CIRCUITED TO THE LOCAL BRANCH CIRCUIT IN THAT AREA.
 PLEASE SEE 700.12F.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-10-23 Cont ID  
Sent By mawillia Date 2007-10-23 Time 14:57 Rev Time 0.00
Received By mawillia Date 2007-10-23 Time 14:33 Sent To  
Notes
2007-10-23 14:46:06*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED: PLAN SHEETS A-1.1 AND E-1.1 WERE
 STAMPED, INITIALED, AND DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-20 Cont ID  
Sent By mawillia Date 2007-09-20 Time 11:40 Rev Time 0.00
Received By mawillia Date 2007-09-20 Time 10:58 Sent To  
Notes
2007-09-20 11:00:02*****UNSAT*****
  
 *THE FOLLOWING COMMENT FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
  
 4.DECLARE INTERIOR WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.BASED UPON
 YOUR RESPONSE LETTER,ADD COMMENT "ALL FINISHES ARE
 CLASS A." TO SHEET A-1.0
  
 *NEW COMMENT
  
 A. THERE WAS ONLY ONE PLAN SET THAT WAS SUBMITTED ALONG
 WITH THE OLD VOIDED SET.AT LEAST TWO, NO MORE THAN
 THREE PLAN SETS NEEDED
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-10 Cont ID  
Sent By mawillia Date 2007-07-10 Time 17:36 Rev Time 0.00
Received By mawillia Date 2007-07-10 Time 16:40 Sent To  
Notes
2007-07-10 17:31:38*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS, INCLUDING THE TENANT SPACE
 NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 2.NFPA 101, THE LIFE SAFETY CODE, 2003 EDITION SHALL
 BE REFERENCED.AMEND APPLICABLE CODE ON SHEET A-01.
  
 3.CONSTRUCTION/DEMOLITION OPERATIONS AND/OR THE
 PLACEMENT OF THE DUMPSTER SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS RESPONSE TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES).
  
 4.DECLARE INTERIOR WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 5.INDICATE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-07 Cont ID  
Sent By adarroug Date 2007-11-07 Time 13:01 Rev Time 0.00
Received By adarroug Date 2007-11-07 Time 13:01 Sent To  
Notes
2007-11-07 13:02:07TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-30 Cont ID  
Sent By adarroug Date 2007-10-30 Time 11:50 Rev Time 0.00
Received By adarroug Date 2007-10-30 Time 11:50 Sent To  
Notes
2007-10-30 11:52:53TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-01 Cont ID  
Sent By adarroug Date 2007-10-01 Time 12:01 Rev Time 0.00
Received By adarroug Date 2007-10-01 Time 12:01 Sent To  
Notes
2007-10-01 12:01:46WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-09 Cont ID  
Sent By dpalmer Date 2007-08-09 Time 11:24 Rev Time 0.00
Received By dpalmer Date 2007-08-09 Time 11:24 Sent To  
Notes
2007-09-07 16:28:00TO "COMM" BD#42
2007-08-09 11:26:43WAITING FOR COMM BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-10 Cont ID  
Sent By mawillia Date 2007-07-10 Time 16:40 Rev Time 0.00
Received By mawillia Date 2007-05-30 Time 10:25 Sent To  
Notes
2007-06-15 16:12:51TO "COMM"BD#22
2007-05-30 10:25:52WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-09-10 Cont ID  
Sent By rregueir Date 2007-09-10 Time 08:02 Rev Time 0.00
Received By rregueir Date 2007-09-10 Time 08:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-23 Cont ID  
Sent By rregueir Date 2007-06-23 Time 15:30 Rev Time 0.00
Received By rregueir Date 2007-06-23 Time 15:23 Sent To  
Notes
2007-06-23 15:30:42--------------------DENIED---------------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
  
 1. PG A-0.1: PLEASE REFERENCE FLORIDA BUILDING CODE,
 MECHANICAL 2004 ON PLANS.
  
 2. THE ENGINEER'S PRINTED NAME AND LICENCE NUMBER,
 ALONG WITH ENGINEERING FIRM'S CERTIFICATE OF
 AUTHORIZATION NUMBER ARE REQUIRED ON EACH PAGE FOR
 WHICH THE ENGINEER IS RESPONSIBLE PER FAC RULE
 61G15-23.002
  
 3. AIR BALANCE AS SHOWN ON PLAN IS AT -20 CFM.
 MECHANICAL SYSTEMS SHALL BE DESIGNED TO ASSURE THAT
 BUILDINGS ARE PRESSURIZED WITH RESPECT TO THE OUTDOORS
 PER FBC 13-409.1.ABC.2
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status N Date 2007-09-10 Cont ID  
Sent By kstevens Date 2007-09-10 Time 10:59 Rev Time 0.00
Received By kstevens Date 2007-09-10 Time 10:59 Sent To  
Notes
2007-09-10 11:00:19STILL NO PLUMBING WORK INDICATED/SHOWN

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-07-09 Cont ID  
Sent By kstevens Date 2007-07-09 Time 11:13 Rev Time 0.00
Received By kstevens Date 2007-07-09 Time 11:13 Sent To  
Notes
2007-07-09 11:13:37NO PLUMBING WORK INDICATED