Plan Review Details - Permit 07050881
Plan Review Stops For Permit 07050881
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-08-20 Cont ID  
Sent By lursu Date 2007-08-20 Time 16:51 Rev Time 0.00
Received By lursu Date 2007-08-20 Time 16:51 Sent To  
Notes
2007-08-20 17:00:35SITE ADDRESS AND PCN ARE CORRECT .
  
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-12-14 Cont ID  
Sent By jgomez Date 2007-12-14 Time 08:00 Rev Time 0.00
Received By jgomez Date 2007-12-14 Time 07:41 Sent To PC
Notes
2007-12-14 08:05:53MASTER BEDROOM EXTERIOR DOOR REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-10-04 Cont ID  
Sent By jgomez Date 2007-10-04 Time 10:01 Rev Time 0.00
Received By jgomez Date 2007-10-04 Time 10:01 Sent To PC
Notes
2007-10-04 10:02:48NEW RESIDENCE TRUSS DRAWINGS BUILDING REVIEW FIRST
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE AND 2004
 FBC.
  
 1- ENGINEER OF RECORD NEEDS TO REVIEW AND APPROVE TRUSS
 PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 2- "EACH OF THE DRAWINGS IN THE TRUSS DESIGN PACKAGE
 FOR INDIVIDUAL TRUSSES SHALL INCLUDE A TITLE BLOCK
 BEARING THE PRINTED NAME, ADDRESS, AND LICENSE NUMBER
 OF THE TRUSS DESIGN ENGINEER AND THE DATE OF THE
 DRAWINGS" AS REQUIRED BY SEC. 61G15-31.003(5) OF
 FLORIDA ADMINISTRATIVE CODE.
  
 3- ALL GENERAL DETAILS NEED TO HAVE ENGINEER'S ORIGINAL
 SEAL, SIGNATURE AND DATE AS WELL AS ALL ENGINEER'S
 INFORMATION AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE
 AND SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 4- SOME OF THE GENERAL DETAILS INCLUDED IN THE TRUSS
 PACKAGE ARE NOT LEGIBLE. PLEASE, MAKE SURE ALL COPIES
 ARE CLEAR AND LEGIBLE PRIOR TO SUBMITTAL. SEC. 106.1.3
 CITY AMENDMENTS TO FBC 2004.
  
 5- UPDATE "TRUSSED VALLEY DETAIL".DETAIL IS REFERRING
 TO ASCE 7-98 AND 100MPH. REVISEAS REQUIRED USING ASCE
 7-02 AND 140MPH.
  
 6- CONNECTORS SPECIFIED FOR ROOF TRUSS G1DON'T RESIST
 THE CALCULATED UPLIFT LOADS. ENGINEER OF RECORD TO
 REVISEROOF FRAMING PLAN AND TRUSS ANCHOR SCHEDULE AS
 REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 7- TRUSS PACKAGE INDEX SHEET IS MISSING THE NAME OF THE
 ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-31.003(5).
  
 8- THESE COMMENTS APPLY TO MAIN RESIDENCE AND GUEST
 HOUSE TRUSS PACKAGE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-24 Cont ID  
Sent By jgomez Date 2007-08-24 Time 15:07 Rev Time 0.00
Received By jgomez Date 2007-08-24 Time 15:07 Sent To PC
Notes
2007-08-24 15:07:52LILI SAYS ADDRESS IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-03 Cont ID  
Sent By jgomez Date 2007-08-03 Time 16:47 Rev Time 0.00
Received By jgomez Date 2007-08-02 Time 17:42 Sent To PC
Notes
2007-08-03 17:05:33BUILDING REVIEW:
 ***NOTE: NO FEES DUE WHEN RE-SUBMITTING WITH CORRECT
 LOT NUMBER.
 1-OWES $284.27 FOR UPDATED VALUATION AND RADON FEES.
  
 2- NEED TO CORRECT ISSUE REGARDING ADDRESS AND CORRECT
 LOT NUMBER.OUR PARCEL ID NUMBER INDICATES THAT THIS
 HOUSE WILL BE LOCATED ON LOT 8.PLEASE, CONTACT LILLI
 FROM THE ADDRESSING DEPARTMENT AT (561)822-1239TO
 MAKE SURE CORRECT ADDRESS AND LOT NUMBER IS WORKED OUT.
 THEN REVISEINFORMATION ON NOTICE OF COMMENCEMENT,
 PLANS, SURVEY,ETC.
 ***NOTE: IF NOTICE OF COMMENCEMENT NEEDS TO BE REVISED,
 THEN IT NEEDS TO BE RE-RECORDED AS WELL.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-29 Cont ID  
Sent By jgomez Date 2007-06-29 Time 18:57 Rev Time 0.00
Received By jgomez Date 2007-06-29 Time 18:45 Sent To PC
Notes
2007-06-29 18:58:20BUILDING REVIEW CHECKLIST:
 1- NEED TO PROVIDE TWO SETS WITH ORIGINAL ENGINEER'S
 SEAL AND SIGNATURE. ONLYONE SET WAS SIGNED AND
 SEALED.
  
