Plan Review Details - Permit 07050622
Plan Review Stops For Permit 07050622
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-20 Cont ID  
Sent By jwitmer Date 2007-10-20 Time 10:11 Rev Time 1.50
Received By jwitmer Date 2007-10-20 Time 09:53 Sent To  
Notes
2007-10-20 10:28:11BUILDING PLAN REVIEW
 PERMIT: 07050622
 ADD: 540 CLEMATIS
 CONT: KDN CONSTRUCTION
 TEL: (561)662-1002
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLANS INDICATE THIS BUILDING TO BE A TYPE IIB
 UNPROTECTED, UNSPRINKLERED, THIS BUILDING IS
 APPROXIMATELY 3,150 SQ FT. PLEASE INDICATE THE MINIMUM
 BUILDING
 TYPE OF CONSTRUCTION. IF THIS SPACE IS TO BE BUILT OUT
 AS A TYPE IIB THE BEARING WALLS WILL AS WELL AS
 NONBEARING WALLS WILL ALL NEED TO BE FIRE RETARDANT
 TREATED WOOD PLEASE SEE TABLE 601 FOOTNOTE C-II . LOOK
 AT TABLE 503 UNDER MERCANTILE AT A BUILDING TYPE VB,
 THE ALLOWABLE AREA OF 9,000 FOR A SINGLE STORY
 BUILDING. IN THIS CATEGORY THE EXTERIOR AND INTERIOR OF
 THE BUILDING DOES NOT REQUIRE THE FIRE RETARDANT
 TREATED WOOD.
 PLEASE PROVIDE :
 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT WAS
 DESIGNED.NOTE THE BASE CODE IS THE 2004 FBC WITH 2006
 REVISIONS.
 ALSO NOTE TO WHAT LEVEL OF ALTERATION IS BEING
 COMPLETED UNDER THE 2004 FBC EXISTING BUILDING CODE?
 IS THIS A CHANGE IN OCUPANCY?
 B) COMPLIED.
 C)THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE
 503- MERCANTILE & CHAPTER 6, TABLE 601.
 D) COMPLIED.
 E) COMPLIED.
 F) COMPLIED.
 G) SEMI-COMPLIED.SQ. FT. UNDER ROOF (TOTAL) FOR THE
 TOTAL BUILDING NOT TENANT SPACE. TENANT SPACE IS ALSO
 NEEDED AND PROVIDED. THE REQUIEMENT FOR THE TOTAL BLDG
 SQUAREFOOTAGE IS BECAUSE OF THE TYPE II BUILDING
 CLASSIFICATION THE DESIGN PROFESSIONAL HAS INDICATED
 INACTING THE FIRERETARDANT TREATED WOOD. THIS
 BUILDING BEING A ONE STORY BUILDING APPROXIMATELY 3150
 SQ. FT. WILL QUALIFY AS A TYPE V-B.
  
 4) 2ND REQUEST,THE PLANS DO NOT INDICATE WHERE THE
 PROPERTY LINE WOULD BE OR IF THE FRONT DOOR SWINGS IN
 OR OUT OVER THE PROPERTY LINE? AGAIN, IF THE LEVEL OF
 ALTERATION PROVIDED UNDER THE 2004 FBC, AND IF THIS IS
 A CHANGE OF OCCUPANCY IT MAY OR MAY NOT ENACT CERTAIN
 REQUIREMENTS OF THE CODE. 2004 EXISTING BUILDING CODE
 SECTION 303 ALL BUILDING ALTERATIONS WILL BE CLASSIFIED
 TO ACCORDING TO LEVEL OF ALTERATION. CHANGES IN
 OCCUPANCIES MAY OR MAY NOT INACT CODE ISSUES DEPENDING
 ON THE CATEGORY OF OCCUPANCY, SEE 2004 EXISTING
 BUILDING
 CODE IN CHAPTER 8 CHANGE OF OCCUPANCIES.
  
 5) COMPLIED.
  
 6)2ND REQUEST,PLANS INDICATE A RAMP DIRECTLY INSIDE
 THE UNIT WITH NO BOTTOM LANDING.11-4.8.4.(2)
 LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT BE LESS THAN
 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL HAVE NOT LESS
 THAN 72" OF STRAIGHT & LEVEL CLEARENCE. THE PLANS ARE
 MISSING THE BOTTOM LANDING OF 72", DEPENDING ON PART OF
 THE ANSWER TO COMMENT 3A) ANDCOMMENT# 4THIS
 REQUIREMENT MAY NOT HAVE TO BE MET.
  
 7) 2ND REQUEST, PLEASE PROVIDE DOOR WIDTH FOR ALL NEW
 INTERIOR DOORS. 11-4.13.5 DOORWAYS, MINIMUM CLEAR
 WIDTH: DOORWAY SHALL HAVE A MINIMUM CLEAR OPENING OF
 32" WITH THE DOOR OPEN 90 DEGREES, MEASURED BETWEEN THE
 FACE OF THE DOOR AND THE OPPOSITE STOP. THE PLANS
 INDICATE A 32INCH OPENING TO THE RESTROOM THIS WILL
 ONLY WORK IF THE HINGES ARE SWING CLEAR OF OPENING
 TYPE OF HINGE, THE DOOR WHEN OPENED 90 DEGRESS WILL
 SWING CLEAR OF THE DOOR OPENING OTHERWISE THE MINIMUM
 DOOR OPENING SIZE IS A 2'-10" OR 34INCHES.
  
 8) 2ND REQUEST, THE RESTROOM DOES NOT PROVIDE
 DIMENSIONS, NOR IS THE 5'-0" TURNING CIRCLE INDICATED
 FOR THE HANDICAPPED RESTROOM. IT APPEARS THE TOLIET IS
 LOCATED IN THE TURNING RADIUS. 11-4.2.3 WHEELCHAIR
 TURNING SPACE. THE SPACE REQUIRED FOR A WHEELCHAIR TO
 MAKE A 180-DEGREE TURN IS A CLEAR SPACE OF 60 INCHES
 (1525 MM) DIAMETER [SEE FIGURE 3 (A)] OR A T-SHAPED
 SPACE [SEE FIGURE 3 (B)].
  
 9) IS THIS AGAIN A CHANGE IN OCCUPANCY, AND OR A NEW OR
 RECONFIGURED RESTROOM? 11-4.16.2 CLEAR FLOOR SPACE.
 WATER CLOSET.CLEAR FLOOR SPACE FOR WATER CLOSETS NOT IN
 STALLS SHALL COMPLY WITH FIGURE 28 . CLEAR FLOOR SPACE
 MAY BE ARRANGED TO ALLOW EITHER A LEFT-HANDED OR
 RIGHT-HANDED APPROACH.
  
