Plan Review Details - Permit 07050962
Plan Review Stops For Permit 07050962
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-02-19 Cont ID  
Sent By amorse Date 2008-02-19 Time 15:38 Rev Time 0.00
Received By amorse Date 2008-02-19 Time 15:38 Sent To PC
Notes
2008-02-19 15:40:20 
  
 REVISION OF SINGLE HUNG WINDOW AND FRENCH DOOR PRODUCT
 APPROVALS IS APPROVED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-06 Cont ID  
Sent By amorse Date 2007-10-06 Time 10:51 Rev Time 0.00
Received By amorse Date 2007-10-06 Time 10:51 Sent To PC
Notes
2007-10-06 10:56:19 
  
 PASSED
  
 1)PROVIDE OLD SHEET THAT CONTAINS THE COUNTY IMPACT
 FEE STAMP TO BE ATTACHED TO THE CITY FILE SET
  
 2)FINALDATE STAMPING OF DRAWINGS AND PRODUCT
 APPROVALS WILL BE PERFORMED UPON RECEIPT OF CORRECTED
 ENERGY CALC'S AND STAMPED IMPACT FEE SHEET
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-13 Cont ID  
Sent By amorse Date 2007-09-13 Time 18:15 Rev Time 0.00
Received By amorse Date 2007-09-13 Time 18:15 Sent To PC
Notes
2007-09-13 18:41:39 
  
 DENIED
  
 1)IF THE GLASS BLOCK IS NO LONGER BEING USED AS THE
 MASTER BATH ROOM WINDOW PLEASE REMOVE FROM THE
 DRAWINGS. IF ANOTHER WINDOW IS TO BE INSTALLED SHOW
 SIZE AND STATE THAT SAFETY GLAZING WILL BE USED.
  
 2)THE PRODUCT APPROVAL FOR THE ENTRY DOORS MEETS THE
 DESIGN PRESSURE (-47.2 PSF) REQUIRED ON SHEET 2 OF THE
 DRAWINGS FOR THE SINGLE DOORS BUT NOT THE DOUBLE SET AT
 THE REAR, THE PRODUCT APPROVAL IS ONLY GOOD UP TO -45
 PSF
  
 3)THE PRODUCT APPROVAL FOR THE GARAGE DOOR IS FOR A
 COMMERCIAL ROLL UP TYPE, IS THIS SLAT TYPE DOOR THE
 TYPE YOU WISH TO INSTALL IF SO THE PROBLEM IS THE SAME
 AS COMMENT NUMBER 2, PRODUCT APPROVAL GOOD TO -34 PSF
 AND SHEET 2 OF DRAWINGS HAS A DESIGN PRESSURE OF -39.8
 PSF
  
 4)THE ENERGY CALCS PROVIDED SHOWAN R- VALUE OF 1586
 FOR INTERIOR CONCRETE WALL ?? PLEASE CLARIFY, ALSO
 COMPLETE THE INFORMATION IN THE TOP BOX
 (BUILDER,PERMITTING OFFICE,PERMIT # AND JURISDICTION
 #)
  
 PLEASE NOTE THAT ALL FEES AND A NOTICE OF COMMENCEMENT
 WILL BE DUE BEFORE A PERMIT CAN BE ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-30 Cont ID  
Sent By amorse Date 2007-06-30 Time 15:32 Rev Time 0.00
Received By amorse Date 2007-06-30 Time 15:32 Sent To PC
Notes
2007-06-30 15:59:34 
  
 DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MOREINFORMATION.
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: THE AMOUNT DUE FOR INCREASED VALUE AND STATE
 RADON FEES IS $ 3718.47 THIS AMOUNT MUST BE PAID BEFORE
 FURTHER REVIEWS ARE PERFORMED.
  
 4)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA
 STATE APPROVAL COVER PAGES, AND THE PRODUCT NOA THAT
 LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES, THE
 PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM TO BE USED AND
 THE GENERAL LIMITATIONS PAGE. ALL CAN BE FOUND ON
 WWW.FLORIDABUILDING.ORG
  
 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 6)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 7)PROVIDE PRODUCT APPROVALS FOR THE GLASS BLOCK AND
 TIE DOWNS AND CONNECTORS (IF PREFERRED FL#'S CAN BE
 ADDED TO THE CONNECTION SCHEDULE OR DOWNLOAD THE
 SIMPSON FLORIDA STATEWIDE APPROVAL INDEX AND MARK THE
 TIES/STRAPS/CONNECTORS THAT WILL BE USED
  
 8)PROVIDE 2 COPIES OF A COMPLETE SHUTTER SCHEDULE,
 SEE ATTACHED EXAMPLE SCHEDULE AND CITY MEMO
  
 9)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES.
  
