Plan Review Details - Permit 07050939
Plan Review Stops For Permit 07050939
Review Stop P PLUMBING
Rev No 2 Status P Date 2007-05-30 Cont ID  
Sent By mperson Date 2007-05-30 Time 09:17 Rev Time 0.45
Received By mperson Date 2007-05-30 Time 09:17 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-25 Cont ID  
Sent By mperson Date 2007-05-25 Time 08:42 Rev Time 0.33
Received By mperson Date 2007-05-25 Time 08:42 Sent To PC
Notes
2007-05-25 08:57:34DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3
 PLUMBING (3) WATER RISER REQUIRED.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3
 PLUMBING (5)PLEASE INDICATE IF THERE IS A WATER
 HEATER FOR THE PROPOSED SINK AND IF THERE IS A WATER
 HEATER DEATAIL IS REQUIRED.
 NOTE: PLEASE INCLUDE THERMAL EXPANSION CONTROL OF WATER
 HEATER PER FBC-2004 PLUMBING, SECTIONS 607.3.1 AND
 6073.2.
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3
 PLUMBING (10) LOCATION OF WATER SUPPLY LINE REQUIRED.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721