 10) 2ND REQUEST, THE SIDE GRAB BAR IN THE RESTROOM,
 PLEASE DIMENSION THE SIZE AND LOCATION OF THE GRAB BAR.
 11-4.16.4 GRAB BARS.PLEASE SEE FIGURE# 29 FOR LOCATION
 AND THE MINIMUM SIZE REQUIREMENTS FOR GRAB BARS. THE
 SIDE GRAB BAR IS TO BE A MINIMUM OF 42 INCHES LONG AND
 THE LEADING EDGE TO BE AT 54 INCHES FROM THE CORNER.
 THE BACK BAR ALSO IS NOT DIMENSIONED FOR LENGTH WHICH
 WOULD BE 36" AND ONE END OF THE BACK GRAB BAR BEING 12
 INCHES OF CENTER OF THE WATER CLOSET BEING SET UP FOR A
 LEFTOR RIGHT HANDED SIDE APPROACH, SEE FIGURE 29 FOR
 CLARIFICATION.
 GRAB BARS FOR WATER CLOSETS NOT LOCATED IN STALLS SHALL
 COMPLY WITH SECTION 11-4.26 AND FIGURE 29 . THE GRAB
 BAR BEHIND THE WATER CLOSET SHALL BE 36 INCHES (915 MM)
 MINIMUM.
  
 11) COMPLIED.
  
 12)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-28 Cont ID  
Sent By jwitmer Date 2007-06-28 Time 18:37 Rev Time 1.11
Received By jwitmer Date 2007-06-28 Time 18:37 Sent To  
Notes
2007-06-28 19:00:38BUILDING PLAN REVIEW
 PERMIT: 07050622
 ADD: 540 CLEMATIS
 CONT: KDN CONSTRUCTION
 TEL: (561)662-1002
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLANS INDICATE THIS BUILDING TO BE A TYPE IIA
 UNPROTECTED, UNSPRINKLERED, THIS BUILDING IS
 APPROXIMATELY 3,150 SQ FT. PLEASE INDICATE THE MINIMUM
 BUILDING
 TYPE OF CONSTRUCTION. IF THIS SPACE IS TO BE BUILT OUT
 AS A TYPE IIA THE BEARING WALLS WILL NEED TO BE 1 HR
 RATED AS WELL AS THE CEILING ROOF ASSEMBLY.PLEASE
 PROVIDE :
 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 ALSO NOTE TO WHAT LEVEL OF ALTERATION IS BEING
 COMPLETED UNDER THE 2004 FBC EXISTING BUILDING CODE? B)
 THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3. IS THIS A CHANGE OF
 OCCUPANCY?
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THEOCCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT
 G) SQ. FT. UNDER ROOF (TOTAL) FOR THE TOTAL BUILDING
 NOT TENANT SPACE.
  
 4)THE PLANS DO NOT INDICATE WHERE THE PROPERTY LINE
 WOULD BE OR IF THE FRONT DOOR SWINGS IN OR OUT OVER THE
 PROPERTY LINE?
  
 5) THE PLANSALSO INDICATE A HASHED LINE IN FRONT OF THE
 UNIT, IS THIS AAWNING? REQUIRES A SEPERATE PERMIT.
  
 6) PLANS INDICATE A RAMP DIRECTLY INSIDE THE UNIT WITH
 NO BOTTOM LANDING.11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL HAVE NOT LESS
 THAN 72" OF STRAIGHT & LEVEL CLEARENCE.
  
 7) PLEASE PROVIDE DOOR WIDTH FOR ALL NEW INTERIOR
 DOORS. 11-4.13.5 DOORWAYS, MINIMUM CLEAR WIDTH: DOORWAY
 SHALL HAVE A MINIMUM CLEAR OPENING OF 32" WITH THE DOOR
 OPEN 90 DEGREES, MEASURED BETWEEN THE FACE OF THE DOOR
 AND THE OPPOSITE STOP.
  
 8)HANDICAPPED ESTROM THE TOLIET IS LOCATED IN THE
 TURNING RADIUS. 11-4.2.3 WHEELCHAIR TURNING SPACE. THE
 SPACE REQUIRED FOR A WHEELCHAIR TO MAKE A 180-DEGREE
 TURN IS A CLEAR SPACE OF 60 INCHES (1525 MM) DIAMETER
 [SEE FIGURE 3 (A)] OR A T-SHAPED SPACE [SEE FIGURE 3
 (B)].
  
 9) 11-4.16.2 CLEAR FLOOR SPACE. WATER CLOSET.CLEAR
 FLOOR SPACE FOR WATER CLOSETS NOT IN STALLS SHALL
 COMPLY WITH FIGURE 28 . CLEAR FLOOR SPACE MAY BE
 ARRANGED TO ALLOW EITHER A LEFT-HANDED OR RIGHT-HANDED
 APPROACH.
  
 10) MISSING THE SIDE GRAB BAR IN THE RESTROOM, PLEASE
 DIMENSION THE SIZE AND LOCATION OF THE GRAB BAR.
 11-4.16.4 GRAB BARS.
 GRAB BARS FOR WATER CLOSETS NOT LOCATED IN STALLS SHALL
 COMPLY WITH SECTION 11-4.26 AND FIGURE 29 . THE GRAB
 BAR BEHIND THE WATER CLOSET SHALL BE 36 INCHES (915 MM)
 MINIMUM.
  
 11) PLEASE INDICATE COMPLIANCE WWITH COUNTERS AND BARS,
 11-5.2 COUNTERS AND BARS.
 WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34
 INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION
 OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN
 LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH
 SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT
 ACCESSIBLE TABLES WITHIN THE SAME AREA.
  
 11-5.6 TABLEWARE AND CONDIMENT AREAS.
 SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR
 TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES
 SHALL BE INSTALLED TO COMPLY WITH SECTION 11-4.2 (SEE
 FIGURE 54 ).
  
 12)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-06 Cont ID  
Sent By dpalmer Date 2007-10-06 Time 18:38 Rev Time 0.00
Received By dpalmer Date 2007-10-06 Time 18:38 Sent To  
Notes
2007-10-06 18:39:512007-10-06 18:39:51
  
