Plan Review Details - Permit 07050872
Plan Review Stops For Permit 07050872
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-08-07 Cont ID  
Sent By rbrown Date 2009-08-07 Time 13:24 Rev Time 0.00
Received By rbrown Date 2009-08-07 Time 13:24 Sent To  
Notes
2009-08-07 13:24:55SITE SPECIFIC PRODUCT APPROVAL FOR CUSTOM ENTRY DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-06-28 Cont ID  
Sent By amorse Date 2008-06-28 Time 08:49 Rev Time 0.00
Received By amorse Date 2008-06-28 Time 08:49 Sent To PC
Notes
2008-06-28 08:50:55 
  
 PASSED
  
 PRODUCT APPROVAL SUBMITTAL FOR WALK THROUGH GARAGE DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-23 Cont ID  
Sent By amorse Date 2008-01-23 Time 18:01 Rev Time 0.00
Received By amorse Date 2008-01-23 Time 18:01 Sent To PC
Notes
2008-01-23 18:58:54 
 PASSED
  
 PLEASE HAVE ARCHITECTURAL SHEETS SP/1, A/7 AND A/8 THAT
 WERE REVISED FOR ZONING COMMENTS SIGNED AND SEALED
 BEFORE BEING RESUBMITTED FOR OUTSTANDING ZONING
 COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-23 Cont ID  
Sent By amorse Date 2007-08-23 Time 18:32 Rev Time 0.00
Received By amorse Date 2007-08-23 Time 18:32 Sent To PC
Notes
2007-08-23 18:42:56 
  
 DENIED
  
 1)FILL OUT BUILDER, JURISDICTION NUMBER, ETC.
 INFORMATION ON THE ENERGY CALC'S
  
 2)CLOPAY GARAGE DOOR DOES NOT MEET THE DESIGN
 PRESSURES REQUIRED BY STRUCTURAL ENGINEERS WIND LOAD
 PRESSURES IN SCHEDULE ON S-7
  
 3)PROVIDE PRODUCT APPROVAL FOR THE SLOPED JOIST
 HANGER ON SECTION 07/S-6 AND THE HGA10 CLIP ON SECTIONS
 03/S-6 AND 05/S-6
  
 4)THE CALCULATIONS PROVIDED FROM RAS 117 FOR THE
 MODIFIED ROOF SYSTEM ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE PREPARER
  
 5)REMOVE ALL OLD PAGES FROM PERMIT SET EXCEPT FOR THE
 PAGE WITH THE IMPACT FEE STAMP
  
 6)PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING, THE NOTICE IS
 VOID
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-30 Cont ID  
Sent By amorse Date 2007-06-30 Time 14:01 Rev Time 0.00
Received By amorse Date 2007-06-30 Time 14:01 Sent To PC
Notes
2007-06-30 14:32:14 
  
 DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION. PLEASE SEE THAT THE SQUARE FOOTAGE ONLY
 APPLIES TO ADDITION AND DOES NOT INCLUDE TWO STORY
 GUEST HOUSE, IF COUNTY HAS EXEMPTED THIS BUILDING
 PLEASE PROVIDE LETTER FROM THAT JURISDICTION
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES.
 NOTE: THE AMOUNT DUE FOR INCREASED VALUE AND STATE
 RADON FEES IS $ 218.04 AND IS PAYABLE BEFORE FURTHER
 REVIEWS ARE MADE.
  
 4)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FL BLDG CODE WITH 2006 AMENDMENTS.
 THIS APPLIES TO ARCHITECTURAL AND STRUCTURAL DRAWINGS.
  
 5)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 6)IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE
 OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2
 COPIES OF A SOIL TEST REPORT SHALL BE SUBMITTED PER
 R401.4 FBC RES.
  