 10)PROVIDE NOTE ON DRAWINGS FOR REQUIRED SAFETY
 GLAZINGAT SHOWER DOOR PER R 308.4 FBC RES.
  
 11)PROVIDE MEAN ROOF HEIGHT AND PITCH ON THE
 ELEVATION DRAWINGS
  
 12)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-04 Cont ID  
Sent By btrobaug Date 2007-09-04 Time 15:47 Rev Time 0.00
Received By btrobaug Date 2007-09-04 Time 15:01 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-06 Cont ID  
Sent By btrobaug Date 2007-06-06 Time 13:25 Rev Time 0.50
Received By btrobaug Date 2007-06-06 Time 12:01 Sent To P
Notes
2007-06-06 12:40:54 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1)
 AND 210.52 (A) (2).SEE BEDROOMS #3 AN 4.
  
 4} SMOKE DETECTORS ARE REQUIRED TO BE INTERCONNECTED
 PER R313.1 FBC, 11.8.2 NFPA-72. BEDROOMS 2 AND 3 NEED.
  
 5} THE AHU LOADS ON THE PANEL SCEDULE AND IN THE
 CALCULATIONS DO NOT CORRELATE. ALSO 125% SHOULD NOT BE
 USED IN THE CALCULATION FOR THE HEAT. SEE ARTICLE 220.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-02-13 Cont ID  
Sent By shill Date 2008-02-13 Time 13:25 Rev Time 0.00
Received By shill Date 2008-02-13 Time 13:25 Sent To B
Notes
2008-02-13 13:26:00TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 15:10 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 15:10 Sent To M
Notes
2007-10-11 15:10:57TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 14:40 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 14:40 Sent To Z
Notes
2007-09-24 14:40:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-28 Cont ID  
Sent By adarroug Date 2007-08-28 Time 15:56 Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 15:56 Sent To Z
Notes
2007-08-28 15:56:23TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-29 Cont ID  
Sent By adarroug Date 2007-05-29 Time 13:56 Rev Time 0.00
Received By adarroug Date 2007-05-29 Time 13:56 Sent To E
Notes
2007-05-29 13:56:22TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-06-30 Time   Rev Time 0.00
Received By adarroug Date 2007-05-25 Time 12:16 Sent To  
Notes
2007-05-25 12:17:09TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-10-22 Cont ID  
Sent By tgordon Date 2007-10-22 Time 08:18 Rev Time 0.45
Received By tgordon Date 2007-10-22 Time 08:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-09-28 Cont ID  
Sent By tgordon Date 2007-09-28 Time 14:42 Rev Time 0.30
Received By tgordon Date 2007-09-28 Time 14:42 Sent To B
Notes
2007-09-28 14:48:01PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 14A SHOWS A NATURAL GAS
 WATER HEATER, ELECTRICAL PLAN STATES THE WATER HEATER
 IS ELECTRIC, PLEASE CORRECT ENERGY CALCULATIONS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, SEE F.B.C.
 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-09-05 Cont ID  
Sent By tgordon Date 2007-09-05 Time 11:41 Rev Time 0.45
Received By tgordon Date 2007-09-05 Time 11:41 Sent To P
Notes
2007-09-05 12:07:13PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) SHOW JOB ADDRESS ON MECHANICAL PLAN, SEE WPB
 106.1.3.
  
 2) MECHANICAL PLANS NEED THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN, ADDRESS,
 PHONE NUMBER, AND ALL COMPANY INFORMATION (IF
 APPLICABLE), SEE WPB 106.1.3.
  