 *** DENIED 2ND REVIEW ***
  
 1) NOTE: PLEASE KNOW WITH RESPECT TO THE
 DESIGNER/ENGINEER OF RECORD RESPONSE COMMENTS WHICH
 SEEM TO CONTEST THIS REVIEWER NOTES. SEVERAL OF THE
 ENGINEER RESPONSE NOTES MENTIONS PLANS DATED FEBRUARY
 07, HOWEVER THE PREVIOUS REVIEW WAS DONE ON PLANS
 SUBMITTED WHICH WERE SIGNED, DATED AND SEALED ON
 3/19/07 BY THE ENGINEER OF RECORD.
 PLEASE KNOW THAT THIS OFFICE/REVIEWER ONLY REVIEWS
 THE PLANS WHICH ARE SUBMITTED WITH THE PERMIT
 APPLICATION.
 THE PLANS SUBMITTED FROM THE PREVIOUS REVIEW WERE
 TURNED INTO THIS OFFICE WERE ALSO SUBMITTED BACK WITH
 THIS RE-SUB AS OLD PLANS.
 PLEASE SEE THE SIGNED, DATED AND SEALED PLANS DATED
 3/19/07 FROM THE ENGINEER WERE THE SAME PLANS
 SUBMITTED. PLEASE CHECK THE PLANS SUBMITTED.
 THE PREVIOUS COMMENTS WERE VALID BASED ON THE PLANS
 SUBMITTED ON THE FIRST REVIEW AS SUBMITTED.
 ** PLEASE SEE THOSE SAME PLANS HAVE HAD SEVERAL OF THE
 PREVIOUS REVIEW COMMENTS *HIGH-LIGHTED*.
 EXAMPLE:
 A) PREVIOUS PLANS HAS 65AMP RATED CONDUCTORS ON 100AMP
 DISCONNECTS W/70A OCP.
 B) PREVIOUS PLANS HAVE 244AMPS OF LOAD SHOWN ON A
 300AMP PANEL BEING FED FROM A 100AMP DISCONNECT WITH
 70AMP FUSES.
 C) PREVIOUS PLANS HAD EQUIPMENT/REFRIGERATOR AT FRONT
 DOOR ON GENERAL PURPOSE CIRCUITS.
  
 ** THIS REVIEWER HAS STATED ON ALL REVIEWS PERFORMED BY
 THIS OFFICE THAT IF THERE EVER ANY QUESTIONS, OR
 COMMENTS TO PLEASE DO NOT HESITATE IN CONTACTING THIS
 OFFICE/OR REVIEWER. AT THIS TIME WE MAY GO OVER
 COMMENTS OR EVEN IF A MEETING IS NEEDED WE CAN SCHEDULE
 A TIME TO GO OVER REVIEW COMMENTS.
  
 **THIS HAS NOT CHANGED, AND ONCE AGAIN IF THERE ARE ANY
 ITEMS WHICH NEED TO BE GONE OVER PLEASE CALL.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #2. PLEASE
 SUBMIT LIGHTING PERFORMANCE CALCULATIONS. MAY NOT USE
 METHOD *A* WHOLE BUILDING CALCULATION FOR THE TENANT
 BUILD OUT.
 PLEASE SEE COMMENTS FROM MECHANICAL REVIEWER. PLEASE
 SEE 13-415.2 AND TABLES.
 PLEASE SEE LIGHTING CONTROLS STILL REQUIRED PER
 13-415.1.ABC.1.1, .1.2. PLEASE SEE THE ONLY DEVICE IS
 THE OS SHOWN AT FRONT DOOR WHICH DOES NOT PROVIDE
 NEEDED COVERAGE IN THE REAR OF SPACE. PLEASE ALSO SEE
 THIS DOES NOT THE MEET THE REQUIREMENTS FOR SEPARATE
 SPACE CONTROLS FOR AREAS WHICH HAVE FLOOR TO CEILING
 HEIGHT PARTITIONS.
 PLEASE ADJUST DEVICES, TIMES FOR DEVICES TO BE CHOSEN.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #3 WITH
 RESPECT TO RISER AND TO BE SURE AND COORDINATE ALL WITH
 THE ACTUAL EXISTING RISER. THE LAST SETS OF REVISED
 ELECTRICAL PLANS SUBMITTED TO THE CITY FOR PERMITTING
 AND REVISIONS INDICATES LARGER MAINS BEING TAPPED FORM
 THE EXISTING MAIN AND GUTTER.
 PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON THE
 EXISTING SERVICE WITH NEW LOADS BEING ADDED.(LOAD
 CALCULATIONS SUBMITTED, HOWEVER NOTE TO REMAIN DUE TO
 KNOWN ADJUSTMENTS WHICH WILL BE NEEDED).
 FOR EXAMPLE, ALL OTHER TENANT MAINS ARE SHOWN AT
 100AMPS, YET THERE IS ANOTHER RESTAURANT/ SANDWICH SHOP
 WHICH HAS A LARGER SERVICE MAIN THAN 100AMPS. PLEASE
 SEE 240, 310, 408, 230, 215.5, 220 ETC. PLEASE ADJUST
 ALL.
 FBC 106.3.5.1.2
  
 4) NOTE: PLEASE CLARIFY WATER HEATER LOAD AS THE NEW
 CODE REQUIRED STORAGE TYPE WATER HEATER LOADS TO BE
 SHOWN AT 125%. THESE ARE NOW CONSIDERED CONTINUOUS
 LOADS.
 PLEASE SEE 422.13
  
 ** AS THERE WILL BE SEVERAL CHANGES, PLEASE BE SURE TO
 GO OVER COMMENTS FROM ALL TRADES WHICH MAY AFFECT THE
 SCOPE OF WORK ALONG WITH OTHER TRADE REVIEWED SHEETS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-08 Cont ID  
Sent By dpalmer Date 2007-06-08 Time 08:19 Rev Time 0.00
Received By dpalmer Date 2007-06-07 Time 20:48 Sent To  
Notes
2007-06-08 08:20:10*** UNSAT ***
  
 1) NOTE:PLEASE STATE ALL OF THE RELEVANT CODES AS
 ADOPTED FROM THE STATE OF FLORIDA AS OF DECEMBER 8TH,
 2006.
 PLEASE LIST THE FOLLOWING AT A MINIMUM ON ELECTRICAL
 SHEETS AS WELL AS ARCHITECTURAL.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70 (NEC).
 2003 NFPA-101 (LS CODE).
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13 FOR COMPLIANCE FOR
 ENERGY CALCULATIONS/PERFORMANCE CALCULATIONS
 13-415.1.AB1.1, 13-415.2.
 PLEASE SEE MISSING LIGHTING CONTROLS AS REQUIRED PER
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 ** AS NO INFORMATION ON SCHEDULING, TYPEOF DEVICES,
 FIXTURES, WATTAGES, OVER RIDES, ETC HAVE BEEN SUBMITTED
 FOR REVIEW, COMMENTS CAN NOT BE MADE AT THIS TIME.
  
 3) NOTE: PLEASE SEE THE SERVICE AS SHOWN CONTAINS A
 NOTE AT THE BOTTOM WHICH INDICATES *EXISTING* YET THE
 RISER AS SHOWN INDICATES SOME ITEMS AS *NEW*?? PLEASE
 CLARIFY ALL SERVICE EQUIPMENT AS SHOWN. PLEASE SEE THE
 PANEL SCHEDULE SHOWS THIS AS A 300AMP PANEL WITH 244
 AMP LOAD, YET THE PANEL IS ONLY BEING FED W/ A 2-POLE
 70AMP BREAKER WITH CONDUCTORS WHICH ARE ONLY RATED AT
 65AMPS??
 PLEASE SEE THE LOAD ON PANEL AS NOTED ABOVE SHOWN AT
 244AMPS, YET THE RISER LOAD CALCULATIONS ARE SHOWN
 SUBSTANTIALLY LESS FOR THIS SAME UNIT??
 PLEASE SEE THERE ARE SEVERAL ITEMS INCORRECT WITH THIS
 RISER AND NEW FEED TO PANEL.
 PLEASE SEE 240, 310, 408, 230, 215.5 ETC.
 PLEASE ADJUST ALL.
 FBC 106.3.5.1.2
  
 4) NOTE: PLEASE SEE ALL BREAKERS ON THE PANEL SCHEDULE
 ARE 1-POLE BREAKERS? HOW IS THIS POSSIBLE FOR THE
 240/220/208 VOLT UNITS.
 IS ALL EQUIPMENT ON SINGLE POLE BREAKERS?
 PLEASE SEE NEC.
  