 7)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. SEPARATE ENERGY CALC'S ARE REQUIRED FOR
 THE ADDITION AND THE NEW GUEST HOUSE
  
 8)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 9)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA
 STATE APPROVAL COVER PAGES, AND THE PRODUCT NOA THAT
 LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES, THE
 PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM TO BE USED AND
 THE GENERAL LIMITATIONS PAGE. ALL CAN BE FOUND ON
 WWW.FLORIDABUILDING.ORG
  
 10)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
  
 11)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 12)PLEASE CLARIFY FOUNDATION SCHEDULE ON S/1 THEIR
 ARE 2 F30 FOOTING MARKS
  
 13)PLEASE CLARIFY STRUCTURAL STEEL COLUMNS WITH THE
 BASE PLATE TYPES ON THE COLUMN SCHEDULE
  
 14)ADD NOTE TO NEW SLABS THAT TERMITE TREATMENT IS
 REQUIRED ON ALL EXTERIOR CONCRETE WITHIN 1 FOOT OF
 PRIMARY STRUCTURE PER 1816.1.6 OR R320.1.6 FBC
  
 15)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
  
 16)PROVIDE NOTE FOR BALCONY GUARDRAIL OR SHOW
 DIMENSIONS THAT MEET THE REQUIREMENTS OF R312.2 FBC
 RES.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-10-06 Cont ID  
Sent By btrobaug Date 2008-10-06 Time 16:57 Rev Time 0.00
Received By btrobaug Date 2008-10-06 Time 12:22 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-09-19 Cont ID  
Sent By btrobaug Date 2008-09-19 Time 16:46 Rev Time 0.00
Received By btrobaug Date 2008-09-19 Time 16:34 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-09-04 Cont ID  
Sent By btrobaug Date 2008-09-04 Time 10:31 Rev Time 0.00
Received By btrobaug Date 2008-09-04 Time 08:17 Sent To M
Notes
2008-09-04 10:31:16 
  
  
 REVISION DENIED
  
 1} THE ENGINEER OF RECORD MUST SIGN, DATE AND SEAL THE
 DOCUMENT. 61G15-23.002 FAC. COVENANT ENGINEERING WAS
 THE DESIGN TEAM FOR THE PERMIT SET OF PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-22 Cont ID  
Sent By btrobaug Date 2008-01-22 Time 11:23 Rev Time 0.00
Received By btrobaug Date 2008-01-22 Time 09:56 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-16 Cont ID  
Sent By btrobaug Date 2007-08-16 Time 10:56 Rev Time 0.00
Received By btrobaug Date 2007-08-16 Time 07:26 Sent To P
Notes
2007-08-16 07:48:50 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE GENERATOR MUST BE PERMITTED SEPARATELY. THE
 MANUAL TRANSFER SWITCH MAY BE LEFT ON THE RISER WITH
 THIS PERMIT, BUT MANUFACTURERS SPECIFICATIONS MUST BE
 SUBMITTED FOR REVIEW PRIOR TO A PERMIT BEING ISSUED.
 MAKE A NOTE ON THE RISER DIAGRAM, SHEET E-2, THAT THE
 GENERATOR WILL BE PERMITTED SEPARATELY. REMOVE THE "
 +NEW DRIVEWAY+NEW GENERATOR" PENCIL ADDITIONS IN THE
 DESCRIPTION ON THE APPLICATION. IF ADDING TO THE
 DESCRIPTION INCREASE THE VALUE TO INCLUDE SAME.
  
 2}NOTE THE SIZE PER 250.122, #2 IS EXCESSIVE, AND
 ALTHOUGH PERMITTED, WILL PROBABLY RESULT IN A LATER
 REVISION. SEE TABLE. THIS COMMENT REFERS TO THE PANEL
 "A" FEED FROM THE TRANSFER SWITCH.
  