 2- REVISE DRAINAGE PLAN.WATER NEED TO BE DIVERTED
 AWAY FROM THE NEIGHBOR'S PROPERTY.ARROWS SHOWN ON
 SURVEY SHOW WATER LEADING TO THE NEIGHBOR'S PROPERTY.
 REVISE AS REQUIRED.
  
 3- ENERGY CALCULATIONS NEED TO BE SIGNED AND DATED BY
 THE OWNER/AGENT.
 ALSO, COMPLETE INFORMATION ON TOP OF FORM AND REVISE
 OWNER INFORMATION.
  
 4- DRAWINGS TO HAVE CORRECT ADDRESS. THIS PROPERTY IS
 LOCATED ON LOT 8, NOT 9. REVISE AS REQUIRED.
  
 5- OWES $284.27 FOR UPDATED VALUATION AND RADON FEES.
  
 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) ALLSIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS.
 ***NOTE: PROVIDE ONLY THE FLROIDA PRODUCT APPROVAL
 COVERPAGE AND SHEET WHERE CONENCTORS IS SHOWN. 7-
 ENGINEER OF RECORDNEEDS TO REVIEW AND APPROVEIN
 WRITING (NOT SIGNING AND SEALING)ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS
 TO FBC 2004.
  
 8- REVISE ROOF SHEATHING SPECIFICATIONS. SEE SEC.
 R803.2.3.1 FOR MINIMUM TYPE OF NAIL TO BE USED AND
 SPACING FOR CORNER AREAS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-03-24 Cont ID  
Sent By btrobaug Date 2008-03-24 Time 14:12 Rev Time 0.00
Received By btrobaug Date 2008-03-24 Time 14:06 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-20 Cont ID  
Sent By btrobaug Date 2007-07-20 Time 08:13 Rev Time 0.00
Received By btrobaug Date 2007-07-20 Time 07:52 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-29 Cont ID  
Sent By btrobaug Date 2007-05-29 Time 14:23 Rev Time 0.50
Received By btrobaug Date 2007-05-29 Time 13:29 Sent To P
Notes
2007-05-30 09:38:56 
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE INFORMATION ON THE RISER DIAGRAM INDICATES THE
 METER AND PANEL ARE "EXISTING", THE APPLICATION IS FOR
 A NEW RESIDENCE.
  
 2} THE WATER HEATERS APPEARS TO PLUG IN TO A 220 VOLT
 RECEPTACLE.SEE 422.16 FOR CORD CONNECTED APPLIANCES.
 CHANGE SYMBOL TO A DISCONNECT IF REQUIRED.
  
 3} SEE 210.52(C)(5) FOR RECEPTACLE REQUIREMENTS AT THE
 "PASS THROUGH".NOTE THE EXEPTION.
  
 4} A SMOKE ALARM IS REQUIRED "OUTSIDE--IN THE IMMEDIATE
 VICINITY" OF THE BEDROOM IN THE GUEST HOUSE PER 313.1.1
 FBC RESIDENTIAL.
  
 5} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. ALL SHEETS.
  
 NOTE: THE ABSENCE OF T.V. AND PHONE DEVICES ON THE PLAN
 WILL DICTATE ANOTHER SET OF PLANS BE SUBMITTED SHOWING
 THOSE LOCATIONS AND ANOTHER PERMIT APPLIED FOR.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
2007-05-29 14:13:21 
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-13 Cont ID  
Sent By shill Date 2007-12-13 Time 20:02 Rev Time 0.00
Received By shill Date 2007-12-13 Time 20:02 Sent To B
Notes
2007-12-13 20:03:39TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-19 Cont ID  
Sent By adarroug Date 2007-09-19 Time 11:02 Rev Time 0.00
Received By adarroug Date 2007-09-19 Time 11:02 Sent To B
Notes
2007-09-19 11:02:59TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 10:22 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 10:22 Sent To Z
Notes
2007-07-18 10:23:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-29 Cont ID  
Sent By jgomez Date 2007-06-29 Time 18:58 Rev Time 0.00
Received By jgomez Date 2007-05-23 Time 15:56 Sent To  
Notes
2007-05-23 15:56:49TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-08-02 Cont ID  
Sent By tgordon Date 2007-08-02 Time 11:02 Rev Time 0.30
Received By tgordon Date 2007-08-02 Time 11:02 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-29 Cont ID  
Sent By tgordon Date 2007-05-29 Time 10:47 Rev Time 0.25
Received By tgordon Date 2007-05-29 Time 10:47 Sent To E
Notes
2007-05-29 10:48:04*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) PLEASE SHOW THE SEER OF THE A/C SYSTEMS ON THE
 MECHANICAL PLANS.
  
 3) PLEASE SHOW THE LOCATION OF THE CLOTHES DRYER VENTS
 TERMINATION ON THE MECHANICAL PLANS, BE ADVISED THE
 CLOTHES DRYERS MAY NOT DISCHARGE NEAR THE A/C CONDENSER
 UNITS, SEE 2004 FBC/M 501.2 .
  
