Plan Review Details - Permit 07050661
Plan Review Stops For Permit 07050661
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-30 Cont ID  
Sent By mjacobs Date 2007-08-30 Time 14:49 Rev Time 0.00
Received By mjacobs Date 2007-08-30 Time 13:47 Sent To PC
Notes
2007-08-30 14:12:00BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRENGTH
 ASTM D3787 150 LB BALL BURST STRENGTH
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-07-24 Cont ID  
Sent By mjacobs Date 2007-07-24 Time 08:42 Rev Time 0.00
Received By mjacobs Date 2007-07-24 Time 06:51 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-22 Cont ID  
Sent By mjacobs Date 2007-06-22 Time 07:12 Rev Time 0.00
Received By mjacobs Date 2007-06-21 Time 14:56 Sent To PC
Notes
2007-06-21 16:00:17BUILDING PLAN REVIEW
 PERMIT: 07050661
 ADD: 285 CORDOVA RD.
 CONT: CRAFTMASTER CUSTOM POOLS
 TEL: (561)278-3515
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)IS THE EXISTING CBS WALL ENCLOSING THE ENTIRE
 PROPERTY? IF IT IS, SHOW THIS INFORMATION ON THE
 DRAWINGS AND INDICATE THE HEIGHT OF THE FENCE.
  
 3)SHOW IN DETAIL HOW THE CHILD BARRIER WILL MEET THE
 REQUIREMENTS OF FBC. SEC.4101.17.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-29 Cont ID  
Sent By btrobaug Date 2007-08-29 Time 13:59 Rev Time 0.00
Received By btrobaug Date 2007-08-29 Time 13:51 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-05 Cont ID  
Sent By btrobaug Date 2007-07-05 Time 16:02 Rev Time 0.00
Received By btrobaug Date 2007-07-05 Time 15:28 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-06 Cont ID  
Sent By btrobaug Date 2007-05-29 Time 10:04 Rev Time 0.25
Received By btrobaug Date 2007-05-29 Time 10:00 Sent To P
Notes
2007-06-06 15:58:33 
  
  
  
 DENIED/INCOMPLETE INFORMATION
  
 WHEN RESUBMITTING BADU JET INFORMATION, INCLUDE THE
 CHANGE ON THE ELECTRICAL SCHEMATIC AND INFORMATIION(HP)
 IN THE SPECIFICATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2007-08-29 Cont ID  
Sent By mperson Date 2007-08-29 Time 13:04 Rev Time 0.00
Received By mperson Date 2007-08-29 Time 13:04 Sent To E
Notes
2007-08-29 13:06:33CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-07-23 Cont ID  
Sent By mperson Date 2007-07-23 Time 09:21 Rev Time 0.00
Received By mperson Date 2007-07-23 Time 09:21 Sent To B
Notes
2007-07-23 09:24:04CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-06-06 Cont ID  
Sent By mperson Date 2007-06-06 Time 14:49 Rev Time 0.00
Received By mperson Date 2007-06-06 Time 14:49 Sent To B
Notes
2007-06-06 14:51:29CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 09:31 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 09:31 Sent To P
Notes
2007-08-21 09:32:13TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-03 Cont ID  
Sent By adarroug Date 2007-07-03 Time 08:59 Rev Time 0.00
Received By adarroug Date 2007-07-03 Time 08:59 Sent To Z
Notes
2007-07-03 09:00:10TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 11:45 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 11:45 Sent To E
Notes
2007-05-23 11:45:39TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-05 Cont ID  
Sent By btrobaug Date 2007-07-05 Time 15:28 Rev Time 0.00
Received By btrobaug Date 2007-05-18 Time 08:43 Sent To  
Notes
2007-07-05 15:30:25THE "OUT" FOR THIS STOP WAS LEFT OPEN, I CLOSED IT
 TODAY./WRT.
2007-05-18 08:43:35TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-08-29 Cont ID  
Sent By mperson Date 2007-08-29 Time 11:39 Rev Time 0.00
Received By mperson Date 2007-08-29 Time 11:39 Sent To G
Notes
2007-08-29 13:03:22****************PROVISO****************
 A} PER FBC-2004 SECTION 424.2.6.6.3 ENTRAPMENT
 ADVOIDANCE. ALL POOLS AND SPAS SHALL HAVE A BACKUP
 SYSTEM WHICH SHALL PROVIDE VACUUM PROTECTION SHOULD
 GRATE COVERS BECOME MISSING OR INOPERATIVE WITH RESPECT
 TO THEIR APPROVED USE. VACUUM PROTECTION DEVICES SHALL
 CONSIST OF ONE OF THE FOLLOWING:
  
 1. APPROVED SAFETY VACUUM RELEASE SYSTEM (SVRS).
  
 2. APPROVED VENT PIPING.
  
 3. OTHER DEVICES OR MEANS.
  
 NOTE: THE BADU-JET SYSTEM SHALL BE PROTECTED BY ONE OF
 THE ABOVE.
  
 B} SHEET 1, PLUMBING ITEMS INDICATE AN AUTO FILL: THE
 AUTO FILL PIPE SHALL BE INSTALLED BY A LICENSED
 PLUMBING CONTRACTOR WHERE IT CONNECTS TO THE POTABLE
 WATER SYSTEM AND BE INSTALLED PER FBC-2004 PLUMBING
 SECTION 608 PROTECTION OF POTABLE WATER SUPPLY.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-07-23 Cont ID  
Sent By mperson Date 2007-07-23 Time 08:17 Rev Time 0.33
Received By mperson Date 2007-07-23 Time 08:07 Sent To G
Notes
2007-07-23 09:20:22DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING POOLS.
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. RESPONSE IS NOTED ON THE BADU JET SWIM PUMP BUT THE
 SYSTEM IS NOT CODE COMPLIANT PER THE FOLLOWING: A}
 FBC-2004 SEC.424.2.6.6.4, OR FBCR-2004 SEC.
 R4101.6.6.4 MINIMUM OF TWO SUCTION INLETS SHALL BE
 PROVIDED FOR EACH PUMP. SEPARATED BY A MINIMUM OF 3
 FEET OR LOCATED ON TWO DIFFERENT PLANES.B} FBC-2004
 SEC 424.2.6.6, OR FBCR-2004 SEC R4101.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. THE RESUBMITTED BADU
 SYSTEM DOES NOT REFLECT THOSE REQUIREMENTS. (DETAIL
 REQUIRED ON SHEET 4 OF 5 AND INDICATED ON 1 OF 5)
 NOTE: THE SUBMITTED BADU SYSTEM MATERIAL FROM MET
 LABORATORIES IS INDICATING THAT THE BADU JET SUCTION
 COVER HAS BEEN TESTED AND ACCEPTED BY A RECOGNIZED
 FACILITY AND COMPLIES WITH ANSI/ASME A112.19.8M BUT
 THIS SYSTEM IS NOT FBC-2004 CODE COMPLIANT.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-06 Cont ID  
Sent By btrobaug Date 2007-06-06 Time 15:58 Rev Time 0.45
Received By mperson Date 2007-06-06 Time 13:38 Sent To G
Notes
2007-06-06 14:48:58DENIED
 REFERENCE:
 ** FBC-2004 SECTIONS 424.2 AND R4101 SWIMMING POOLS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE SUBMIT A DETAIL OF THE PROPOSED "BADU SWIM
 JET". ALSO SUBMIT TWO COPIES OF MANUFACTURER'S
 SPECIFICATIONS OF THE PROPOSED "BADU SWIM JET" AND
 PLEASE PROVIDE THE FOLLOWING INFORMATION INDICATING THE
 SYSTEM IS CODE COMPLIANT.
 A} FBC-2004 SEC 424.2.6.6, OR FBCR-2004
 SEC R4101.6.6 ENTRAPMENT PROTECTION FOR
 SUCTION INLETS. (DETAIL REQUIRED)
 B} FBC-2004 424.2.6.6.2, OR FBCR-2004
 SEC R4101.6.6.2 SHOW COMPLIANCE WITH
 ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 C} FBC-2004424.2.6.6.3, OR FBCR-2004
 SEC R4101.6.6.3 (1,2,3) ENTRAPMENT
 AVOIDANCE. (DETAIL REQUIRED)
 D} FBC-2004 SEC.424.2.6.6.4, OR
 FBCR-2004 SEC. R4101.6.6.4 MINIMUM OF
 TWO SUCTION INLETS SHALL BE PROVIDED FOR
 EA PUMP. SEPARATED BY A MINIMUM OF 3
 FEET OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL REQUIRED)
 E} FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1" OR 1-1/2" PVC VENT PIPE, FROM
 WHERE IT STARTS TO WHERE IT ENDS UP,
 COMPLYING WITH THE THREE SECOND RELEASE.
 NOTE: THE SUBMITTED VENT PIPE MAXIMUM LENGTH TABLE ON
 SHEET 3 ONLY GOES AS HIGH AS A 3 HORSEPOWER PUMP. FROM
 PAST PLAN REVIEWS OF THIS SYSTEM PUMPS HAVE HADHIGHER
 HORSEPOWER RATINGS. PLEASE ADJUST TABLE ACCORDINGLY FOR
 THE "BADU SWIM JET" SYSTEM ON THE RESUBMITTAL.
  
 2. SHEET 1 SPECIFICATIONS, PLEASE ADD THE "BADU SWIM
 JET" PUMP HORSEPOWER SIZE TO THE POOL EQUIPMENT ITEMS.
  
 3. SHEET 1 SPECIFICATIONS, PLEASE ADD THE THREE POOL
 RETURNS TO THE POOL EQIPMENT ITEMS. THE ONLY RETURNS TO
 POOL INDICATED ARE THE 3 JETS ON THE BENCH.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 3 Status P Date 2007-08-21 Cont ID  
Sent By choops Date 2007-08-21 Time 16:58 Rev Time 0.00
Received By choops Date 2007-08-21 Time 16:58 Sent To P
Notes
2007-08-21 17:00:37PROVISO:POOL EQUIPMENT MUST BE A MINIMUM OF 1' FROM
 THE WEST SIDE PROPERTY LINE AND A MINIMUM OF 8.5' FROM
 THE NORTH (REAR) PROPERTY LINE.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-07-05 Cont ID  
Sent By choops Date 2007-07-05 Time 09:36 Rev Time 0.00
Received By choops Date 2007-07-05 Time 09:36 Sent To E
Notes
2007-07-05 09:54:16***FAILED***
  
  
 1)POOL EQUIPMENT LOCATION NOT CONSISTANT BETWEEN
 PLANS.CLARIFY LOCATION.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-22 Cont ID  
Sent By choops Date 2007-05-22 Time 17:22 Rev Time 0.00
Received By choops Date 2007-05-22 Time 17:22 Sent To I
Notes
2007-05-22 17:28:36***FAILED***
  
  
 1)PLEASE PROVIDE SETBACK DIMENSIONS FROM POOL
 EQUIPMENT TO PROPERTY LINES ON THE 2 SURVEYS.
  
 2)SURVEY SHOWS A FENCE SURROUNDING ON 3 SIDES, BUT
 NOT COMPLETELY ENCLOSING THE POOL AREA.ALSO SHOWS
 PARTS AS 3 FT. WHICH IS ALSO NOT SUFFICIENT.A
 SEPERATE PERMIT WILL BE REQUIRED FORA FENCE THAT
 MEETS REQUIREMENTS.PLEASE SEE THE CITY OF WEST PALM
 BEACH ZONING AND LAND DEVELOPMENT REGULATIONS SECTION
 94-304(D)(2)(B)+(C):
  
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720
  
  
  