 3} REGARDING NOTE #5, PREVIOUS REVIEW "THERE IS
 EQUIPMENT LISTED IN THE CALCULATIONS THAT ARE NOT ON
 ANY PANEL SCHEDULES. SEE REVIEWED PLAN." THE POOL PANEL
 WITH A 10240 W CALCULATED LOAD STILL IS LISTED IN THE
 LOAD CALCULATION(SERVICE), 6283 VA IN THE POOL
 EQUIPMENT CALCULATION AND ONLY A PUMP AND LIGHT ARE
 LISTED IN PANEL "A". PLEASE CORRELATE TO INDICATE
 ACTUAL CONDITIONS.
  
 4} PANEL "A", CIRCUIT 1,3,SHEET E-2, LISTS #3
 CONDUCTORS FEEDING PANEL "B", AND THE RISER FEEDERS ARE
 LISTED AS #2. PLEASE VERIFY EXISTING CONDITIONS AND
 CORRECT ON PLAN.
  
 5} CIRCUITS 16 AND 18, PANEL "A" ARE REVERSED FROM THE
 NUMBERED CIRCUITS ON SHEET E-2. SMALL APPLIANCE
 (REQUIRED) AND LIGHTING.
  
 NOTE #1: CIRCUIT # A24,FOR THE SMOKE DETECTORS MUST
 BE ON A AFCI PER 210.12, THE OUTSIDE LIGHTS ARE ON THIS
 SAME CIRCUIT, NO VIOLATION, JUST A NOTE.
 #2: ALTHOUGH THE GENERATOR IS NOT BEING
 REVIEWED AT THIS TIME, IT WAS NOTED THAT THE GENERATOR
 CALCULATION IS 101 AMPS (24KW), THE SPEC'S SUBMITTED
 ARE FOR A 20KW GENERATOR WITH AN OUTPUT OF 84 AMPS.
  
 THE DESIGNER OF RECORD IS THE ENGINEER THAT SEALED THE
 PLAN, THE RESPONSE FOR THE PREVIOUS REVIEW WAS SIGNED
 BY THE ARCHITECT. PLEASE SEE THAT ALL GET A COPY OF
 THESE COMMENTS.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS.
 ANSWER REVIEW COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-05 Cont ID  
Sent By btrobaug Date 2007-06-05 Time 12:32 Rev Time 1.00
Received By btrobaug Date 2007-06-05 Time 11:33 Sent To P
Notes
2007-06-05 12:32:52 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} ALL COMMENTS ARE REQUIREMENTS OF THE 2004 FLORIDA
 BUILDING CODE AND REFERENCED MATERIAL THEREIN,
 INCLUDING THE 2005 NEC.. NOTE #4, SHEET E-1 REFERENCES
 INCORRECT CYCLES.
  
 2} NOTE 14, SHEET E-1DOES NOPT ALLOW FOR NMC. WHILE NOT
 IN VIOLATION, IF IT REMAINS AS WRITTEN, ALL WIRING MUST
 BE INSTALLED IN CONDUIT, OR A REVISION WILL BE REQUIRED
 TO CHANGE THIS NOTE AT A LATER DATE, AND COULD CREATE A
 WORK HOLD UNTILL SUBMITTED AND REVIEWED.
  
 3} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6. ALSO NOTE
 THE SIZE PER 250.122, #2 IS EXCESSIVE, AND ALTHOUGH
 PERMITTED, WILL PROBABLY RESULT IN A LATER REVISION.
 SEE TABLE.
  
 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. THE
 ARTICLE QUOTED, 220.11, IS INCORRECT, PANEL "C" SHOULD
 NOT BE CALCULATED SEPARATELY.
  
 5} THERE IS EQUIPMENT LISTED IN THE CALCULATIONS THAT
 ARE NOT ON ANY PANEL SCHEDULES. SEE REVIEWED PLAN.
  
 6} LOCATE THE POOL PANEL ON THE PLAN AND RISER.
  
