Plan Review Details - Permit 07050986
Plan Review Stops For Permit 07050986
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-27 Cont ID  
Sent By shill Date 2007-08-27 Time 13:31 Rev Time 0.00
Received By shill Date 2007-08-27 Time 13:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-24 Cont ID  
Sent By shill Date 2007-07-24 Time 07:04 Rev Time 0.00
Received By shill Date 2007-07-24 Time 07:04 Sent To  
Notes
2007-07-24 07:06:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)PROVIDE A SITE PLAN SHOWING IMPROVEMENT LOCATION.
  
 2ND REVIEW - THIS WAS SUBMITTED, BUT IS A PHOTOCOPY.
 AN ENGINEERED SITE PLAN IS NOT REQUIRED BUT IF IT IS
 PREPARED BY AN ENGINEER, THE DOCUMENT IS TO BE A
 SIGNED, SEALED, DATED ORIGINAL FAC61G15-23.
  
 2.)DECLARE GOVERNING CODE (VERSION).
  
 3.)DECLARE DESIGN CRITERIA ASCE7 VERSION, FBC35.
  
 2ND REVIEW - THIS WAS NOT ADDRESSED; SAME ENGINEERING
 WAS SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By shill Date 2007-06-26 Time 08:04 Rev Time 0.00
Received By shill Date 2007-06-26 Time 08:04 Sent To Z
Notes
2007-06-26 08:05:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)PROVIDE A SITE PLAN SHOWING IMPROVEMENT LOCATION.
  
 2.)DECLARE GOVERNING CODE (VERSION).
  
 3.)DECLARE DESIGN CRITERIA ASCE7 VERSION, FBC35.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-22 Cont ID  
Sent By btrobaug Date 2007-08-22 Time 18:32 Rev Time 0.00
Received By btrobaug Date 2007-08-22 Time 18:28 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-20 Cont ID  
Sent By btrobaug Date 2007-07-20 Time 09:53 Rev Time 0.00
Received By btrobaug Date 2007-07-20 Time 08:40 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-30 Cont ID  
Sent By btrobaug Date 2007-05-30 Time 13:39 Rev Time 0.50
Received By btrobaug Date 2007-05-30 Time 13:27 Sent To B
Notes
2007-05-30 13:39:01 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
  
 1} PER 106.1.3 SUBMIT A SITE PLAN INDICATING LOCATION
 OF THE POLE .
  
 2} GIVE THE PANEL DESIGNATION, LOCATION AND CIRCUIT
 NUMBER(S) FEEDING THE POLE.
  
 3} INDICATE THE ROUTING OF THE FEED CONDUCTORS, THEIR
 SIZE AND TYPE OF CONDUIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 10:33 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 10:32 Sent To Z
Notes
2007-09-28 10:33:15TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-15 Cont ID  
Sent By adarroug Date 2007-08-15 Time 13:11 Rev Time 0.00
Received By adarroug Date 2007-08-15 Time 13:11 Sent To Z
Notes
2007-08-15 13:11:35TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 13:48 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 13:48 Sent To Z
Notes
2007-07-18 13:49:07TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-26 Cont ID  
Sent By btrobaug Date 2007-06-26 Time 08:06 Rev Time  
Received By shill Date 2007-05-25 Time 11:35 Sent To  
Notes
2007-05-25 11:35:28TO "E" BOX

Review Stop Z ZONING
Rev No 4 Status P Date 2007-10-02 Cont ID  
Sent By choops Date 2007-10-02 Time 13:37 Rev Time 0.00
Received By choops Date 2007-10-02 Time 13:37 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2007-08-16 Cont ID  
Sent By choops Date 2007-08-16 Time 12:55 Rev Time 0.00
Received By choops Date 2007-08-16 Time 12:55 Sent To E
Notes
2007-08-16 12:57:26***FAILED******RESUB #2***
  
  
 1) REPEAT COMMENT - PHOTOMETRIC PLAN TO EXTEND TO
 EDGE OF RESIDENTIAL DISTRICT, SHOWING FOOT CANDLES TO
 THAT POINT.(EDGE OF RESIDENTIAL DISTRICT IS AT MID
 POINT OF ROAD/ALLEY.)
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2007-07-19 Cont ID  
Sent By choops Date 2007-07-19 Time 14:49 Rev Time 0.00
Received By choops Date 2007-07-19 Time 14:49 Sent To E
Notes
2007-07-19 14:53:00***FAILED***
  
  
 1)SCOPE OF WORK / PROPOSED WORK IS INCONSISTENT.
 SCOPE OF WORK ON APPLICATION INDICATES ONE (1) LAMP
 POST.PLANS SHOW VARIOUS OTHER LIGHTS AND INDICATES
 LIGHT POST TO BE ON SEPARATE PERMIT???PLEASE
 CLARIFY.
  
 2)PHOTOMETRIC PLAN TO EXTEND TO EDGE OF RESIDENTIAL
 DISTRICT, SHOWING FOOT CANDLES TO THAT POINT.(EDGE OF
 RESIDENTIAL DISTRICT IS AT MID POINT OF ROAD/ALLEY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By choops Date 2007-06-26 Time 09:14 Rev Time 0.00
Received By choops Date 2007-06-26 Time 09:14 Sent To E
Notes
2007-06-26 09:19:50***FAILED***
  
  
 1)AS PER THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION 94-309(A);
  
 EXTERIOR LIGHTING.ALL OUTDOOR LIGHTING SHALL BE
 SHIELDED TO REDUCE GLARE AND SHALL BE ARRANGED TO
 REFLECT LIGHT OR GLARE AWAY FROM ALL ADJACENT
 RESIDENTIAL DISTRICTS, ADJACENT RESIDENCES, OR PUBLIC
 THOROUGHFARES.
  
 2)PLEASE PROVIDE A PHOTOMETRIC SITE PLAN SHOWING
 COMPLIANCE WITH SECTION 94-310(D):
  
 GLARE.ANY OPERATION OR ACTIVITY PRODUCING GLARE SHALL
 BE CONDUCTED SO THAT DIRECT OR INDIRECT LIGHT FROM THE
 SOURCE SHALL NOT CAUSE ILLUMINATION IN EXCESS OF 0.5
 FOOT CANDLES WHEN MEASURED IN A RESIDENTIAL DISTRICT
 (DIRECTLY ABUTTING).
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720


Account Summary | Usage Policy | Privacy Policy