 5) NOTE: PLEASE SEE THE AHU SEEMS TO BE SHOWN WITH 10KW
 LOAD YET THE CONDUCTOR AND BREAKER SIZE IS NOT
 SUFFICIENT PER CODE.
 PLEASE SEE 240.4, 310.16, 424.3B.
  
 6) NOTE: PLEASE CLARIFY WATER HEATER AS PLANS INDICATES
 A STORAGE TYPE UNIT AND PANEL SCHEDULE INDICATES
 INSTANT TYPE HEATERS.
 PLEASE SEE 422.13 AND THE FOLLOWING COMMENT FOR LOAD
 CALCULATIONS.
  
 7) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON
 THE NEW PROPOSED LOAD FOR THIS TENANT SPACE AND FOR THE
 ENTIRE SERVICE FOR EXISTING LOADS AND NEW LOADS BEING
 ADDED TO SERVICE. THE LOAD AS SHOWN ON THE RISER LOAD
 CALCULATIONS IS NOT POSSIBLE.
 PLEASE SEE NEC 220 (ALL), 215.3, 230.42.
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AT 125%
  
 8) NOTE: PLEASE SEE THE SHOW WINDOW RECEPTACLE IS BEING
 SHOWN ON THE GENERAL RECEPTACLE CIRCUIT WHICH IS NOT
 PERMITTED.
 210.62,220.14, 220.44.
  
 9) NOTE: PLEASE SEE THE PLANS INDICATE SOME SORT OF
 REFRIGERATOR AT THE FRONT ENTRANCE WHICH IS BEING SHOWN
 ON THE SAME GENERAL RECEPTACLE CIRCUIT AS SHOW WINDOW
 ETC. PLEASE SEE THE VA ON UNIT NEEDS TO BE VERIFIED AS
 THE CIRCUIT MOST LIKELY WILL NEED TO BE DEDICATED.
 PLEASE KNOW AS THE LOADS ARE NOT SHOWN, DETERMINATION
 CAN NOT BE DONE AT THIS TIME.
 PLEASE SEE 430, 422, 422, 220 ETC.
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE 210.8B2 FOR ALL REQUIRED GFI
 PROTECTED CIRCUITS/RECEPTACLES ON PLANS IN KITCHEN FOOD
 PREP AREAS AND THE LIKE.
  
 11) NOTE: PLEASE SEE VALUE FOR SCOPE OF WORK IS TO
 INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST
 ETC., EVEN IF ANY OF THESE ARE OWNER SUPPLIED. PLEASE
 SEE FBC 108.3.
  
 12) NOTE: PLEASE SEE CU IS BEING SHOWN ON 1-POLE
 CIRCUIT?
  
 13) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 COORDINATE WITH THE SUBMITTED PANEL SCHEDULE. PLEASE
 SEE SOME ELECTRICAL ITEMS NOT SHOWING CIRCUITS. PLEASE
 ALSO SEE 700.12F FOR CIRCUITING OF EM/EXT LTS.
  
 14) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER ON
 PLANS/ TITLE BLOCKS.
 FAC 61G1-16.004 FBC 106.1.2
  
 15) NOTE: PLEASE SEE THE PANEL SCHEDULE INDICATES
 SEVERAL ITEMS BEING EXISTING, HOWEVER AS THIS IS A NEW
 BUILD-OUT FROM PREVIOUS SHELL THIS IS NOT POSSIBLE.
 PLEASE ADJUST. 408.4.
 FBC 106.3.5.1.2
  
  
 ** PLEASE KNOW AT THIS TIME AS SOME OF THE INSTALLATION
 IS NOT CLEAR, THERE MAY BE COMMENTS IF THE INSTALLATION
 CHANGES AND/OR PERMIT APPLICATION CHANGES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-08 07:35:12IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-10-24 Cont ID  
Sent By mwennerg Date 2007-10-24 Time 13:11 Rev Time 0.00
Received By mwennerg Date 2007-10-24 Time 13:11 Sent To  
Notes
2007-10-24 13:33:11***DENIED***
  
 SOME OF THE PREVIOUS COMMENTS WERE ADDRESSED DIRECTLY
 ON THE PLANS. (SHT A-1) A RESPONSE LETTER (2ND REQUEST)
 WOULD BE HELPFUL AND AS STATED IN THE FIRST REVIEW WILL
 HELP EXPEDITE THE PLAN REVIEW PROCESS.
  
 1) OK
  
 2) OK
  
 3) OK
  
 4) COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MOVE FREQUENTLY AS NECESSARY FOR SAFE OPEARTION.
  
 5) THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES ETC).
  
 6) CLASSIFY THE HAZARD OF CONTENTS OF
 BUILDING/STRUCTURE AS LOW, ORDINARY OR HIGH.
  
 7) OK
  
 8) LOCKS ON EGRESS DOORS SHALL NOT REQUIRE THE USE OF A
 KEY, TOOL OR SPECIAL KNOWLEDGE OR EFFORT OF OPERATION
 FROM THE EGRESS SIDE. (NO DOOR SCHEDULE)
  
 9) OK
  
 10) AN EXIT SIGN LIGHT WITH BATTERY BACK-UP CAPABILITY
 SHALL BE REQUIRED TO DIRECT PERSON(S) FROM THE COOKING
 PREPARATION AREA.
  
 11) SPECIFY THE INTERIOR WALLS AND CEILING FINISH
 MATERIALS IN TERMS OF CLASSA,B OR C.
  
 12) COMMERCIAL COOKING EQUIPMENT TO COMPLY WITH NFPA
 96, 2001 EDITION.
  
 13) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR
 HOOD AND SUPPRESSION SYSTEMS. PLANS INDICATE SEPARATE
 PERMIT FOR FIRE SPRINKLER WHICH PLANS ALSO STATE NOT
 APPLICABLE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By mawillia Date 2007-07-12 Time 09:22 Rev Time 0.00
Received By mawillia Date 2007-07-12 Time 08:45 Sent To  
Notes
2007-07-12 09:18:01*****DENIED*****
  
 DUE TO THE ALTERATION, MODERNIZATION, OR RENOVATION TO
 THIS SITE, THE REQUIREMENTS OF A NEW MERCANTILE
 OCCUPANCY SHALL APPLY.IT SHALL BE SUB-CLASSIFIED AS A
 CLASS C MERCALNTILE (GROSS AREA NOT MORE THAN 3000
 SQUARE FEET).
  