 3) SHOW THE A/C SYSTEMS TOTAL AND SENSIBLE BTU'S ON THE
 MECHANICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-31 Cont ID  
Sent By tgordon Date 2007-05-31 Time 12:09 Rev Time 0.30
Received By tgordon Date 2007-05-31 Time 12:09 Sent To E
Notes
2007-05-31 12:11:37*** DENIED ***
 1) MECHANICAL PERMIT #07050973 HAS BEEN APPLIED FOR BUT
 NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY
 OF WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-09-12 Cont ID  
Sent By mperson Date 2007-09-12 Time 09:02 Rev Time 0.00
Received By mperson Date 2007-09-12 Time 09:02 Sent To B
Notes
2007-09-12 09:07:01 
 ****************PROVISO****************
 (A) 406.3 THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN
 SHALL CONNECT TO A BRANCH DRAIN OR DRAINAGE STACK A
 MINIMUM OF 3 INCHES (76MM) IN DIAMETER.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By mperson Date 2007-06-19 Time 09:59 Rev Time 0.55
Received By mperson Date 2007-06-19 Time 09:59 Sent To B
Notes
2007-06-19 10:50:04DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. SHEET D-1 PLUMBING RISER:
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
 NOTE: THE SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRECT OR CLARIFY THE
 FOLLOWING FOR THE RESUBMITTAL.
 A} 1ST FLOOR KITCHEN SINK DOES NOT REFLECT THE
 FLOOR PLAN AND PLEASE ADD THE DISHWASHER DRAIN PER
 802.1.6 DOMESTIC DISHWASHING MACHINES SHALL DISCHARGE
 INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF THE
 KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD
 WASTE GRINDER. THE
 KITCHEN SINK APPEARS TO BE LOCATED IN AN ISLAND, IF SO
 PLEASE DELETE THE 2" VENT THROUGH ROOF AND ADD AN AIR
 ADMITTANCE VALVE PER 917.3.
 B} 1ST FLOOR BATH #4, THE LAV AND TUB DO NOT
 REFLECT THE FLOOR PLAN.
 C} 2ND FLOOR BATH #1, THE TUB, LAV, AND SHOWER DO
 NOT REFLECT THE FLOOR PLAN.
 D} 2ND FLOOR LAUNDRY, THE LAUNDRY TRAY IS MISSING
 FROM THE RISER DIAGRAM. PLEASE BE AWARE THAT THE
 MINIMUM SIZE REQUIRED TRAP AND STANDPIPE FOR THE
 WASHING MACHINE IS TWO INCH (2") PER 406.3 AND THAT YOU
 ARE INDICATING A THREE INCH TRAP BUT NO STANDPIPE.
 PLEASE INDICATE THE STANDPIPE FOR THE WASHING MACHINE
 AND PLEASE CLARIFY THAT IT IS YOUR INTENT TO USE A
 THREE INCH (3") TRAP ON THE RESUBMITTAL.
 E} 2ND FLOOR BATH #2, THE LAV AND TUB DO NOT
 REFLECT THE FLOOR PLAN.
 F} 2ND FLOOR BATH #3, THE LAV AND TUB DO NOT
 REFLECT THE FLOOR PLAN.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 3 Status P Date 2007-09-28 Cont ID  
Sent By choops Date 2007-09-28 Time 13:05 Rev Time 0.00
Received By choops Date 2007-09-28 Time 13:05 Sent To M
Notes
2007-09-28 13:07:14PROVISO:MUST MEET MINIMUM LANDSCAPE REGULATIONS FOUND
 IN SECTION 94-442 OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS: FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST
 ONE SHADE, FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR
 EACH 1,200 SQUARE FEET OF OPEN SPACE OR PORTION
 THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE
 SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN
 SPACE OR PORTION THEREOF.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-08-31 Cont ID  
Sent By choops Date 2007-08-31 Time 12:35 Rev Time 0.00
Received By choops Date 2007-08-31 Time 12:35 Sent To E
Notes
2007-08-31 12:45:41***FAILED***
  
  
 1)THE A/C AND MECHANICAL EQUIPMENT SETBACK SHOWN ON
 SURVEY IS INACCURATE.THE SETBACK IS SHOWN AS 11' TO
 THE PROPERTY LINE, HOWEVER, THERE IS ONLY 7.5' BETWEEN
 THE HOUSE AND PROPERTY LINE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-25 Cont ID  
Sent By choops Date 2007-05-25 Time 16:13 Rev Time 0.00
Received By choops Date 2007-05-25 Time 16:13 Sent To I
Notes
2007-05-25 16:21:20***FAILED***
  
  
 1)PLEASE SHOW REAR SETBACK DIMENSIONS MORE CLEARLY
 ON SURVEY (MUST BE AT LEAST 10.2 FT.)
  
 2)DRIVEWAY NOT INCLUDED IN THE SCOPE OF WORK FOR
 THIS PERMIT.EITHER FILE FOR A SEPERATE DRIVEWAY
 PERMIT, OR ADD IT TO THE SCOPE OF WORK AND ADJUST
 VALUE.
  
 3)PLEASE SHOW A/C / MECHANICAL EQUIPMENT ON SURVEYS
 WITH SETBACK DIMENSIONS TO THE PROPERTY LINES.
  
 4)ELEVATIONS SHALL BE SHOWN FROM GRADE TO THE
 MIDPOINT OF THE ROOF'S PITCH.
  
 5)PROVIDE ALL OVERHANG DIMENSIONS.
  
 6)THE FRONT SETBACK REQUIREMENT OF 25' SHALL BE FROM
 THE FRONT OF THE STRUCTURAL POSTS OF THE PORCH TO THE
 FRONT PROPERTY LINE.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720