Plan Review Stops For Permit 07050661 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-08-30 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-08-30 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-08-30 |
Time |
13:47 |
Sent To |
PC |
|
Notes |
2007-08-30 14:12:00 | BUILDING PROVISO: | | TO BE IN PLACE AT C.O.: | | | | 1) 424.2.17.1 OUTDOOR SWIMMING POOLS. | | OUTDOOR SWIMMING POOLS SHALL BE PROVIDED | | WITH A BARRIER COMPLYING WITH | | 424.2.17.1.1 THROUGH 424.2.17.1.14. | | 424.2.17.1.5 CHILD SAFETY BARRIER | | ASTM D5034 100 LB TENSILE STRENGTH | | ASTM D3787 150 LB BALL BURST STRENGTH | | 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED. | | SPAS AND HEATED SWIMMING POOLS SHALL BE | | EQUIPPED WITH A COVER DESIGNED TO | | MINIMIZE HEAT LOSS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2007-07-24 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-07-24 |
Time |
08:42 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-07-24 |
Time |
06:51 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-06-22 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-06-22 |
Time |
07:12 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-06-21 |
Time |
14:56 |
Sent To |
PC |
|
Notes |
2007-06-21 16:00:17 | BUILDING PLAN REVIEW | | PERMIT: 07050661 | | ADD: 285 CORDOVA RD. | | CONT: CRAFTMASTER CUSTOM POOLS | | TEL: (561)278-3515 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 1ST | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 2)IS THE EXISTING CBS WALL ENCLOSING THE ENTIRE | | PROPERTY? IF IT IS, SHOW THIS INFORMATION ON THE | | DRAWINGS AND INDICATE THE HEIGHT OF THE FENCE. | | | | 3)SHOW IN DETAIL HOW THE CHILD BARRIER WILL MEET THE | | REQUIREMENTS OF FBC. SEC.4101.17. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-08-29 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-08-29 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-08-29 |
Time |
13:51 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2007-07-05 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-07-05 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-07-05 |
Time |
15:28 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-06-06 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-05-29 |
Time |
10:04 |
Rev Time |
0.25 |
Received By |
btrobaug |
Date |
2007-05-29 |
Time |
10:00 |
Sent To |
P |
|
Notes |
2007-06-06 15:58:33 | | | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | WHEN RESUBMITTING BADU JET INFORMATION, INCLUDE THE | | CHANGE ON THE ELECTRICAL SCHEMATIC AND INFORMATIION(HP) | | IN THE SPECIFICATIONS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
N |
Date |
2007-08-29 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-08-29 |
Time |
13:04 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-08-29 |
Time |
13:04 |
Sent To |
E |
|
Notes |
2007-08-29 13:06:33 | CONTRACTOR INFORMATION | | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | BEFORE FINAL POOL INSPECTION. | | | | REVIEW BY MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL= [email protected] | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
N |
Date |
2007-07-23 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-07-23 |
Time |
09:21 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-07-23 |
Time |
09:21 |
Sent To |
B |
|
Notes |
2007-07-23 09:24:04 | CONTRACTOR INFORMATION | | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | BEFORE FINAL POOL INSPECTION. | | | | REVIEW BY MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL= [email protected] | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2007-06-06 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-06-06 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-06-06 |
Time |
14:49 |
Sent To |
B |
|
Notes |
2007-06-06 14:51:29 | CONTRACTOR INFORMATION | | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | BEFORE FINAL POOL INSPECTION. | | | | REVIEW BY MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-08-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-21 |
Time |
09:31 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-21 |
Time |
09:31 |
Sent To |
P |
|
Notes |
2007-08-21 09:32:13 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-07-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-03 |
Time |
08:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-03 |
Time |
08:59 |
Sent To |
Z |
|
Notes |
2007-07-03 09:00:10 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-05-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-23 |
Time |
11:45 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-23 |
Time |
11:45 |
Sent To |
E |
|
Notes |
2007-05-23 11:45:39 | TO "E" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-07-05 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-07-05 |
Time |
15:28 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-05-18 |
Time |
08:43 |
Sent To |
|
|
Notes |
2007-07-05 15:30:25 | THE "OUT" FOR THIS STOP WAS LEFT OPEN, I CLOSED IT | | TODAY./WRT. | 2007-05-18 08:43:35 | TO "Z" BOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2007-08-29 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-08-29 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-08-29 |
Time |
11:39 |
Sent To |
G |
|
Notes |
2007-08-29 13:03:22 | ****************PROVISO**************** | | A} PER FBC-2004 SECTION 424.2.6.6.3 ENTRAPMENT | | ADVOIDANCE. ALL POOLS AND SPAS SHALL HAVE A BACKUP | | SYSTEM WHICH SHALL PROVIDE VACUUM PROTECTION SHOULD | | GRATE COVERS BECOME MISSING OR INOPERATIVE WITH RESPECT | | TO THEIR APPROVED USE. VACUUM PROTECTION DEVICES SHALL | | CONSIST OF ONE OF THE FOLLOWING: | | | | 1. APPROVED SAFETY VACUUM RELEASE SYSTEM (SVRS). | | | | 2. APPROVED VENT PIPING. | | | | 3. OTHER DEVICES OR MEANS. | | | | NOTE: THE BADU-JET SYSTEM SHALL BE PROTECTED BY ONE OF | | THE ABOVE. | | | | B} SHEET 1, PLUMBING ITEMS INDICATE AN AUTO FILL: THE | | AUTO FILL PIPE SHALL BE INSTALLED BY A LICENSED | | PLUMBING CONTRACTOR WHERE IT CONNECTS TO THE POTABLE | | WATER SYSTEM AND BE INSTALLED PER FBC-2004 PLUMBING | | SECTION 608 PROTECTION OF POTABLE WATER SUPPLY. | | | | REVIEW BY MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL= [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-07-23 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-07-23 |
Time |
08:17 |
Rev Time |
0.33 |
Received By |
mperson |
Date |
2007-07-23 |
Time |
08:07 |
Sent To |
G |
|
Notes |
2007-07-23 09:20:22 | DENIED 2ND TIME | | REFERENCE: | | ** FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING POOLS. | | ** FBC-2004 PLUMBING. | | ** FBC-2004 CHAPTER 1, THE CITY OF | | WEST PALM BEACH AMENDMENTS. | | ** FLORIDA ADMINISTRATIVE CODE. | | ** FLORIDA STATUTES. | | | | 1. RESPONSE IS NOTED ON THE BADU JET SWIM PUMP BUT THE | | SYSTEM IS NOT CODE COMPLIANT PER THE FOLLOWING: A} | | FBC-2004 SEC.424.2.6.6.4, OR FBCR-2004 SEC. | | R4101.6.6.4 MINIMUM OF TWO SUCTION INLETS SHALL BE | | PROVIDED FOR EACH PUMP. SEPARATED BY A MINIMUM OF 3 | | FEET OR LOCATED ON TWO DIFFERENT PLANES.B} FBC-2004 | | SEC 424.2.6.6, OR FBCR-2004 SEC R4101.6.6 ENTRAPMENT | | PROTECTION FOR SUCTION INLETS. THE RESUBMITTED BADU | | SYSTEM DOES NOT REFLECT THOSE REQUIREMENTS. (DETAIL | | REQUIRED ON SHEET 4 OF 5 AND INDICATED ON 1 OF 5) | | NOTE: THE SUBMITTED BADU SYSTEM MATERIAL FROM MET | | LABORATORIES IS INDICATING THAT THE BADU JET SUCTION | | COVER HAS BEEN TESTED AND ACCEPTED BY A RECOGNIZED | | FACILITY AND COMPLIES WITH ANSI/ASME A112.19.8M BUT | | THIS SYSTEM IS NOT FBC-2004 CODE COMPLIANT. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL= [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-06-06 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-06-06 |
Time |
15:58 |
Rev Time |
0.45 |
Received By |
mperson |
Date |
2007-06-06 |
Time |
13:38 |
Sent To |
G |
|
Notes |
2007-06-06 14:48:58 | DENIED | | REFERENCE: | | ** FBC-2004 SECTIONS 424.2 AND R4101 SWIMMING POOLS. | | ** FBC-2004 CHAPTER 1, THE CITY OF | | WEST PALM BEACH AMENDMENTS. | | ** FLORIDA ADMINISTRATIVE CODE. | | ** FLORIDA STATUTES. | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | 1. PLEASE SUBMIT A DETAIL OF THE PROPOSED "BADU SWIM | | JET". ALSO SUBMIT TWO COPIES OF MANUFACTURER'S | | SPECIFICATIONS OF THE PROPOSED "BADU SWIM JET" AND | | PLEASE PROVIDE THE FOLLOWING INFORMATION INDICATING THE | | SYSTEM IS CODE COMPLIANT. | | A} FBC-2004 SEC 424.2.6.6, OR FBCR-2004 | | SEC R4101.6.6 ENTRAPMENT PROTECTION FOR | | SUCTION INLETS. (DETAIL REQUIRED) | | B} FBC-2004 424.2.6.6.2, OR FBCR-2004 | | SEC R4101.6.6.2 SHOW COMPLIANCE WITH | | ANSI/ASME A112.19.8M. PROVIDE MODEL | | NUMBER AND MANUF INFO FOR VAC LOCK. | | (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) | | C} FBC-2004424.2.6.6.3, OR FBCR-2004 | | SEC R4101.6.6.3 (1,2,3) ENTRAPMENT | | AVOIDANCE. (DETAIL REQUIRED) | | D} FBC-2004 SEC.424.2.6.6.4, OR | | FBCR-2004 SEC. R4101.6.6.4 MINIMUM OF | | TWO SUCTION INLETS SHALL BE PROVIDED FOR | | EA PUMP. SEPARATED BY A MINIMUM OF 3 | | FEET OR LOCATED ON TWO DIFFERENT PLANES. | | (DETAIL REQUIRED) | | E} FBC-2004 SEC. 424.6.6 OR FBC-2004 | | RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT | | PROTECTION FOR SUCTION INLETS. PLEASE | | SUBMIT AN ENGINEERED TABLE FOR "VENT | | PIPE MAXIMUM LENGTH" INDICATING PUMP | | SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH | | OF THE 1" OR 1-1/2" PVC VENT PIPE, FROM | | WHERE IT STARTS TO WHERE IT ENDS UP, | | COMPLYING WITH THE THREE SECOND RELEASE. | | NOTE: THE SUBMITTED VENT PIPE MAXIMUM LENGTH TABLE ON | | SHEET 3 ONLY GOES AS HIGH AS A 3 HORSEPOWER PUMP. FROM | | PAST PLAN REVIEWS OF THIS SYSTEM PUMPS HAVE HADHIGHER | | HORSEPOWER RATINGS. PLEASE ADJUST TABLE ACCORDINGLY FOR | | THE "BADU SWIM JET" SYSTEM ON THE RESUBMITTAL. | | | | 2. SHEET 1 SPECIFICATIONS, PLEASE ADD THE "BADU SWIM | | JET" PUMP HORSEPOWER SIZE TO THE POOL EQUIPMENT ITEMS. | | | | 3. SHEET 1 SPECIFICATIONS, PLEASE ADD THE THREE POOL | | RETURNS TO THE POOL EQIPMENT ITEMS. THE ONLY RETURNS TO | | POOL INDICATED ARE THE 3 JETS ON THE BENCH. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2007-08-21 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-08-21 |
Time |
16:58 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-08-21 |
Time |
16:58 |
Sent To |
P |
|
Notes |
2007-08-21 17:00:37 | PROVISO:POOL EQUIPMENT MUST BE A MINIMUM OF 1' FROM | | THE WEST SIDE PROPERTY LINE AND A MINIMUM OF 8.5' FROM | | THE NORTH (REAR) PROPERTY LINE. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2007-07-05 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-07-05 |
Time |
09:36 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-07-05 |
Time |
09:36 |
Sent To |
E |
|
Notes |
2007-07-05 09:54:16 | ***FAILED*** | | | | | | 1)POOL EQUIPMENT LOCATION NOT CONSISTANT BETWEEN | | PLANS.CLARIFY LOCATION. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | TECHNICIAN | | (561)805-6720 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-05-22 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-05-22 |
Time |
17:22 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-05-22 |
Time |
17:22 |
Sent To |
I |
|
Notes |
2007-05-22 17:28:36 | ***FAILED*** | | | | | | 1)PLEASE PROVIDE SETBACK DIMENSIONS FROM POOL | | EQUIPMENT TO PROPERTY LINES ON THE 2 SURVEYS. | | | | 2)SURVEY SHOWS A FENCE SURROUNDING ON 3 SIDES, BUT | | NOT COMPLETELY ENCLOSING THE POOL AREA.ALSO SHOWS | | PARTS AS 3 FT. WHICH IS ALSO NOT SUFFICIENT.A | | SEPERATE PERMIT WILL BE REQUIRED FORA FENCE THAT | | MEETS REQUIREMENTS.PLEASE SEE THE CITY OF WEST PALM | | BEACH ZONING AND LAND DEVELOPMENT REGULATIONS SECTION | | 94-304(D)(2)(B)+(C): | | | | B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE | | OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT | | ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF | | THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED. | | BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN | | HEIGHT ABOVE GRADE. | | C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE | | THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND | | SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR | | WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF | | GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL | | SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH | | WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT | | SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A | | 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE, | | AT THE PROPERTY LINE, TO ENSURE PRIVACY. | | | | | | CHRIS HOOPS | | ZONING TECHNICIAN | | 561-805-6720 | | | | | | |
|
|