 01.THE SUITE NUMBER SHALL BE INCLUDED WITH NUMERICAL
 ADDRESS IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATION SHALL COMPLY WITH NFPA 241.
  
 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 05.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES).
  
 06.CLASSIFY THE HAZARD OF CONTENTS OF
 BUILDING/STRUCTURE AS LOW, ORDINARY, OR HIGH.
  
 07.DECLARE THE OCCUPANT LOAD IN NUMBER OF PERSONS FOR
 WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE
 REQUIRED.
  
 08.LOCKS ON EGRESS DOORS SHALL NOT REQUIRE THE USE OF
 A KEY, A TOOL, OR SPECIAL KNOWLEDGEOR EFFORT OF
 OPERATION FROM THE EGRESS SIDE.
  
 09.A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN A
 CLASS C MERCANTILE PROVIDED THAT THE 75' TRAVEL
 DISTANCE TO THE EXIT IS NOT EXCEEDED.PLEASE
 DEMONSTRATE
  
 10.AN EXIT SIGN LIGHT, WITH BATTERY BACK-UP
 CAPABILITY, SHALL BE REQUIRED TO DIRECT PERSON(S) FROM
 THE COOKING PREPARATION AREA.
  
 11.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A OR CLASS B.
  
 12.COMMERCIAL COOKING EQUIPMENT SHALL BE ACCORDANCE
 WITH NFPA 96 - 2001 EDITION.
  
 13.SEPARATE PLANS AND PERMIT REQUIRED FOR BOTH THE
 COOKING HOOD INSTALLATION AND THE HOOD'S SUPPRESSION
 SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLANS EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-11-03 Cont ID  
Sent By kstevens Date 2007-11-03 Time 17:07 Rev Time 0.00
Received By kstevens Date 2007-11-03 Time 17:07 Sent To  
Notes
2007-11-03 17:13:22DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT COMMENT NOT COMPLETLY
 ADDRESSED. LENGTHS OF PIPE NOT SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE
 NOTED, BUT COMMENT NOT ADDRESSED. PIPE TYPE NOT
 INDICATED ON LEGEND.
  
 C. OK
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT THIS WILL BE VERIFIED WHEN ALL
 CUT SECTION LENGTHS ARE INDICATED ON THE GAS ISOMETRIC
 RISER DIAGRAM.
  
 E. OK
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE
 MANUF. SPECIFICATION SHEETS FOR ALL GAS APPLIANCES
 INCLUDING THE RTU ARE REQUIRED AND SHALL SHOW A LISTING
 AS WELL AS THE BTU LOAD OF THE APPLIANCE.
  
 G. N/A
 H. N/A
  
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT THE COMMENT IS NOT ADDRESSED.
  
 **********NEW COMMENTS***********
  
 1B. SEDIMENT TRAPS REQUIRED BY SECTION 408.4 SHALL BE
 SHOWN ON THE GAS RISER DIAGRAM.
  
 2B. SHUT OFF VALVES SHALL BE PROVIDED FOR EACH GAS
 APPLIANCE. SECTION 409.5. PLEASE SHOW THE SHUT OFF
 VALVE FOR THE RTU UNIT. ALL SHUT OFF VALVES SHALL BE
 ACCESSIBLE PER SECTION 409.5.
  
 3B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE ONLY AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-11-03 Cont ID  
Sent By kstevens Date 2007-06-20 Time 14:48 Rev Time 0.00
Received By kstevens Date 2007-06-20 Time 14:48 Sent To  
Notes
2007-11-03 14:50:22DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-14 Cont ID  
Sent By adarroug Date 2007-09-14 Time 09:27 Rev Time 0.00
Received By adarroug Date 2007-09-14 Time 09:27 Sent To  
Notes
2007-10-05 17:19:16TO "COMM" BD#22
2007-09-14 09:27:40WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-12 Cont ID  
Sent By mawillia Date 2007-07-12 Time 08:45 Rev Time 0.00
Received By mawillia Date 2007-05-17 Time 15:52 Sent To  
Notes
2007-06-06 15:21:40TO "COMM" BD#55
2007-05-17 15:54:09WAITING FOR "COMM" BD--RESTAURANT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-05 Cont ID  
Sent By rregueir Date 2007-11-05 Time 11:18 Rev Time 0.00
Received By rregueir Date 2007-11-05 Time 07:53 Sent To PC
Notes
2007-11-05 11:18:01REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 NOTE: THERE WAS NO WRITTEN RESPONSE TO PREVIOUS
 MECHANICAL REVIEW COMMENTS IN THIS SUBMITTAL PACKAGE.
 PLANS WILL BE REVIEWED TO DETERMINE IF PREVIOUS
 COMMENTS WERE ADDRESSED.
  
 1. NOT ADDRESSED. INFORMATION IS STILL MISSING ON
 PLANS.
  
 2. NOT ADDRESSED.
  
 3. NO VENTILATION (OUTSIDE AIR) CALCULATIONS OR
 INFORMATION PROVIDED. OCCUPANCY AND OCCUPANT LOAD FOR
 PURPOSES OF VENTILATION SHALL BE DETERMINED IN
 ACCORDANCE WITH FBC,M TABLE 403.3 PROVIDE CALCULATIONS
 SHOWING OCCUPANCY, OCCUPANT LOAD, O.A. REQUIRED AND
 O.A. PROVIDED. ALSO, PROVIDE BATHROOM EXHAUST FAN
 INFORMATION ON EQUIPMENT SCHEDULE SHOWING MAKE/MODEL,
 CFM AND MEANS OF CONTROL. ALSO SHOW DISCHARGE LOCATION
 OF BATH EXHAUST IN ACCORDANCE WITH FBC,M 401.5. NOTE:
 BATH EXHAUST FAN IS NOT SHOWN ON ELECTRICAL PLANS. HOW
 WILL THIS FAN BE POWERED?
  
 4. AIR BALANCE SCHEDULE FOR THE SPACE HAS NOT BEEN
 PROVIDED. PLEASE READ PREVIOUS COMMENT AND PROVIDE ALL
 REQUESTED INFORMATION TO SHOW COMPLIANCE WITH THE CODE
 SECTIONS AS PREVIOUSLY REFERENCED. NOTE: IT IS
 PROHIBITED TO HAVE RETURN AIR IN THE KITCHEN FOR
 NON-DEDICATED KITCHEN HVAC SYSTEMS IN ACCORDANCE WITH
 FBC,M 407.1.
  