 4) SEE COOLING LOAD CALCULATIONS PAGE 3 SHOWS NO
 MINIMUM AND MAXIMUM VELOCITY'S, PLEASE CORRECT.
  
 5) SEE MECHANICAL PLANS FOR THE COTTAGE THE 6" MAIN
 SUPPLY DUCT TO THE MIXING BOX AT 800 CFM'S WOULD BE A
 HIGH PRESSURE DUCT, PLEASE SHOW ON PLANS THAT THE DUCTS
 ARE TO BE METAL AS FLEX DUCT IS NOT RATED FOR HIGH
 PRESSURE, OR RE-CALCULATE DUCT CALCULATIONS.
  
 6) SEE MECHANICAL PLANS MAIN HOUSE THE TWO 6" MAIN
 SUPPLY AIR DUSTS TO THE MIXING BOXES APPEARS TO BE A
 MISTAKE PLEASE RE-CALCULATE DUCT CALCULATIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-02 Cont ID  
Sent By mperson Date 2007-08-02 Time 08:28 Rev Time 0.33
Received By mperson Date 2007-08-02 Time 08:28 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By mperson Date 2007-06-13 Time 09:52 Rev Time 0.50
Received By mperson Date 2007-06-13 Time 09:52 Sent To B
Notes
2007-06-13 12:02:01DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PROPOSED RESIDENCE SHEET NO 2, PLUMBING RISER:PER
 FBC-2004, CHAPTER 1, SECTION
 106.1.3, QUALITY OF BUILDING PLANS: THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST,
 CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
 NOTE: THE SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE REFERENCE THE FOLLOWING
 RED LINE CORRECTIONS ON THIS SHEET FOR THE
 RESUBMITTAL.
 A} LAV IN MASTER BATH.
 B} LAV AND TUB IN THE BATHROOM BETWEEN BEDROOMS#1
 AND #2.
 C} KITCHEN SINK WITH DISPOSAL.
 D} CLEANOUT REQUIRED FOR WASHING MACHINE TO BE
 LOCATED AT FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.)
 PER FBC-2004 PLUMBING, SECTION 708.9.
 E} DELETE "SEPTIC" FROM "4" TO SEPTIC SEWER" ON
 THE RESUBMITTAL.
  
 2. PROPOSED GUEST HOUSE SHEET D-1, PLUMBING RISER: PER
 FBC-2004, CHAPTER 1, SECTION 106.1.3, THE SANITARY
 ISOMETRIC RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN. PLEASE REFERENCE THE RED LINE CORRECTIONS ON THIS
 SHEET FOR THE RESUBMITTAL.
 A} LAV AND TUB IN BATHROOM.
 B} KITCHEN SINK.
 C} CLEANOUT REQUIRED FOR THE WASHING MACHINE TO
 BE LOCATED AT FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.)
 PER FBC-2004 PLUMBING, SECTION 708.9.
 D} DELETE "SEPTIC" FROM "4" TO SEPTIC SEWER" ON
 THE RESUBMITTAL.
  
 3. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING. IF AN ARCHITECT OR
 ENGINEER, COMPLY WITH 418 AND 417 FS, RESPECTIVELY. ALL
 SHEETS
 NOTE: THE ENGINEER SEAL APPEARS TO BE INITIALED INSTEAD
 OF BEING SIGNED. REFERENCE PROPOSED RESIDENCE SHEET T1
 COPIED SIGNATURE OF ENGINEER H. JOHN GRIFFIN II, PE
 #38647 AND COMPARE. ALSO ENGINEER LICENSE NUMBER
 MISSING ON SOME SHEETS. PLEASE CORRECT THIS ON THE
 RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-02 Cont ID  
Sent By choops Date 2007-08-02 Time 08:41 Rev Time 0.00
Received By choops Date 2007-08-02 Time 08:41 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-25 Cont ID  
Sent By choops Date 2007-05-25 Time 11:01 Rev Time 0.00
Received By choops Date 2007-05-25 Time 11:01 Sent To E
Notes
2007-05-25 11:02:15***FAILED***
  
  
 1)ACCESSORY APARTMENT BUILDING NOT PERMITTED IN MF14
 ZONED AREAS.
  
 ***IF YOU WISH TO CONTINUE WITH THE SINGLE FAMILY
 DWELLING THE FOLLOWING WILL NEED REVISED.
  
 2)PROVIDE SETBACK DIMENSIONS FROM PROPOSED A/C UNITS
 TO PROPERTY LINES.
  
 3)PLEASE SHOW ELEVATION FROM GRADE TO MIDPOINT OF
 ROOF'S PITCH.
  
 4)PLEASE INCLUDE LANDSCAPE PLANS THAT INDICATES
 COMPLIANCE WITH SECTION 94-442 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 5)PROVIDE ALL OVERHANG DIMENSIONS
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved