Plan Review Details - Permit 07050861
Plan Review Stops For Permit 07050861
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-11-27 Cont ID  
Sent By mperson Date 2007-11-27 Time 13:10 Rev Time 0.00
Received By mperson Date 2007-11-27 Time 13:10 Sent To PC
Notes
2007-11-27 13:17:11GAS REVISION #2: THE CHANGING OF THE PIPING LAYOUT TO
 THE WATER HEATER AND THE ADDITION OF THE ADDED MAXITROL
 MP REGULATOR TO THE BBQ HAS BEEN REVIEWED AND APPROVED
 FOR CODE COMPLIANCE.
  
 ****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 NOTE: REFERENCE MASTER PERMIT #07011206 FOR GENERATOR
 MANUFACTURER'S SPECIFICATIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-11-08 Cont ID  
Sent By mperson Date 2007-11-08 Time 14:07 Rev Time 0.00
Received By mperson Date 2007-11-08 Time 14:07 Sent To PC
Notes
2007-11-08 14:11:07REVISION: "OK" EQUIPMENT LAYOUT CHANGED AND ADDED
 TANKLESS WATER HEATER.
  
 ****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 NOTE: REFERENCE MASTER PERMIT #07011206 FOR GENERATOR
 MANUFACTURER'S SPECIFICATIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-06-18 Cont ID  
Sent By mperson Date 2007-06-18 Time 11:44 Rev Time 0.45
Received By mperson Date 2007-06-18 Time 11:44 Sent To PC
Notes
2007-06-18 11:51:37NOTE: GENERATOR LOCATION AND MANUFACTURER
 SPECIFICATIONS ARE APPROVED ON PERMIT #07011206.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPENINGSREQUIRED
 PER SECTION 304.5 OR SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 9,950 CUBIC FEET REQUIRED.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-08 Cont ID  
Sent By adarroug Date 2007-11-08 Time 09:50 Rev Time 0.00
Received By adarroug Date 2007-11-08 Time 09:50 Sent To G
Notes
2007-11-08 09:51:35TO "G" BOX/REV--PLANS WERE ROUTED TO GAS UNDER ANOTHER
 PERMIT# GIVEN BY THE CONTRACTOR.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-18 Cont ID  
Sent By mperson Date 2007-06-18 Time 11:53 Rev Time 0.00
Received By mperson Date 2007-05-23 Time 08:42 Sent To  
Notes
2007-05-23 08:42:29TO "G" BOX