 5. NOT ADDRESSED. NO INFORMATION PROVIDED. SEE PREVIOUS
 REVIEW COMMENT.
  
 6. WITHOUT A WRITTEN RESPONSE, THE FOLLOWING IS NOTED
 BASED ON INFORMATION ON PLANS AND SUBMITTALS:
 A) PLAN INDICATES A/C IS NEW AND EXISTING. ONLY ONE
 SYSTEM IS SHOWN ON PLAN. ARE THERE TWO SYSTEMS? ONLY
 ONE IS LISTED ON EQUIPMENT SCHEDULE.
 B) FLOOR PLAN SHOWS A ?CU #5 ON ROOF.? IS THIS A
 ROOFTOP PACKAGE UNIT AS INDICATED BY EQUIPMENT SCHEDULE
 AND MANUAL J FORM OR A SPLIT SYSTEM WITH AHU AND CU? IS
 THIS THE NEW SYSTEM OR THE EXISTING SYSTEM?
 C) THE RTU LISTED ON PLAN DOES NOT MATCH THE RTU LISTED
 ON MANUAL J FORM.
 D) THE GAS RISER DIAGRAM SHOWS AN EXISTING 4 TON RTU ON
 ROOF. THIS DOES NOT MATCH ANY OF THE OTHER SUPPLIED
 INFORMATION. THERE IS ALSO A GAS LINE SHOWN GOING TO
 THE RTU FOR HEAT WHILE THE ELECTRICAL PLAN SHOWS A 5KW
 HEAT STRIP.
 E) ELECTRICAL PLAN SHOWS SERVICE FOR ONE AHU AND ONE CU
 FOR ONE SPLIT SYSTEM. WHERE IS THE 2ND SYSTEM ON
 ELECTRICAL PLANS? THE LETTER FROM A & J TECHNOLOGIES,
 INC. INDICATES THAT A NEW UNIT IS SIZED TO PROVIDE
 ADDITIONAL COOLING REQUIRED BY THE KITCHEN. IS THE ONE
 EXISTING SYSTEM BEING REPLACED OR IS THIS AN ADDITIONAL
 SYSTEM? IN ANY EVENT, THE ELECTRICAL SHOWS ONLY ONE
 SPLIT SYSTEM. THE ACTUAL NATURE OF THE WORK TO BE
 PERFORMED CAN NOT BE DETERMINED AT THIS TIME.
 F) THE LETTER INDICATES THAT A & J TECHNOLOGIES HAS
 DESIGNED THIS A/C SYSTEM. IN ORDER TO PERFORM DESIGN OF
 THIS COMMERCIAL SYSTEM, THEY ARE REQUIRED TO BE
 LICENSED AS AN ENGINEERING BUSINESS UNDER FS 471 OR AS
 A MECHANICAL CONTRACTOR UNDER FS 489. PROVIDE ALL
 RELEVANT LICENSE INFORMATION FOR THIS COMPANY. SEE FBC
 105.3.1.2(4).
  
 7. AIRFLOW ON SCHEDULE NOW SHOWS 1300 CFM, BUT WE STILL
 DON?T KNOW THE CFM OF THE 6 INCH DROP IN THE KITCHEN.
 THIS NEEDS TO BE ADJUSTED BASED ON WHAT EQUIPMENT IS
 ACTUALLY BEING USED AND WHAT IS REQUIRED BASED ON THE
 MANUAL J SUBMITTED.
  
 8. NOTE 9 HAS BEEN REMOVED. THERE IS NO LONGER A
 CONFLICT. HOWEVER, NOTE 4 NOW STATES 1\ INCH R-6 DUCT.
 GENERALLY 1 ? INCH IS REQUIRED TO ACHIEVE R-6. PLEASE
 CORRECT NOTE OR PROVIDE DUCT MANUFACTURER?S SUBMITTAL
 TO VERIFY THIS INFORMATION.
  
 9 AND 10. NO INFORMATION WAS PROVIDED REGARDING THE
 COMMERCIAL KITCHEN EXHAUST SYSTEM OTHER THAN A NOTE FOR
 CFM ON HE MANUAL J FORM. PROVIDE INFORMATION FOR A
 COMPLETE COMMERCIAL KITCHEN EXHAUST SYSTEM,
 DEMONSTRATING COMPLIANCE WITH FBC,M SECTIONS 505
 THROUGH 509.
  
 11. THIS COMMENT STILL STANDS AS SIGNIFICANT
 INFORMATION IS STILL MISSING.
  
 ENERGY CALCULATIONS: METHOD A COMPLIANCE FORM IS NOT
 AVAILABLE FOR THIS PROJECT AS THIS IS NOT A WHOLE
 BUILDING. SHOW COMPLIANCE WITH MINIMUM PRESCRIPTIVE
 REQUIREMENTS FOR ALL NEW COMPONENTS BEING INSTALLED IN
 ACCORDANCE WITH FBC 13-400.0.C.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-16 Cont ID  
Sent By rregueir Date 2007-06-16 Time 11:45 Rev Time 0.00
Received By rregueir Date 2007-06-16 Time 10:11 Sent To  
Notes
2007-06-16 11:44:25------------------DENIED--------------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
  
 1. PLEASE SHOW SIZE OF OUTSIDE AIR DUCT FROM 12X12
 O.A.I. TO R/A PLENUM. ALSO, PLEASE SHOW CFM OF 6" DROP
 IN BACK OF SPACE. FBC 106.1.1.
  
 2. SUPPLY TRUNK LINE SHOWS ONE TRANSITION FROM 1/12 TO
 12/10. IS THE TRUNK LINE TO REMAIN THAT SIZE FOR THE
 REMAINING 3 DROPS? FBC 106.1.2.
  
 3.PLEASE SHOW VENTILATION CALCULATIONS WHICH
 DEMONSTRATE COMPLIANCE WITH FBC,M 403.3. ALSO, BATHROOM
 EXHAUST IS ALSO REQUIRED BY THIS SECTION. PLEASE SHOW
 MEANS OF EXHAUST, CFM AND DISCHARGE LOCATION.
  
 4. PLEASE SHOW AN AIR BALANCE SCHEDULE INCLUDING
 SUPPLY, RETURN, OUTSIDE AIR, BATHROOM EXHAUST, KITCHEN
 EXHAUST WITH MAKE-UP AIR TO SHOW PRESSURIZATION OF
 SPACE PER FBC 13-409.1.ABC.2 AND COMPLIANCE WITH
 KITCHEN SPACE REQUIREMENTS OF 13-409-1.ABC 3.6.1.
  
 5.PLEASE SHOW MEANS/LOCATION OF CONDENSATE DISPOSAL IN
 COMPLIANCE WITH FBC,M 307.2 (ALL SECTIONS) INCLUDING
 SECONDARY/AUXILIARY DRAIN PROTECTION PER 307.2.3.
  
 6. ELECTRICAL PLAN INDICATES A/C EQUIPMENT IS EXISTING,
 BUT SCOPE OF WORK AS DESCRIBED ON PERMIT APPLICATION
 STATES "SPACE IS CURRENTLY GUTTED."ALSO, HVAC NOTE #6
 SUGGESTS A/C EQUIPMENT IS NEW, NOT EXISTING. WHICH ONE
 IS CORRECT? FBC 106.1.1.
  
