Plan Review Details - Permit 07050844
Plan Review Stops For Permit 07050844
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-29 Cont ID  
Sent By adarroug Date 2007-05-29 Time 11:49 Rev Time 0.00
Received By adarroug Date 2007-05-29 Time 11:49 Sent To M
Notes
2007-05-29 11:49:50TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-23 Cont ID  
Sent By tgordon Date 2007-05-23 Time 10:09 Rev Time 0.00
Received By tgordon Date 2007-05-22 Time 14:46 Sent To  
Notes
2007-05-22 14:46:43TO "M" BOX/RESUB

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-06-12 Cont ID  
Sent By tgordon Date 2007-06-12 Time 11:51 Rev Time 0.20
Received By tgordon Date 2007-06-12 Time 11:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-05-29 Cont ID  
Sent By tgordon Date 2007-05-29 Time 14:56 Rev Time 0.30
Received By tgordon Date 2007-05-29 Time 14:56 Sent To  
Notes
2007-05-29 15:03:51*** DENIED ***
 1) COOLING LOAD CALCULATIONS SUBMITTED ARE FOR 2265
 SQUARE FEET AND A 4.7 TON A/C SYSTEM. THE ADDITION IS
 ONLY 480 SQUARE FEET. PLEASE SUBMIT CORRECT COOLING
 LOAD CALCULATIONS, SEE 2004 FBC 13-607.1.ABC.1.
  
 2) PLEASE SUBMIT TWO COPIES OF ALL PAPER WORK.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-23 Cont ID  
Sent By tgordon Date 2007-05-23 Time 09:47 Rev Time 0.45
Received By tgordon Date 2007-05-23 Time 09:47 Sent To  
Notes
2007-05-23 10:09:44*** DENIED ***
 1) THE MECHANICAL PERMIT MAY NOT ATTACHE TO THE MASTER
 PERMIT AS THE MASTER PERMIT SHOWED NO MECHANICAL WORK
 TO BE DONE.
  
 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 3) THE JOB ADDRESS MUST APPEAR ON ALL PLANS, SEE 2004
 FBC CITY WPB AMEND. 106.1.3.
  
 4) PLEASE SUBMIT ENERGY CALCULATIONS,PER 2004 FBC
 13-101.2.2, (12-8-06 REVISION).
  
 5) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1.
  
 6) IT APPEARS THE AIR HANDLER IS LOCATED IN THE
 BATHROOM AND THE RETURN AIR DUCT IS AN OPEN DUCT,
 RETURN AIR MAY NOT COME FROM THE BATHROOM THIS WILL
 HAVE TO BE A CLOSED DUCT SYSTEM, PLEASE CORRECT, SEE
 2004 FBC/R M1602.2(4).
  
 7) PLEASE SHOW THE TOTAL AND SENSIBLE COOLING BTU'S ON
 THE PLANS.
  
 8) PLEASE BE ADVISED YOU WILL NEED TO FILE A NOTICE OF
 COMMENCEMENT FOR THE A/C WORK.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.