 7} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE
 SAME ON PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2008-01-22 Cont ID  
Sent By mperson Date 2008-01-22 Time 15:08 Rev Time 0.00
Received By mperson Date 2008-01-22 Time 15:08 Sent To M
Notes
2008-01-22 15:10:57NOTE: GENERATOR AND GAS NOT IN CONTRACT, TO BE
 SUBMITTED SEPERATELY.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-08-17 Cont ID  
Sent By mperson Date 2007-08-17 Time 08:28 Rev Time 0.33
Received By mperson Date 2007-08-17 Time 08:28 Sent To B
Notes
2007-08-17 08:54:16DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. SHEET P-1 AND P-2 INDICATE A PROPOSED GENERATOR: A
 SEPERATE PERMIT IS REQUIRED. EITHER REMOVE FROM PLANS
 OR LABEL "TO BE PERMITTED SEPERATELY."
 **LABEL GAS PIPING TO GENERATOR
 "FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE
 GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF
 GENERATOR PLACEMENT.
 NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET
 CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES
 SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS
 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR
 TO FINAL INSPECTION."
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-06-14 Cont ID  
Sent By mperson Date 2007-06-14 Time 09:20 Rev Time 0.33
Received By mperson Date 2007-06-14 Time 09:20 Sent To B
Notes
2007-06-14 10:25:28DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. NOTE: THERE IS NO INDICATION OF A GENERATOR BEING
 APPLIED FOR ON THE PERMIT APPLICATION. ON THE PERMIT
 APPLICATION IT STATES "DESCRIBE PROJECT IN DETAIL
 (FAILURE TO DO SO MAY RESULT IN DELAYS)". A SEPERATE
 PERMIT IS REQUIRED FOR THE GENERATOR.
 A} SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT (GENERATOR) TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 B} A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING FOR
 THE GENERATOR LOCATION.
  
 2. REMOVE GENERATOR AND GAS FROM RESUBMITTED PRINTS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-01-10 Cont ID  
Sent By ssherman Date 2008-01-10 Time 14:44 Rev Time 0.00
Received By ssherman Date 2008-01-10 Time 14:44 Sent To  
Notes
2008-01-10 14:45:04HISTORICAL APPROVAL PER GALINA JUDGE

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-07-22 Cont ID  
Sent By lmartine Date 2009-07-22 Time 15:41 Rev Time 0.00
Received By lmartine Date 2009-07-22 Time 15:43 Sent To  
Notes
2009-07-22 15:43:21GAVE TO MCDOUGLE

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-09-24 Cont ID  
Sent By adarroug Date 2008-09-24 Time 14:36 Rev Time 0.00
Received By adarroug Date 2008-09-24 Time 14:36 Sent To E
Notes
2008-09-24 14:37:16TO "BTROBUAG" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-09-12 Cont ID  
Sent By adarroug Date 2008-09-12 Time 12:43 Rev Time 0.00
Received By adarroug Date 2008-09-12 Time 12:43 Sent To E
Notes
2008-09-12 12:51:23TO "BTROBAUGH" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 16:35 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 16:35 Sent To E
Notes
2008-09-03 16:35:24TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-06-25 Cont ID  
Sent By adarroug Date 2008-06-25 Time 10:13 Rev Time 0.00
Received By adarroug Date 2008-06-25 Time 10:12 Sent To B
Notes
2008-06-25 10:13:14TO "AMORSE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-04 Cont ID  
Sent By adarroug Date 2008-06-04 Time 16:28 Rev Time 0.00
Received By adarroug Date 2008-06-04 Time 16:27 Sent To M
Notes
2008-06-04 16:28:15TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-11 Cont ID  
Sent By spalmer Date 2008-01-11 Time 10:37 Rev Time 0.00
Received By spalmer Date 2008-01-11 Time 10:37 Sent To Z
Notes
2008-01-11 10:37:27TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-08 Cont ID  
Sent By dpalmer Date 2007-08-08 Time 18:50 Rev Time 0.00
Received By dpalmer Date 2007-08-08 Time 18:49 Sent To Z
Notes
2007-08-08 18:50:42TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-06-30 Time   Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 15:48 Sent To  
Notes
2007-05-23 15:48:43TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-10-07 Cont ID  
Sent By tgordon Date 2008-10-07 Time 09:37 Rev Time 0.35
Received By tgordon Date 2008-10-07 Time 09:37 Sent To  
Notes
2008-10-07 09:39:32SUBMITTAL LETTER HAD BEEN EXCEPTED 9/18/08 CONTRACTORS
 COPY IS BEING RETURNED TO CONTRACTOR.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-09-18 Cont ID  
Sent By tgordon Date 2008-09-18 Time 11:04 Rev Time 0.40
Received By tgordon Date 2008-09-18 Time 11:04 Sent To E
Notes
2008-09-18 11:05:29REVISION TO MECH. PLANS M-2, M-3 AND E-CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-09-04 Cont ID  
Sent By tgordon Date 2008-09-04 Time 15:45 Rev Time 0.45
Received By tgordon Date 2008-09-04 Time 15:45 Sent To  
Notes
2008-09-04 15:50:02PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS.
 *** DENIED ***
  
