Plan Review Details - Permit 07050984
Plan Review Stops For Permit 07050984
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-11 Cont ID  
Sent By lmartine Date 2007-07-11 Time 14:40 Rev Time 0.00
Received By lmartine Date 2007-07-11 Time 14:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-10 Cont ID  
Sent By shill Date 2007-07-10 Time 15:34 Rev Time 0.00
Received By shill Date 2007-07-10 Time 15:34 Sent To  
Notes
2007-07-10 15:35:24****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 ____1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13.
  
 ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY;
 MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF
 EACH ROOF TYPE
  
 _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 ____4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.
  
 ____5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
  
 _XX_ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM
 ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72.
  
 ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-04 Cont ID  
Sent By kconrad Date 2007-06-04 Time 18:29 Rev Time 0.00
Received By kconrad Date 2007-06-04 Time 17:49 Sent To I
Notes
2007-06-04 18:28:22PLANS EXAMINER: KEN CONRAD
 3814 SHELLY ROAD
 #07050984
  
 APPLICABLE CODE: 2004 FLORIDA EXISTING BUILDING CODE
  
 DENIED: SEE BELOW.
  
  
 A PRELIMINARY INSPECTION WAS PERFORMED. THE FOLLOWING
 WAS NOTED:
  
 1) REQUIRE TWO COPIES OF THE STATE AND LOCAL PRODUCT
 APPROVALS FOR THE ROOF TILE.
 2) DUE TO THE INTENDED SCOPE OF THE ROOF REPAIR
 ENCOMPASSING 30% OF THE ROOF, THE WORK SHALL COMPLY TO
 THE PROVISIONS OF FEBC 511.1.2.
  
 511.1GENERAL.
 MATERIALS AND METHODS OF APPLICATION USED FOR
 RECOVERING OR REPLACING AN EXISTING ROOF COVERING SHALL
 COMPLY WITH THE REQUIREMENTS OF CHAPTER 15 OF THE
 FLORIDA BUILDING CODE, BUILDING. ROOF REPAIRS TO
 EXISTING ROOFS AND ROOF COVERINGS SHALL COMPLY WITH THE
 PROVISIONS OF THIS CODE.
  
 511.1.2
 NOT MORE THAN 25 PERCENT OF THE TOTAL ROOF AREA OR ROOF
 SECTION OF ANY EXISTING BUILDING OR STRUCTURE SHALL BE
 REPAIRED, REPLACED OR RECOVERED IN ANY 12 MONTH PERIOD
 UNLESS THE ENTIRE ROOFING SYSTEM OR ROOF SECTION
 CONFORMS TO REQUIREMENTS OF THIS CODE.
  
 511.2STRUCTURAL AND CONSTRUCTION LOADS.
 THE STRUCTURAL ROOF COMPONENTS SHALL BE CAPABLE OF
 SUPPORTING THE ROOF COVERING SYSTEM AND THE MATERIAL
 AND EQUIPMENT LOADS THAT WILL BE ENCOUNTERED DURING
 INSTALLATION OF THE ROOF COVERING SYSTEM