Plan Review Stops For Permit 07050998 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-10-20 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-10-20 |
Time |
13:22 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-10-20 |
Time |
12:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-09-11 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-09-11 |
Time |
08:22 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-09-10 |
Time |
15:36 |
Sent To |
|
|
Notes |
2007-09-11 08:22:47 | BUILDING PLAN REVIEW | | PERMIT: 07050998 | | ADD: 550 S.ROSEMARY AVE | | CONT: RCC ASSOCIATES, INC. | | TEL: (954)429-3700 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 2ND | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 2)F.A.C. 61G15-23.002ENGINEERS SHALL LEGIBLY | | INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON | | EACH SHEET, IF PRACTICING THROUGH A DULY AUTHORIZED | | ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE | | THEIR NAME AND LICENSE NUMBER, AS WELL AS, THE NAME, | | ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | ENGINEERING BUSINESS ON EACH SHEET. SEE 61G1-16.004 / | | F.S. 471.023 / 481.219. | | **THE NEW ARCHITECTURAL SHEETS ARE MISSING THE SEAL OF | | THE ARCHITECT AND THE DATE WHICH THEY WERE SEALED. ONE | | SET OF NEW PLANS IS MISSING THE ELECTRICAL SHEETS. OUR | | OFFICE SHALL RETAIN ON SET AS PROOF THE PLANS WERE NOT | | SEALED. | | | | 3)INDICATE HOW WALL DETAIL # 2 ON SHEET A-4.0 WILL BE | | ATTATCH TO THE EXISTING STRUCTURE? | | | | 4)OK | | | | 5)OK | | | | 6)OK | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | [email protected]. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-06-27 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-06-27 |
Time |
18:37 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-06-27 |
Time |
17:10 |
Sent To |
|
|
Notes |
2007-06-27 18:37:49 | BUILDING PLAN REVIEW | | PERMIT:07050998 | | ADD:550 S.ROSEMARY AVE | | CONT: RCC ASSOCIATES, INC. | | TEL: (954)429-3700 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 1ST | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 2)F.A.C. 61G15-23.002ENGINEERS SHALL LEGIBLY | | INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON | | EACH SHEET, IF PRACTICING THROUGH A DULY AUTHORIZED | | ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE | | THEIR NAME AND LICENSE NUMBER, AS WELL AS, THE NAME, | | ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | ENGINEERING BUSINESS ON EACH SHEET. SEE 61G1-16.004 / | | F.S. 471.023 / 481.219. | | | | 3)INDICATE HOW WALL DETAIL # 2 ON SHEET A-4.0 WILL BE | | ATTATCH TO THE EXISTING STRUCTURE? | | | | 4)FBC SEC 11-7.2(1) IN DEPARTMENT STORES AND | | MISSCELLANEAUS RETAIL STORES WHERE COUNTERS HAVE CASH | | REGISTERS AND ARE PROVIDED FOR SALES OR DISTRIBUTION OF | | GOODS OR SERVICES TO THE PUBLIC, AT LEAST ONE OF EACH | | TYPE SHALL HAVE A PORTION OF THE COUNTER WHICH IS AT | | LEAST 36 INCHES IN LENGTH WITH A MAXIMUM HEIGHT OF 36 | | INCHES ABOVE THE FINISH FLOOR. SHOW COMPLIANCE WITH | | DETAIL ELEVATION DRAWINGS. | | | | 5)FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN | | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF | | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OFTHIS | | CODE. | | | | 6)ENERGY CALCULATIONS NEED TO BE SIGNED BY | | OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
P |
Date |
2007-11-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-11-09 |
Time |
09:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-11-09 |
Time |
08:57 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
F |
Date |
2007-11-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-11-03 |
Time |
11:50 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-11-03 |
Time |
11:08 |
Sent To |
PC |
|
Notes |
2007-11-03 11:54:28 | ** TEMP FAILED STATUS** | | | | 1) NOTE: NEW ELECTRICAL PLANS IN BOTH SETS NEED TO HAVE | | THE CITY PLACE STAMP BY CITY PLACE MANAGMENT. | | THE SECOND SET OF PLANS CONTAINS NEW MECHANICAL SHEETS | | WHICH ALSO REQUIRE CP STAMPS. MECHANICAL REVIEWER WILL | | STAMP SECOND SET ONCE CP STAMPS ARE PRESENT BEFORE | | ISSUANCE. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2007-11-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-11-01 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-11-01 |
Time |
09:00 |
Sent To |
PC |
|
Notes |
2007-11-01 10:02:23 | | | ** DENIED 4TH REVIEW** | | | | | | 1) NOTE: THE NEW SHEET E1.1 IS SIGNED WITH A SIGNATURE | | WHICH IS DIFFERENT THAN OTHER ELECTRICAL SHEETS | | SIGNED. | | PLEASE SEE FS 471.025 AS ONLY THE SEAL HOLDER MAY SIGN, | | DATE AND SEAL PLANS. | | SETS NEED NEW ELECTRICAL SHEETS IN BOTH SETS SO THAT | | THE SIGNATURE MATCH AND COORDINATE. ALSO NEED A | | SIGNATURE VERIFICATION LETTER AS THIS OFFICE HAS | | RECEIVED TWO SEPARATE SIGNATURES AND IS NOT CLEAR WHICH | | ONE IS THE ENGINEER OF RECORD. THE LETTER IS REQUIRED | | TO BE ORIGINAL, SIGNED DATED AND SEALED ALONG WITH A | | NOTARY. | | | | PLACED CALL TO THE ENGINEER'S OFFICE AND NEW SHEETS | | WILL BE SENT. | | PLANS ARE ON HOLD UNDER "R", WAITING FOR NEW SHEETS. | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-10-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-10-22 |
Time |
08:46 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-10-21 |
Time |
16:22 |
Sent To |
FIRE |
|
Notes |
2007-10-22 08:46:16 | *** DENIED 3RD REVIEW *** | | | | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL | | IN NEED OF ADDRESSING. | | | | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS | | SUBMITTED WHICH ARE RUN THROUGH THE FLA/COM PROJECT MAY | | NOT BE ALTERED BY TYPING IN INFORMATION ETC BY HAND. | | PLEASE ALSO SEE THAT THE DESIGN WATTAGE IS BEING SHOWN | | MUCH HIGHER THAN THE EFFECTIVE OR ALLOWANCE WATTAGE. | | HOW IS THIS POSSIBLE? | | PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS, THESE | | MAY BE ON THE PLANS SET UP IN SOME SORT OF TABLE FORM. | | RESPONSE LETTER MENTIONS THIS WAS DONE PER 13-415.2.B, | | PLEASE SHOW THIS ON PLANS. | | | | ** PLEASE CALL TO GO OVER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-10-22 08:06:17 | 2007-10-22 08:06:17 | | | | IN PROGRESS |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-09-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-09-07 |
Time |
18:51 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-09-07 |
Time |
17:36 |
Sent To |
|
|
Notes |
2007-09-07 18:52:12 | ** DENIED 2ND REVIEW ** | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | IN NEED OF ADDRESSING. | | | | | | 1) NOTE:THIS IS THE SAME COMMENT AS PREVIOUS REVIEW. | | THE RESPONSE MENTIONS THIS WAS UPDATED ON SHEET A-0.1 | | HOWEVER IT WAS ASKED FOR THE RELEVANT CODES TO BE | | PLACED ON ELECTRICAL SHEETS HOWEVER THIS WAS NOT DONE. | | PLANS ONLY STATE THE *LATEST ADOPTED CODES*. | | AS PLANS ARE COMING BACK FOR OTHER COMMENTS AND | | CORRECTION PLEASE INCLUDE ON ELECTRICAL PLANS. | | ** PREVIOUS REVIEW NOTE** | | PLEASE BE SURE TO STATE ALL THE RELEVANT CODES AS | | ADOPTED BY THE STATE OF FLORIDA AS OF DECEMBER 8TH, | | 2006. | | PLEASE SEE THE FOLLOWING AT A MINIMUM MUST BE STATED. | | SOME CODES STATED NEVER EXISTED.(2003 NEC) | | | | 2004 FBC W/ 2006 REVISIONS. | | 2005 NFPA-70 | | 2003 NFPA-101 (DONE ON COVER ALTHOUGH REQUIRED ON | | ELECTRICAL SHEETS) | | 2002 NFPA-72 | | | | ** PLEASE BE AWARE OF ANY POSSIBLE CODES FROM OTHER | | TRADES. | | | | 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS | | FOR THE ARCHITECTURAL FIRM ON E-SHEETS. AS THESE SHEET | | ARE BEING CORRECTED FOR OTHER COMMENTS, PLEASE SEE THE | | PRINTED FIRM CERTIFICATE OF AUTHORIZATION NUMBER IS THE | | ONLY ITEM THAT IS MISSING. 61G1-16.004 FOR ARCHITECT | | FIRM. | | | | ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES | | WHETHER OR NOT THIS COMMENT IS MADE BY ANY OTHER TRADE | | REVIEWER(S). | | | | 3) NOTE: PLEASE SEE COMPLIANCE WITH CHAPTER 13 OF THE | | FBC HAS NOT BEEN MET. | | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED ONCE | | AGAIN DO NOT CORRELATE WITH PLANS OR THE FIXTURE LEGEND | | AS SUBMITTED. PLEASE SEE THERE ARE IN FACT SEVERAL HAND | | PRINTED ITEMS ON THE INPUT DATA REPORT WHICH MUST BE | | PLACED INTO THE IDR WHEN RUNNING REPORT. | | PLEASE CORRELATE. | | PLEASE SEE THE LIGHTING FIXTURE TYPES DO NOT MATCH. | | PLEASE SEE THE WATTAGE ON FIXTURES DOES NOT MATCH. | | PLEASE SEE THE NUMBER OF EACH FIXTURE ALSO DOES MATCH. | | PLEASE SEE 13-415.2.ABC.1.2 FOR REQUIRED TRACK | | LIGHTING CALCULATIONS AND FIGURES. | | ** PLEASE SEE THE FBC 13-415.1.B.1.1, 13-415.2 AND | | TABLES FOR METHOD *B*. | | PLEASE SEE THE REQUIRED LIGHTING CONTROLS ARE NOT | | SHOWN ON PLANS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2. | | PLEASE INDICATE TIME FOR SCHEDULING IF A LIGHTING | | CONTROL SYSTEM IS INSTALLED ALONG WITH ALL OVER RIDE | | DEVICE TIMES. | | PLEASE PROVIDE MORE INFORMATION/DETAIL FOR THE TIME | | CLOCK BEING NOTED. | | AT THIS TIME. | | | | 4) NOTE: PLEASE SEE NOTE #10 ON SHEET E-2.0 MENTIONS | | THE FIRE ALARM PANEL IS TO BE CIRCUITED TO PANEL *A* | | 41, YET THIS SPACE IS BEING SHOWN AS SPARE? | | PLEASE COORDINATE. | | FBC 106.3.5.1.2, 106.1.2 | | NEC 408.4. | | | | 5) NOTE: PLEASE SEE 220.53 FOR MINIMUM LOADS TO BE | | FIGURED FOR SHOW WINDOW RECEPTACLES. PLEASE ADJUST | | SERVICE CALCULATIONS. | | RESPONSE MENTIONS TO REFER TO REVISED CALCULATIONS | | HOWEVER HOW THE SHOW WINDOW LOAD WAS DERIVED OR SHOWN | | IN THESE CALCULATIONS IS NOT CLEAR. | | | | 6) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A | | NOTICE GIVEN AT THIS TIME. | | TWO SETS OF ELECTRICAL PLANS AND ENERGY CALCULATIONS | | ARE BEING RETAINED BY THIS OFFICE. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** AS STATED IN THE PREVIOUS REVIEW,: | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-06-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-06-20 |
Time |
21:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-06-20 |
Time |
20:31 |
Sent To |
|
|
Notes |
2007-06-20 21:03:50 | *** UNSAT*** | | | | | | 1) NOTE: PLEASE BE SURE TO STATE ALL THE RELEVANT CODES | | AS ADOPTED BY THE STATE OF FLORIDA AS OF DECEMBER 8TH, | | 2006. | | PLEASE SEE THE FOLLOWING AT A MINIMUM MUST BE STATED. | | SOME CODES STATED NEVER EXISTED.(2003 NEC) | | | | 2004 FBC W/ 2006 REVISIONS. | | 2005 NFPA-70 | | 2003 NFPA-101 (DONE ON COVER ALTHOUGH REQUIRED ON | | ELECTRICAL SHEETS) | | 2002 NFPA-72 | | | | ** PLEASE BE AWARE OF ANY POSSIBLE CODES FROM OTHER | | TRADES. | | | | 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS | | FOR BOTH THE ARCHITECT, FIRM AS WELL AS THE ENGINEER | | AND ENGINEERING FIRM. | | PLEASE SEE MISSING THE PRINTED NAMES FOR DESIGNERS. | | PLEASE SEE THE PRINTED LICENSE NUMBERS FOR DESIGNERS. | | PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION | | NUMBERS FOR BOTH FIRMS. | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 FOR | | ENGINEERS AND 61G1-16.004 FOR ARCHITECT FIRM.. PLEASE | | SEE FLORIDA STATUTES 471.023 FOR ENGINEERS AND 481.219 | | FOR ARCHITECT FIRM. | | | | ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES | | WHETHER OR NOT THIS COMMENT IS MADE BY ANY OTHER TRADE | | REVIEWER(S). | | | | 2) NOTE: PLEASE SEE COMPLIANCE WITH CHAPTER 13 OF THE | | FBC HAS NOT BEEN MET. | | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED ARE | | NOTE SEALED BY THE DESIGNER OF RECORD. PLEASE BE SURE | | TO SIGN, DATE AND SEAL CALCULATIONS. | | 13-103.1.1.1 | | ** PLEASE ALSO SEE THE OWNER AGENT IS NOT SIGNED ON | | SECOND SHEET AS REQUIRED. | | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO NOT | | CORRELATE WITH PLANS. | | PLEASE SEE THE LIGHTING FIXTURE TYPES DO NOT MATCH. | | PLEASE SEE THE WATTAGE ON FIXTURES DOES NOT MATCH | | PLEASE SEE THE NUMBER OF EACH FIXTURE ALSO DOES MATCH. | | PLEASE SEE 13-415.2.ABC.1.2 FOR REQUIRED TRACK LIGHTING | | CALCULATIONS AND FIGURES. | | ** PLEASE SEE THE FBC 13-415.1.AB.1.1, 13-415.2 AND | | TABLES FOR METHOD *B*. PLEASE VERIFY METHOD *B*. PLEASE | | SEE THE REQUIRED LIGHTING CONTROLS ARE NOT SHOWN ON | | PLANS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2 AND .1.3. | | PLEASE INDICATE TIME FOR SCHEDULING IF A LIGHTING | | CONTROL SYSTEM IS INSTALLED ALONG WITH ALL OVER RIDE | | DEVICE TIMES. | | PLEASE SEE OF OCCUPANCY SENSOR TYPE DEVICES ARE USED, | | PLEASE LIST THE MAXIMUM TIMES PER SECTIONS ABOVE. IF | | TIMER TYPE DEVICES ARE USED PLEASE LIST MAXIMUM | | TIMES.(4HRS). | | ** AS DESIGNS WERE NOT SHOWN ON PLANS FOR REVIEW A | | COMPLETE REVIEW OF THESE ITEMS CAN NOT BE DONE AT THIS | | TIME. | | | | 3) NOTE: PLEASE SEE ELECTRICAL EQUIPMENT IS BEING NOTED | | IN STORAGE ROOM WHICH IS NOT PERMITTED. PLEASE SEE | | 110.26, 408.7, 240.24 ETC. | | THIS MAY NOT BE STORAGE ROOM. | | | | 4) NOTE: PLEASE SEE RISER SHOWS A NEW PANEL ON THE | | SECONDARY SIDE OF THE TRANSFORMER HOWEVER THE NOTE ON | | THE RISER MENTIONS EXISTING CONDUCTORS TO REMAIN. AS | | THE EXISTING PANEL, MAIN CIRCUIT BREAKER SIZE AND | | CONDUCTORS WAS NOT GIVEN IT CAN NOT BE DETERMINED IF | | THE EXISTING CONDUCTORS ARE OF SUFFICIENT SIZE TO | | TERMINATE IN THE 100AMP BREAKER AS SHOWN ON NEW PANEL. | | PLEASE SEE 240.21, 310.16, 240.4. | | PLEASE PROVIDE MORE INFORMATION. | | FBC 106.1.2, 106.3.5.1.2 | | | | 5) NOTE: PLEASE SEE 220.53 FOR MINIMUM LOADS TO BE | | FIGURED FOR SHOW WINDOW RECEPTACLES. PLEASE ADJUST | | SERVICE CALCULATIONS. | | | | 6) NOTE: PLEASE SEE THE EMERGENCY AND EXIT LIGHTS SHALL | | BE CIRCUITED TO THE LOCAL BRANCH CIRCUIT IN THAT AREA. | | PLEASE SEE 700.12F. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES | | WHICH MAY AFFECT ELECTRICAL PLANS |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-10-23 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-10-23 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-10-23 |
Time |
14:33 |
Sent To |
|
|
Notes |
2007-10-23 14:46:06 | *****APPROVED***** | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | BEEN ADDRESSED: PLAN SHEETS A-1.1 AND E-1.1 WERE | | STAMPED, INITIALED, AND DATED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-09-20 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-09-20 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-09-20 |
Time |
10:58 |
Sent To |
|
|
Notes |
2007-09-20 11:00:02 | *****UNSAT***** | | | | *THE FOLLOWING COMMENT FROM THE PREVIOUS FIRE PLAN | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 4.DECLARE INTERIOR WALL AND CEILING FINISH MATERIALS | | IN TERMS OF CLASS A, CLASS B, OR CLASS C.BASED UPON | | YOUR RESPONSE LETTER,ADD COMMENT "ALL FINISHES ARE | | CLASS A." TO SHEET A-1.0 | | | | *NEW COMMENT | | | | A. THERE WAS ONLY ONE PLAN SET THAT WAS SUBMITTED ALONG | | WITH THE OLD VOIDED SET.AT LEAST TWO, NO MORE THAN | | THREE PLAN SETS NEEDED | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-07-10 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-07-10 |
Time |
17:36 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-07-10 |
Time |
16:40 |
Sent To |
|
|
Notes |
2007-07-10 17:31:38 | *****DENIED***** | | | | | | 1.THE NUMERICAL ADDRESS, INCLUDING THE TENANT SPACE | | NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED | | PLAN SHEET. | | | | 2.NFPA 101, THE LIFE SAFETY CODE, 2003 EDITION SHALL | | BE REFERENCED.AMEND APPLICABLE CODE ON SHEET A-01. | | | | 3.CONSTRUCTION/DEMOLITION OPERATIONS AND/OR THE | | PLACEMENT OF THE DUMPSTER SHALL NOT INTERFERE OR HINDER | | EMERGENCY ACCESS RESPONSE TO THE PROPERTY OR VICINITY | | THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES). | | | | 4.DECLARE INTERIOR WALL AND CEILING FINISH MATERIALS | | IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | 5.INDICATE LOCATION OF THE 2A:10BC RATED FIRE | | EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-11-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-07 |
Time |
13:01 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-07 |
Time |
13:01 |
Sent To |
|
|
Notes |
2007-11-07 13:02:07 | TO "DPALMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-10-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-30 |
Time |
11:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-30 |
Time |
11:50 |
Sent To |
|
|
Notes |
2007-10-30 11:52:53 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-10-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-01 |
Time |
12:01 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-01 |
Time |
12:01 |
Sent To |
|
|
Notes |
2007-10-01 12:01:46 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-08-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-09 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-09 |
Time |
11:24 |
Sent To |
|
|
Notes |
2007-09-07 16:28:00 | TO "COMM" BD#42 | 2007-08-09 11:26:43 | WAITING FOR COMM BOARD. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-07-10 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-07-10 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-05-30 |
Time |
10:25 |
Sent To |
|
|
Notes |
2007-06-15 16:12:51 | TO "COMM"BD#22 | 2007-05-30 10:25:52 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2007-09-10 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-09-10 |
Time |
08:02 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-09-10 |
Time |
08:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-06-23 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-06-23 |
Time |
15:30 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-06-23 |
Time |
15:23 |
Sent To |
|
|
Notes |
2007-06-23 15:30:42 | --------------------DENIED--------------------- | | | | FBC 2004 CODE FAMILY W/ 2006 REVISIONS | | | | 1. PG A-0.1: PLEASE REFERENCE FLORIDA BUILDING CODE, | | MECHANICAL 2004 ON PLANS. | | | | 2. THE ENGINEER'S PRINTED NAME AND LICENCE NUMBER, | | ALONG WITH ENGINEERING FIRM'S CERTIFICATE OF | | AUTHORIZATION NUMBER ARE REQUIRED ON EACH PAGE FOR | | WHICH THE ENGINEER IS RESPONSIBLE PER FAC RULE | | 61G15-23.002 | | | | 3. AIR BALANCE AS SHOWN ON PLAN IS AT -20 CFM. | | MECHANICAL SYSTEMS SHALL BE DESIGNED TO ASSURE THAT | | BUILDINGS ARE PRESSURIZED WITH RESPECT TO THE OUTDOORS | | PER FBC 13-409.1.ABC.2 | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2007-09-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-09-10 |
Time |
10:59 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-09-10 |
Time |
10:59 |
Sent To |
|
|
Notes |
2007-09-10 11:00:19 | STILL NO PLUMBING WORK INDICATED/SHOWN |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2007-07-09 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-07-09 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-07-09 |
Time |
11:13 |
Sent To |
|
|
Notes |
2007-07-09 11:13:37 | NO PLUMBING WORK INDICATED |
|
|