 1) THE MECHANICAL PLANS ON FILE WERE SIGNED AND SEALED
 BY AN ENGINEER (EDWARD J. KRANZ) SO ONLY HE CAN MAKE
 REVISIONS TO THEM, PER FAC 61G15-23.002.
  
 2) ENERGY CALCULATION ON FILE ARE CALLING FOR HEAT PUMP
 UNIT, REVISED MECHANICAL PLAN IS SHOWING A STRAIGHT
 COOLING SYSTEM. PLEASE CORRECT PLANS OR REVISE ENERGY
 CALCULATIONS, PER 2004 FBC 13-103.3.
  
 3) PLAN M-3 A/C SCHEDULE IS CALLING FOR A 60 AMP FUSE
 FOR A 5 KW HEATER, PLEASE CORRECT TO MANUFACTURES
 SPEC'S.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-06-09 Cont ID  
Sent By tgordon Date 2008-06-09 Time 10:42 Rev Time 0.45
Received By tgordon Date 2008-06-09 Time 10:42 Sent To  
Notes
2008-06-09 10:54:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS.
 *** DENIED ***
  
 1) THE MECHANICAL PLANS ON FILE WERE SIGNED AND SEALED
 BY AN ENGINEER (EDWARD J. KRANZ) SO ONLY HE CAN MAKE
 REVISIONS TO THEM, PER FAC 61G15-23.002.
  
 2) ENERGY CALCULATION ON FILE ARE CALLING FOR HEAT PUMP
 UNIT, REVISED MECHANICAL PLAN IS SHOWING A STRAIGHT
 COOLING SYSTEM. PLEASE CORRECT PLANS OR REVISE ENERGY
 CALCULATIONS, PER 2004 FBC 13-103.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-05-24 Cont ID  
Sent By tgordon Date 2007-05-24 Time 10:39 Rev Time 0.30
Received By tgordon Date 2007-05-24 Time 10:38 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-22 Cont ID  
Sent By mperson Date 2008-01-22 Time 15:02 Rev Time 0.00
Received By mperson Date 2008-01-22 Time 15:02 Sent To G
Notes
2008-01-22 15:08:14*****************PROVISO******************
 THE MAIN HOUSE NEW PANTRY PERFBC PLUMBING SECTION
 *909.1 WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE
 VENTED BY A WET VENT. THE WET VENT SHALL BE CONSIDERED
 THE VENT FOR THE FIXTURES AND SHALL EXTEND FROM THE
 CONNECTION OF THE DRY VENT ALONG THE DIRECTION OF THE
 FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE
 DRAIN CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY
 THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT.
 THE NEW SINK FOR THE PANTRY MUST DRAIN DOWNSTREAM OF
 THE EXISTING BATHROOM IF BATHROOM IS WET VENTED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-06-14 Cont ID  
Sent By btrobaug Date 2007-06-05 Time 12:33 Rev Time 0.45
Received By mperson Date 2007-06-14 Time 09:19 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2008-02-12 Cont ID  
Sent By choops Date 2008-02-12 Time 13:53 Rev Time 0.00
Received By choops Date 2008-02-12 Time 13:53 Sent To PC
Notes
2008-02-12 13:54:04***APPROVED - RESUB #2 - CONTRACTOR SUBMITTED REQUESTED
 INFORMATION ON 2-12-08***