 7. EQUIPMENT SCHEDULE SHOWS INDOOR AIRFLOW AT 1000 CFM
 BUT FLOOR PLAN SHOWS 1300 CFM, NOT INCLUDING THE 6"
 DROP WHICH DOESN'T SHOW CFM. PLEASE SHOW CORRELATION
 BETWEEN SCHEDULE AND FLOOR PLAN.
  
 8. HVAC NOTE #4 IS IN CONFLICT WITH NOTE #9. PLEASE
 CLARIFY.
  
 9. SCOPE OF WORK ON PERMIT APPLICATION INDICATES GAS
 AND KITCHEN EQUIPMENT. PLEASE SHOW ALL VENTS AND
 KITCHEN EXHAUST PER FBC 106.3.5.1.4. ALSO, A COMMERCIAL
 KITCHEN GREASE EXHAUST VENTILATION SYSTEM W/ AUTOMATIC
 FIRE SUPPRESSION SYSTEM IS REQUIRED PER FBC,M 507.2.1
 AND 509.1.
  
 10. PLEASE SEE FBC,M 507.9 FOR CLEARANCE REQUIREMENTS
 RELATED TO TYPE I KITCHEN HOODS INCLUDING REQUIREMENTS
 FOR WALL SURFACES ADJASCENT TO THE HOOD AND COOKING
 EQUIPMENT.
  
 11. SIGNIFICANT INFORMATION IS MISSING FROM PLANS TO
 SHOW A CODE COMPLIANT BUILDING/SPACE AT THIS TIME.
 ADDITIONAL COMMENTS ARE POSSIBLE BASED ON THE
 ADDITIONAL INFORMATION WHEN IT IS PROVIDED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-11-03 Cont ID  
Sent By kstevens Date 2007-11-03 Time 16:21 Rev Time 0.00
Received By kstevens Date 2007-11-03 Time 16:21 Sent To  
Notes
2007-11-03 17:07:29DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW. THE COMMENT NUMBER SHALL
 REMAIN THE SAME AS 1ST REVIEW:
  
 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT.
 OF BUSINESS REGULATION, (DBR), DIVISION OF HOTEL AND
 RESTAURANT FOOD SERVICE FOR REVIEW. A MINIMUM OF TWO
 STAMPED PLANS WITH "TWO PAGE WORKSHEETS" ATTATCHED TO
 STAMPED PAGE SHALL BE SUBMITTED FOR REVIEW TO CITY WPB.
 SECTION 102.2.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 2. THE GREASE INTERCEPTOR SHALL BE SIZED BY
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO,
 (561) 822-2272,[email protected] OR CALVIN WILLIAMS,
 (561) 822-2284 [email protected]. THEIR FAX NUMBER IS
 (561) 822-2287. PLEASE INDICATE THEIR DETERMINATION
 WHEN RESUBMITTING. ARTICLE III SECTION 90-124. PLEASE
 SUBMIT A DETAIL FOR THE GREASE INTERCEPTOR. (SEE
 ATTACHED SHEET SHOWING WPB UTILITY STANDARD FOR
 INTERCEPTORS).
 ****RESPONSE NOTED, BUT THE GREASE INTERCEPTOR IS STILL
 SHOWN ON THE PLANS. ALSO IF THE GREASE INTERCEPTOR IS
 TO BE WAIVED, THEN AS REQUIRED A SAMPLE POINT SHALL BE
 INSTALLED ON THE GREASE LINE PRIOR TO CONNECTING INTO
 THE SANITARY DRAIN AND THE GREASE INTERCEPTOR SHOULD BE
 DELETED FROM THE RISER DIAGRAM.
  
 3. ALL SHEETS. THE ADDRESS OF THE ARCHITECT OF RECORD
 DOES NOT REFLECT THE ADDRESS RECORDED ON THE STATE OF
 FLORIDA DBPR WEBSITE. (SEE ATTACHED SHEET). PLEASE
 UPDATE THE DBPR WEBSITE OR THE TITLE BLOCKS ON EACH
 SHEET SO THE ADDRESS CORRELATES. FAC 61G1-16.004(1) &
 FS 481-2055.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED ON ALL
 SHEETS WITH THE ARCHITECT FIRM TITLE BLOCK. ALL SHEETS
 SHALL SHOW THE CORRECT ADDRESS.
  
 4. OK
 5. OK
  
 6. INDICATE CODE REFERENCES THAT THE PLANS HAVE BEEN
 DESIGNED TO. FBC-2004 W/2006 AMENDMENTS MINIMUM.
 ****RESPONSE NOTED, BUT THE CODE ADOPTED IS NOT 2007
 BUILDING CODE. PLEASE CORRECT CODE REFERENCE.
  
 7. SHT A-1 TOILET ROOM. THE TURNING AREA SHALL BE
 UNOBSTRUCTED AND THE TOILET SHALL NOT BE IN THE TURNING
 AREA. SECTION 11-4.22.3.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. REMOVING
 THE TURNING AREA IS NOT A CORRECT RESPONSE TO SHOW
 COMPLIANCE. PLEASE SHOW THE REQUIRED TURNING AREA AND
 THE TOILET SHALL NOT BE IN THE TURNING AREA.
  
 8. SUBMIT A DETAIL FOR THE TOILET ROOM SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22
 WITH ALL SUBSECTIONS. THE DETAIL SHALL SHOW THE FLOOR
 PLAN AND ELEVATIONS WITH ALL REQUIRED MEASUREMENTS. THE
 W/C SHALL BE 18" OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE, AND THE LAV SHALL BE A MINIMUM 15" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE. SEE FIGS 28 &
 29.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 ___FOR THE W/C:
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS
 C. 11-4.16.5 FLUSH CONTROLS
 D. 11-4.16.6 DISPENSERS
 ___FOR THE LAV:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
  
 9. SUBMIT A FINISH SCHEDULE FOR THE TOILET ROOM SHOWING
 COMPLIANCE WITH SECTIONS 1210.1 & 1210.2. WALLS WITHIN
 2 FEET OF THE WATER CLOSET SHALL BE A SMOOTH, HARD AND
 NONABSORBENT SURFACE.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 10. SHT A-2 THE GREASE RISER DIAGRAM DOES NOT REFLECT
 THE FIXTURE LAYOUT ON THE FLOOR PLAN. PLEASE SHOW A
 PIPING LAYOUT ON THE FLOOR PLAN AND THE GREASE RISER
 ISOMETRIC DIAGRAM SHALL REFLECT THE PIPING LAYOUT.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 11. SHT A-2 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 CONNECT TO THE BUILDING DRAIN. SHOW THE CONNECTION FOR
 THE BRANCH LINE TO THE BUILDING DRAIN . SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 12. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ATTESTORS, (REQD BY SECTIONS
 604.9). SECTION 106.3.5.1.3(3)(8)(10)(13). ****RESPONSE
 NOTED, BUT COMMENT NOT ADDRESSED.
  
