Plan Review Details - Permit 07050823
Plan Review Stops For Permit 07050823
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-07-09 Cont ID  
Sent By shill Date 2007-07-09 Time 11:31 Rev Time 0.00
Received By shill Date 2007-07-09 Time 11:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By shill Date 2007-07-09 Time 11:29 Rev Time 0.00
Received By shill Date 2007-06-13 Time 17:34 Sent To  
Notes
2007-06-13 17:42:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)YOU HAVE STATED ON THE INSTALLATION SCHEDULE THAT
 YOU ARE DESIGNING TO -77PSF, BUT HAVE CIRCLED -62 ON
 THE PRODUCT APPROVAL.C2 CONNECTION WITH A -77 DESIGN
 PRESSURE REQUIRES 5"SPACING, SEE OPENING 4.PLEASE
 REVISE EITHER THE DESIGN PRESSURES ON THE INSTALLATION
 SCHEDULE OR ANCHOR SPACING.CHECK ALL OPEININGS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-09 Cont ID  
Sent By shill Date 2007-07-09 Time 11:32 Rev Time 0.00
Received By adarroug Date 2007-07-09 Time 11:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-22 Cont ID  
Sent By adarroug Date 2007-06-22 Time 15:53 Rev Time 0.00
Received By shill Date 2007-06-22 Time 15:53 Sent To B
Notes
2007-06-22 15:53:29TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-13 Cont ID  
Sent By shill Date 2007-06-13 Time 17:43 Rev Time 0.00
Received By shill Date 2007-05-22 Time 15:25 Sent To  
Notes
2007-05-22 15:25:30TO "MISC" BOX#1