Review Stop Z ZONING
Rev No 3 Status F Date 2008-01-15 Cont ID  
Sent By choops Date 2008-01-15 Time 14:45 Rev Time 0.00
Received By choops Date 2008-01-15 Time 14:44 Sent To E
Notes
2008-01-15 14:35:49***FAILED - RESUB #2***
  
  
 REPEAT COMMENT:
  
 1)AN APPROVED EASEMENT CONSENT FORM FROM THE CITY OF
 WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES (1ST
 FLOOR CITY HALL) IS REQUIRED FOR ALL PROPOSED
 FENCES/WALLS.THE SUBMITTED FORM IS BLANK AND HAS NOT
 BEEN APPROVED BY THE DEPARTMENT OF PUBLIC UTILITIES.
  
 NEW COMMENT:
  
 1)AS THE VALUE OF THE PROPOSED WORK HAS INCREASED,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF THE
 PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE,
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.PLEASE
 SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION
 94-442 AND 94-445 OF THE ZLDRS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" = BT

Review Stop Z ZONING
Rev No 2 Status F Date 2007-08-10 Cont ID  
Sent By choops Date 2007-08-10 Time 17:08 Rev Time 0.00
Received By choops Date 2007-08-10 Time 17:08 Sent To E
Notes
2007-08-10 17:13:41***FAILED******RESUB #1***
  
  
 1)NEWLY SUBMITTED PLANS SHALL BE RE-STAMPED AND
 APPROVED BY HISTORIC PRESERVATION.
  
 2)PROPOSED GUESTHOUSE A/C EQUIPMENT ENCROACHES TOO
 FAR INTO REQUIRED SETBACK.MEASURED FROM REQUIRED
 SETBACK OF PRINCIPAL HOUSE WHICH IS 13.5 FEET...MAY
 ENCROACH 4' INTO THAT...A/C MUST BE 9.5 FEET AWAY FROM
 REAR PROPERTY LINE.
  
 3)PLAN SHOWS NEW GENERATOR, MUST BE PERMITTED
 SEPARATELY.EITHER REMOVE FROM PLANS OR LABEL "TO BE
 PERMITTED SEPARATELY".
  
 4)INDICATE OVERHANG DIMENSIONS FROM THE WALL TO THE
 OUTERMOST POINT OF THE ROOF. (REPEAT COMMENT)
  
 5)PLANS SP-1 SHOW CONCRETE PIERS.PLEASE PROVIDE AN
 EASEMENT CONSENT FORM FROM THE CITY OF WEST PALM BEACH
 DEPARTMENT OF PUBLIC UTILITIES.
  
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-24 Cont ID  
Sent By choops Date 2007-05-24 Time 09:20 Rev Time 0.00
Received By choops Date 2007-05-24 Time 09:20 Sent To E
Notes
2007-05-24 09:25:35***FAILED***
  
  
 1)DRIVEWAY/APPROACH NOT INCLUDED IN SCOPE OF WORK IN
 THIS PERMIT.EITHER ADD TO PERMIT AND ADD VALUE, OR
 FILE SEPERATE PERMIT.
  
 2)PLEASE PROVIDE ELEVATIONS FROM GRADE TO THE
 MIDPOINT OF ROOF'S PITCH.
  
 3)PLEASE PROVIDE ALL OVERHANG DIMENSIONS FROM THE
 WALL TO ROOF'S OUTERMOST POINT.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720