 13. SUBMIT A WATER HEATER DETAIL SHOWING COMPLIANCE
 WITH SECTIONS 503.1, 504.6.1 & 607.3.2 (THERMAL
 EXPANSION CONTROL).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE
 REQUIREMENT FOR SECTION 503.1 IS A SHUT OFF VALVE FOR
 WATER HEATER. THE VALVE AS SHOWN WILL SHUT OFF MORE
 THAN THE WATER HEATER. THE PLACE OF DISPOSAL FOR THE
 T&P VALVE DISCHARGE LINE IS NOT INDICATED, NOR IS THE
 EMERGENCY PAN DRAIN LINE TERMINATION POINT.
  
 14. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 TO THE SPACE. SECTION 608.13.2. PLEASE INDICATE ON THE
 PLANS.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO
 REFERENCE TO THE RPZV BACKFLOW IS FOUND ON SHT A-1.
  
 15. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT COMMENT NOT COMPLETLY
 ADDRESSED. LENGTHS OF PIPE NOT SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE
 NOTED, BUT COMMENT NOT ADDRESSED. PIPE TYPE NOT
 INDICATED ON LEGEND.
  
 C. OK
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT THIS WILL BE VERIFIED WHEN ALL
 CUT SECTION LENGTHS ARE INDICATED ON THE GAS ISOMETRIC
 RISER DIAGRAM.
  
 E. OK
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE
 MANUF. SPECIFICATION SHEETS FOR ALL GAS APPLIANCES
 INCLUDING THE RTU ARE REQUIRED AND SHALL SHOW A LISTING
 AS WELL AS THE BTU LOAD OF THE APPLIANCE.
  
 G. N/A
 H. N/A
  
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT THE COMMENT IS NOT ADDRESSED.
  
 **********NEW COMMENTS***********
  
 1B. SEDIMENT TRAPS REQUIRED BY SECTION 408.4 SHALL BE
 SHOWN ON THE GAS RISER DIAGRAM.
  
 2B. SHUT OFF VALVES SHALL BE PROVIDED FOR EACH GAS
 APPLIANCE. SECTION 409.5. PLEASE SHOW THE SHUT OFF
 VALVE FOR THE RTU UNIT. ALL SHUT OFF VALVES SHALL BE
 ACCESSIBLE PER SECTION 409.5.
  
 3B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE ONLY AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By kstevens Date 2007-06-20 Time 06:38 Rev Time 0.00
Received By kstevens Date 2007-06-19 Time 12:46 Sent To  
Notes
2007-06-20 07:23:18DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT.
 OF BUSINESS REGULATION, (DBR), DIVISION OF HOTEL AND
 RESTAURANT FOOD SERVICE FOR REVIEW. A MINIMUM OF TWO
 STAMPED PLANS WITH "TWO PAGE WORKSHEETS" ATTATCHED TO
 STAMPED PAGE SHALL BE SUBMITTED FOR REVIEW TO CITY WPB.
 SECTION 102.2.1.
  
 2. THE GREASE INTERCEPTOR SHALL BE SIZED BY
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO,
 (561) 822-2272,[email protected] OR CALVIN WILLIAMS,
 (561) 822-2284 [email protected]. THEIR FAX NUMBER IS
 (561) 822-2287. PLEASE INDICATE THEIR DETERMINATION
 WHEN RESUBMITTING. ARTICLE III SECTION 90-124. PLEASE
 SUBMIT A DETAIL FOR THE GREASE INTERCEPTOR. (SEE
 ATTACHED SHEET SHOWING WPB UTILITY STANDARD FOR
 INTERCEPTORS).
  
 3. ALL SHEETS. THE ADDRESS DOES NOT REFLECT THE ADDRESS
 RECORDED ON THE STATE OF FLORIDA DBPR WEBSITE. (SEE
 ATTACHED SHEET). PLEASE UPDATE THE DBPR WEBSITE OR THE
 TITLE BLOCKS ON EACH SHEET SO THE ADDRESS CORRELATES.
 FAC 61G1-16.004(1) & FS 481-2055.
  
 4. SHT A-1 EQUIPMENT SCHEDULE ITEM K11 NOT SHOWN ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1.
  
 5. INDICATE THE OCCUPANCY LOAD AND SEATING ON THE
 PLANS. SECTIONS 1004.3 & 1004.7.
  
 6. INDICATE CODE REFERENCES THAT THE PLANS HAVE BEEN
 DESIGNED TO. FBC-2004 W/2006 AMENDMENTS MINIMUM.
  
 7. SHT A-1 TOILET ROOM. THE TURNING AREA SHALL BE
 UNOBSTRUCTED AND THE TOILET SHALL NOT BE IN THE TURNING
 AREA. SECTION 11-4.22.3.
  
 8. SUBMIT A DETAIL FOR THE TOILET ROOM SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22
 WITH ALL SUBSECTIONS. THE DETAIL SHALL SHOW THE FLOOR
 PLAN AND ELEVATIONS WITH ALL REQUIRED MEASUREMENTS. THE
 W/C SHALL BE 18" OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE, AND THE LAV SHALL BE A MINIMUM 15" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE. SEE FIGS 28 &
 29.
  
 9. SUBMIT A FINISH SCHEDULE FOR THE TOILET ROOM SHOWING
 COMPLIANCE WITH SECTIONS 1210.1 & 1210.2. WALLS WITHIN
 2 FEET OF THE WATER CLOSET SHALL BE A SMOOTH, HARD AND
 NONABSORBENT SURFACE.
  
 10. SHT A-2 THE GREASE RISER DIAGRAM DOES NOT REFLECT
 THE FIXTURE LAYOUT ON THE FLOOR PLAN. PLEASE SHOW A
 PIPING LAYOUT ON THE FLOOR PLAN AND THE GREASE RISER
 ISOMETRIC DIAGRAM SHALL REFLECT THE PIPING LAYOUT.
 SECTION 106.1.1.
  
 11. SHT A-2 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 CONNECT TO THE BUILDING DRAIN. SHOW THE CONNECTION FOR
 THE BRANCH LINE TO THE BUILDING DRAIN . SECTION
 106.1.1.
  
 12. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ATTESTORS, (REQD BY SECTIONS
 604.9). SECTION 106.3.5.1.3(3)(8)(10)(13).
  
 13. SUBMIT A WATER HEATER DETAIL SHOWING COMPLIANCE
 WITH SECTIONS 503.1, 504.6.1 & 607.3.2 (THERMAL
 EXPANSION CONTROL).
  
 14. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 TO THE SPACE. SECTION 608.13.2. PLEASE INDICATE ON THE
 PLANS.
  
 15. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-06-11 Cont ID  
Sent By mflis Date 2007-06-11 Time 16:25 Rev Time 0.00
Received By mflis Date 2007-06-11 Time 16:25 Sent To  
Notes
2007-06-11 16:26:37ZONING REVIEW: NOT REQUIRED
  
 * INTERIOR DEMOLITION ONLY
 * NO MODIFICATION TO EXTERIOR FACADE
  
 MATT FLIS - 822-1445


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved