 |
Plan Review Details - Permit 07050622
Plan Review Stops For Permit 07050622 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-10-20 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-10-20 |
Time |
10:11 |
Rev Time |
1.50 |
Received By |
jwitmer |
Date |
2007-10-20 |
Time |
09:53 |
Sent To |
|
|
Notes |
2007-10-20 10:28:11 | BUILDING PLAN REVIEW | | PERMIT: 07050622 | | ADD: 540 CLEMATIS | | CONT: KDN CONSTRUCTION | | TEL: (561)662-1002 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 2NDREVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 3)PLANS INDICATE THIS BUILDING TO BE A TYPE IIB | | UNPROTECTED, UNSPRINKLERED, THIS BUILDING IS | | APPROXIMATELY 3,150 SQ FT. PLEASE INDICATE THE MINIMUM | | BUILDING | | TYPE OF CONSTRUCTION. IF THIS SPACE IS TO BE BUILT OUT | | AS A TYPE IIB THE BEARING WALLS WILL AS WELL AS | | NONBEARING WALLS WILL ALL NEED TO BE FIRE RETARDANT | | TREATED WOOD PLEASE SEE TABLE 601 FOOTNOTE C-II . LOOK | | AT TABLE 503 UNDER MERCANTILE AT A BUILDING TYPE VB, | | THE ALLOWABLE AREA OF 9,000 FOR A SINGLE STORY | | BUILDING. IN THIS CATEGORY THE EXTERIOR AND INTERIOR OF | | THE BUILDING DOES NOT REQUIRE THE FIRE RETARDANT | | TREATED WOOD. | | PLEASE PROVIDE : | | 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT | | IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF | | OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT WAS | | DESIGNED.NOTE THE BASE CODE IS THE 2004 FBC WITH 2006 | | REVISIONS. | | ALSO NOTE TO WHAT LEVEL OF ALTERATION IS BEING | | COMPLETED UNDER THE 2004 FBC EXISTING BUILDING CODE? | | IS THIS A CHANGE IN OCUPANCY? | | B) COMPLIED. | | C)THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE | | 503- MERCANTILE & CHAPTER 6, TABLE 601. | | D) COMPLIED. | | E) COMPLIED. | | F) COMPLIED. | | G) SEMI-COMPLIED.SQ. FT. UNDER ROOF (TOTAL) FOR THE | | TOTAL BUILDING NOT TENANT SPACE. TENANT SPACE IS ALSO | | NEEDED AND PROVIDED. THE REQUIEMENT FOR THE TOTAL BLDG | | SQUAREFOOTAGE IS BECAUSE OF THE TYPE II BUILDING | | CLASSIFICATION THE DESIGN PROFESSIONAL HAS INDICATED | | INACTING THE FIRERETARDANT TREATED WOOD. THIS | | BUILDING BEING A ONE STORY BUILDING APPROXIMATELY 3150 | | SQ. FT. WILL QUALIFY AS A TYPE V-B. | | | | 4) 2ND REQUEST,THE PLANS DO NOT INDICATE WHERE THE | | PROPERTY LINE WOULD BE OR IF THE FRONT DOOR SWINGS IN | | OR OUT OVER THE PROPERTY LINE? AGAIN, IF THE LEVEL OF | | ALTERATION PROVIDED UNDER THE 2004 FBC, AND IF THIS IS | | A CHANGE OF OCCUPANCY IT MAY OR MAY NOT ENACT CERTAIN | | REQUIREMENTS OF THE CODE. 2004 EXISTING BUILDING CODE | | SECTION 303 ALL BUILDING ALTERATIONS WILL BE CLASSIFIED | | TO ACCORDING TO LEVEL OF ALTERATION. CHANGES IN | | OCCUPANCIES MAY OR MAY NOT INACT CODE ISSUES DEPENDING | | ON THE CATEGORY OF OCCUPANCY, SEE 2004 EXISTING | | BUILDING | | CODE IN CHAPTER 8 CHANGE OF OCCUPANCIES. | | | | 5) COMPLIED. | | | | 6)2ND REQUEST,PLANS INDICATE A RAMP DIRECTLY INSIDE | | THE UNIT WITH NO BOTTOM LANDING.11-4.8.4.(2) | | LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT BE LESS THAN | | 60" | | CLEAR, & THE BOTTOM OF EACH RAMP SHALL HAVE NOT LESS | | THAN 72" OF STRAIGHT & LEVEL CLEARENCE. THE PLANS ARE | | MISSING THE BOTTOM LANDING OF 72", DEPENDING ON PART OF | | THE ANSWER TO COMMENT 3A) ANDCOMMENT# 4THIS | | REQUIREMENT MAY NOT HAVE TO BE MET. | | | | 7) 2ND REQUEST, PLEASE PROVIDE DOOR WIDTH FOR ALL NEW | | INTERIOR DOORS. 11-4.13.5 DOORWAYS, MINIMUM CLEAR | | WIDTH: DOORWAY SHALL HAVE A MINIMUM CLEAR OPENING OF | | 32" WITH THE DOOR OPEN 90 DEGREES, MEASURED BETWEEN THE | | FACE OF THE DOOR AND THE OPPOSITE STOP. THE PLANS | | INDICATE A 32INCH OPENING TO THE RESTROOM THIS WILL | | ONLY WORK IF THE HINGES ARE SWING CLEAR OF OPENING | | TYPE OF HINGE, THE DOOR WHEN OPENED 90 DEGRESS WILL | | SWING CLEAR OF THE DOOR OPENING OTHERWISE THE MINIMUM | | DOOR OPENING SIZE IS A 2'-10" OR 34INCHES. | | | | 8) 2ND REQUEST, THE RESTROOM DOES NOT PROVIDE | | DIMENSIONS, NOR IS THE 5'-0" TURNING CIRCLE INDICATED | | FOR THE HANDICAPPED RESTROOM. IT APPEARS THE TOLIET IS | | LOCATED IN THE TURNING RADIUS. 11-4.2.3 WHEELCHAIR | | TURNING SPACE. THE SPACE REQUIRED FOR A WHEELCHAIR TO | | MAKE A 180-DEGREE TURN IS A CLEAR SPACE OF 60 INCHES | | (1525 MM) DIAMETER [SEE FIGURE 3 (A)] OR A T-SHAPED | | SPACE [SEE FIGURE 3 (B)]. | | | | 9) IS THIS AGAIN A CHANGE IN OCCUPANCY, AND OR A NEW OR | | RECONFIGURED RESTROOM? 11-4.16.2 CLEAR FLOOR SPACE. | | WATER CLOSET.CLEAR FLOOR SPACE FOR WATER CLOSETS NOT IN | | STALLS SHALL COMPLY WITH FIGURE 28 . CLEAR FLOOR SPACE | | MAY BE ARRANGED TO ALLOW EITHER A LEFT-HANDED OR | | RIGHT-HANDED APPROACH. | | | | 10) 2ND REQUEST, THE SIDE GRAB BAR IN THE RESTROOM, | | PLEASE DIMENSION THE SIZE AND LOCATION OF THE GRAB BAR. | | 11-4.16.4 GRAB BARS.PLEASE SEE FIGURE# 29 FOR LOCATION | | AND THE MINIMUM SIZE REQUIREMENTS FOR GRAB BARS. THE | | SIDE GRAB BAR IS TO BE A MINIMUM OF 42 INCHES LONG AND | | THE LEADING EDGE TO BE AT 54 INCHES FROM THE CORNER. | | THE BACK BAR ALSO IS NOT DIMENSIONED FOR LENGTH WHICH | | WOULD BE 36" AND ONE END OF THE BACK GRAB BAR BEING 12 | | INCHES OF CENTER OF THE WATER CLOSET BEING SET UP FOR A | | LEFTOR RIGHT HANDED SIDE APPROACH, SEE FIGURE 29 FOR | | CLARIFICATION. | | GRAB BARS FOR WATER CLOSETS NOT LOCATED IN STALLS SHALL | | COMPLY WITH SECTION 11-4.26 AND FIGURE 29 . THE GRAB | | BAR BEHIND THE WATER CLOSET SHALL BE 36 INCHES (915 MM) | | MINIMUM. | | | | 11) COMPLIED. | | | | 12)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | BUILDING PLAN REVIEW II | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-06-28 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-06-28 |
Time |
18:37 |
Rev Time |
1.11 |
Received By |
jwitmer |
Date |
2007-06-28 |
Time |
18:37 |
Sent To |
|
|
Notes |
2007-06-28 19:00:38 | BUILDING PLAN REVIEW | | PERMIT: 07050622 | | ADD: 540 CLEMATIS | | CONT: KDN CONSTRUCTION | | TEL: (561)662-1002 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 3)PLANS INDICATE THIS BUILDING TO BE A TYPE IIA | | UNPROTECTED, UNSPRINKLERED, THIS BUILDING IS | | APPROXIMATELY 3,150 SQ FT. PLEASE INDICATE THE MINIMUM | | BUILDING | | TYPE OF CONSTRUCTION. IF THIS SPACE IS TO BE BUILT OUT | | AS A TYPE IIA THE BEARING WALLS WILL NEED TO BE 1 HR | | RATED AS WELL AS THE CEILING ROOF ASSEMBLY.PLEASE | | PROVIDE : | | 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT | | IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF | | OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH | | THE PROJECT WAS DESIGNED. | | ALSO NOTE TO WHAT LEVEL OF ALTERATION IS BEING | | COMPLETED UNDER THE 2004 FBC EXISTING BUILDING CODE? B) | | THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | PROVISIONS OF CHAPTER 3. IS THIS A CHANGE OF | | OCCUPANCY? | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | TABLE 601. | | D) THEOCCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | IS REQUIRED. | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | OF THE BUILDING PERMIT | | G) SQ. FT. UNDER ROOF (TOTAL) FOR THE TOTAL BUILDING | | NOT TENANT SPACE. | | | | 4)THE PLANS DO NOT INDICATE WHERE THE PROPERTY LINE | | WOULD BE OR IF THE FRONT DOOR SWINGS IN OR OUT OVER THE | | PROPERTY LINE? | | | | 5) THE PLANSALSO INDICATE A HASHED LINE IN FRONT OF THE | | UNIT, IS THIS AAWNING? REQUIRES A SEPERATE PERMIT. | | | | 6) PLANS INDICATE A RAMP DIRECTLY INSIDE THE UNIT WITH | | NO BOTTOM LANDING.11-4.8.4.(2) LANDINGS. ALL LANDINGS | | ON RAMPS SHALL NOT BE LESS THAN 60" | | CLEAR, & THE BOTTOM OF EACH RAMP SHALL HAVE NOT LESS | | THAN 72" OF STRAIGHT & LEVEL CLEARENCE. | | | | 7) PLEASE PROVIDE DOOR WIDTH FOR ALL NEW INTERIOR | | DOORS. 11-4.13.5 DOORWAYS, MINIMUM CLEAR WIDTH: DOORWAY | | SHALL HAVE A MINIMUM CLEAR OPENING OF 32" WITH THE DOOR | | OPEN 90 DEGREES, MEASURED BETWEEN THE FACE OF THE DOOR | | AND THE OPPOSITE STOP. | | | | 8)HANDICAPPED ESTROM THE TOLIET IS LOCATED IN THE | | TURNING RADIUS. 11-4.2.3 WHEELCHAIR TURNING SPACE. THE | | SPACE REQUIRED FOR A WHEELCHAIR TO MAKE A 180-DEGREE | | TURN IS A CLEAR SPACE OF 60 INCHES (1525 MM) DIAMETER | | [SEE FIGURE 3 (A)] OR A T-SHAPED SPACE [SEE FIGURE 3 | | (B)]. | | | | 9) 11-4.16.2 CLEAR FLOOR SPACE. WATER CLOSET.CLEAR | | FLOOR SPACE FOR WATER CLOSETS NOT IN STALLS SHALL | | COMPLY WITH FIGURE 28 . CLEAR FLOOR SPACE MAY BE | | ARRANGED TO ALLOW EITHER A LEFT-HANDED OR RIGHT-HANDED | | APPROACH. | | | | 10) MISSING THE SIDE GRAB BAR IN THE RESTROOM, PLEASE | | DIMENSION THE SIZE AND LOCATION OF THE GRAB BAR. | | 11-4.16.4 GRAB BARS. | | GRAB BARS FOR WATER CLOSETS NOT LOCATED IN STALLS SHALL | | COMPLY WITH SECTION 11-4.26 AND FIGURE 29 . THE GRAB | | BAR BEHIND THE WATER CLOSET SHALL BE 36 INCHES (915 MM) | | MINIMUM. | | | | 11) PLEASE INDICATE COMPLIANCE WWITH COUNTERS AND BARS, | | 11-5.2 COUNTERS AND BARS. | | WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34 | | INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS | | SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION | | OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN | | LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH | | SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT | | ACCESSIBLE TABLES WITHIN THE SAME AREA. | | | | 11-5.6 TABLEWARE AND CONDIMENT AREAS. | | SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR | | TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES | | SHALL BE INSTALLED TO COMPLY WITH SECTION 11-4.2 (SEE | | FIGURE 54 ). | | | | 12)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | THIS REVIEW. | | | | BUILDING PLAN REVIEW II | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-10-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-10-06 |
Time |
18:38 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-10-06 |
Time |
18:38 |
Sent To |
|
|
Notes |
2007-10-06 18:39:51 | 2007-10-06 18:39:51 | | | | *** DENIED 2ND REVIEW *** | | | | 1) NOTE: PLEASE KNOW WITH RESPECT TO THE | | DESIGNER/ENGINEER OF RECORD RESPONSE COMMENTS WHICH | | SEEM TO CONTEST THIS REVIEWER NOTES. SEVERAL OF THE | | ENGINEER RESPONSE NOTES MENTIONS PLANS DATED FEBRUARY | | 07, HOWEVER THE PREVIOUS REVIEW WAS DONE ON PLANS | | SUBMITTED WHICH WERE SIGNED, DATED AND SEALED ON | | 3/19/07 BY THE ENGINEER OF RECORD. | | PLEASE KNOW THAT THIS OFFICE/REVIEWER ONLY REVIEWS | | THE PLANS WHICH ARE SUBMITTED WITH THE PERMIT | | APPLICATION. | | THE PLANS SUBMITTED FROM THE PREVIOUS REVIEW WERE | | TURNED INTO THIS OFFICE WERE ALSO SUBMITTED BACK WITH | | THIS RE-SUB AS OLD PLANS. | | PLEASE SEE THE SIGNED, DATED AND SEALED PLANS DATED | | 3/19/07 FROM THE ENGINEER WERE THE SAME PLANS | | SUBMITTED. PLEASE CHECK THE PLANS SUBMITTED. | | THE PREVIOUS COMMENTS WERE VALID BASED ON THE PLANS | | SUBMITTED ON THE FIRST REVIEW AS SUBMITTED. | | ** PLEASE SEE THOSE SAME PLANS HAVE HAD SEVERAL OF THE | | PREVIOUS REVIEW COMMENTS *HIGH-LIGHTED*. | | EXAMPLE: | | A) PREVIOUS PLANS HAS 65AMP RATED CONDUCTORS ON 100AMP | | DISCONNECTS W/70A OCP. | | B) PREVIOUS PLANS HAVE 244AMPS OF LOAD SHOWN ON A | | 300AMP PANEL BEING FED FROM A 100AMP DISCONNECT WITH | | 70AMP FUSES. | | C) PREVIOUS PLANS HAD EQUIPMENT/REFRIGERATOR AT FRONT | | DOOR ON GENERAL PURPOSE CIRCUITS. | | | | ** THIS REVIEWER HAS STATED ON ALL REVIEWS PERFORMED BY | | THIS OFFICE THAT IF THERE EVER ANY QUESTIONS, OR | | COMMENTS TO PLEASE DO NOT HESITATE IN CONTACTING THIS | | OFFICE/OR REVIEWER. AT THIS TIME WE MAY GO OVER | | COMMENTS OR EVEN IF A MEETING IS NEEDED WE CAN SCHEDULE | | A TIME TO GO OVER REVIEW COMMENTS. | | | | **THIS HAS NOT CHANGED, AND ONCE AGAIN IF THERE ARE ANY | | ITEMS WHICH NEED TO BE GONE OVER PLEASE CALL. | | | | 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #2. PLEASE | | SUBMIT LIGHTING PERFORMANCE CALCULATIONS. MAY NOT USE | | METHOD *A* WHOLE BUILDING CALCULATION FOR THE TENANT | | BUILD OUT. | | PLEASE SEE COMMENTS FROM MECHANICAL REVIEWER. PLEASE | | SEE 13-415.2 AND TABLES. | | PLEASE SEE LIGHTING CONTROLS STILL REQUIRED PER | | 13-415.1.ABC.1.1, .1.2. PLEASE SEE THE ONLY DEVICE IS | | THE OS SHOWN AT FRONT DOOR WHICH DOES NOT PROVIDE | | NEEDED COVERAGE IN THE REAR OF SPACE. PLEASE ALSO SEE | | THIS DOES NOT THE MEET THE REQUIREMENTS FOR SEPARATE | | SPACE CONTROLS FOR AREAS WHICH HAVE FLOOR TO CEILING | | HEIGHT PARTITIONS. | | PLEASE ADJUST DEVICES, TIMES FOR DEVICES TO BE CHOSEN. | | | | 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #3 WITH | | RESPECT TO RISER AND TO BE SURE AND COORDINATE ALL WITH | | THE ACTUAL EXISTING RISER. THE LAST SETS OF REVISED | | ELECTRICAL PLANS SUBMITTED TO THE CITY FOR PERMITTING | | AND REVISIONS INDICATES LARGER MAINS BEING TAPPED FORM | | THE EXISTING MAIN AND GUTTER. | | PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON THE | | EXISTING SERVICE WITH NEW LOADS BEING ADDED.(LOAD | | CALCULATIONS SUBMITTED, HOWEVER NOTE TO REMAIN DUE TO | | KNOWN ADJUSTMENTS WHICH WILL BE NEEDED). | | FOR EXAMPLE, ALL OTHER TENANT MAINS ARE SHOWN AT | | 100AMPS, YET THERE IS ANOTHER RESTAURANT/ SANDWICH SHOP | | WHICH HAS A LARGER SERVICE MAIN THAN 100AMPS. PLEASE | | SEE 240, 310, 408, 230, 215.5, 220 ETC. PLEASE ADJUST | | ALL. | | FBC 106.3.5.1.2 | | | | 4) NOTE: PLEASE CLARIFY WATER HEATER LOAD AS THE NEW | | CODE REQUIRED STORAGE TYPE WATER HEATER LOADS TO BE | | SHOWN AT 125%. THESE ARE NOW CONSIDERED CONTINUOUS | | LOADS. | | PLEASE SEE 422.13 | | | | ** AS THERE WILL BE SEVERAL CHANGES, PLEASE BE SURE TO | | GO OVER COMMENTS FROM ALL TRADES WHICH MAY AFFECT THE | | SCOPE OF WORK ALONG WITH OTHER TRADE REVIEWED SHEETS. | | | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-06-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-06-08 |
Time |
08:19 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-06-07 |
Time |
20:48 |
Sent To |
|
|
Notes |
2007-06-08 08:20:10 | *** UNSAT *** | | | | 1) NOTE:PLEASE STATE ALL OF THE RELEVANT CODES AS | | ADOPTED FROM THE STATE OF FLORIDA AS OF DECEMBER 8TH, | | 2006. | | PLEASE LIST THE FOLLOWING AT A MINIMUM ON ELECTRICAL | | SHEETS AS WELL AS ARCHITECTURAL. | | 2004 FBC W/2006 REVISIONS. | | 2005 NFPA-70 (NEC). | | 2003 NFPA-101 (LS CODE). | | | | 2) NOTE: PLEASE SEE FBC CHAPTER 13 FOR COMPLIANCE FOR | | ENERGY CALCULATIONS/PERFORMANCE CALCULATIONS | | 13-415.1.AB1.1, 13-415.2. | | PLEASE SEE MISSING LIGHTING CONTROLS AS REQUIRED PER | | 13-415.1.ABC.1.1, .1.2 AND .1.3. | | ** AS NO INFORMATION ON SCHEDULING, TYPEOF DEVICES, | | FIXTURES, WATTAGES, OVER RIDES, ETC HAVE BEEN SUBMITTED | | FOR REVIEW, COMMENTS CAN NOT BE MADE AT THIS TIME. | | | | 3) NOTE: PLEASE SEE THE SERVICE AS SHOWN CONTAINS A | | NOTE AT THE BOTTOM WHICH INDICATES *EXISTING* YET THE | | RISER AS SHOWN INDICATES SOME ITEMS AS *NEW*?? PLEASE | | CLARIFY ALL SERVICE EQUIPMENT AS SHOWN. PLEASE SEE THE | | PANEL SCHEDULE SHOWS THIS AS A 300AMP PANEL WITH 244 | | AMP LOAD, YET THE PANEL IS ONLY BEING FED W/ A 2-POLE | | 70AMP BREAKER WITH CONDUCTORS WHICH ARE ONLY RATED AT | | 65AMPS?? | | PLEASE SEE THE LOAD ON PANEL AS NOTED ABOVE SHOWN AT | | 244AMPS, YET THE RISER LOAD CALCULATIONS ARE SHOWN | | SUBSTANTIALLY LESS FOR THIS SAME UNIT?? | | PLEASE SEE THERE ARE SEVERAL ITEMS INCORRECT WITH THIS | | RISER AND NEW FEED TO PANEL. | | PLEASE SEE 240, 310, 408, 230, 215.5 ETC. | | PLEASE ADJUST ALL. | | FBC 106.3.5.1.2 | | | | 4) NOTE: PLEASE SEE ALL BREAKERS ON THE PANEL SCHEDULE | | ARE 1-POLE BREAKERS? HOW IS THIS POSSIBLE FOR THE | | 240/220/208 VOLT UNITS. | | IS ALL EQUIPMENT ON SINGLE POLE BREAKERS? | | PLEASE SEE NEC. | | | | 5) NOTE: PLEASE SEE THE AHU SEEMS TO BE SHOWN WITH 10KW | | LOAD YET THE CONDUCTOR AND BREAKER SIZE IS NOT | | SUFFICIENT PER CODE. | | PLEASE SEE 240.4, 310.16, 424.3B. | | | | 6) NOTE: PLEASE CLARIFY WATER HEATER AS PLANS INDICATES | | A STORAGE TYPE UNIT AND PANEL SCHEDULE INDICATES | | INSTANT TYPE HEATERS. | | PLEASE SEE 422.13 AND THE FOLLOWING COMMENT FOR LOAD | | CALCULATIONS. | | | | 7) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON | | THE NEW PROPOSED LOAD FOR THIS TENANT SPACE AND FOR THE | | ENTIRE SERVICE FOR EXISTING LOADS AND NEW LOADS BEING | | ADDED TO SERVICE. THE LOAD AS SHOWN ON THE RISER LOAD | | CALCULATIONS IS NOT POSSIBLE. | | PLEASE SEE NEC 220 (ALL), 215.3, 230.42. | | PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AT 125% | | | | 8) NOTE: PLEASE SEE THE SHOW WINDOW RECEPTACLE IS BEING | | SHOWN ON THE GENERAL RECEPTACLE CIRCUIT WHICH IS NOT | | PERMITTED. | | 210.62,220.14, 220.44. | | | | 9) NOTE: PLEASE SEE THE PLANS INDICATE SOME SORT OF | | REFRIGERATOR AT THE FRONT ENTRANCE WHICH IS BEING SHOWN | | ON THE SAME GENERAL RECEPTACLE CIRCUIT AS SHOW WINDOW | | ETC. PLEASE SEE THE VA ON UNIT NEEDS TO BE VERIFIED AS | | THE CIRCUIT MOST LIKELY WILL NEED TO BE DEDICATED. | | PLEASE KNOW AS THE LOADS ARE NOT SHOWN, DETERMINATION | | CAN NOT BE DONE AT THIS TIME. | | PLEASE SEE 430, 422, 422, 220 ETC. | | FBC 106.1.2 | | | | 10) NOTE: PLEASE SEE 210.8B2 FOR ALL REQUIRED GFI | | PROTECTED CIRCUITS/RECEPTACLES ON PLANS IN KITCHEN FOOD | | PREP AREAS AND THE LIKE. | | | | 11) NOTE: PLEASE SEE VALUE FOR SCOPE OF WORK IS TO | | INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST | | ETC., EVEN IF ANY OF THESE ARE OWNER SUPPLIED. PLEASE | | SEE FBC 108.3. | | | | 12) NOTE: PLEASE SEE CU IS BEING SHOWN ON 1-POLE | | CIRCUIT? | | | | 13) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND | | COORDINATE WITH THE SUBMITTED PANEL SCHEDULE. PLEASE | | SEE SOME ELECTRICAL ITEMS NOT SHOWING CIRCUITS. PLEASE | | ALSO SEE 700.12F FOR CIRCUITING OF EM/EXT LTS. | | | | 14) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER ON | | PLANS/ TITLE BLOCKS. | | FAC 61G1-16.004 FBC 106.1.2 | | | | 15) NOTE: PLEASE SEE THE PANEL SCHEDULE INDICATES | | SEVERAL ITEMS BEING EXISTING, HOWEVER AS THIS IS A NEW | | BUILD-OUT FROM PREVIOUS SHELL THIS IS NOT POSSIBLE. | | PLEASE ADJUST. 408.4. | | FBC 106.3.5.1.2 | | | | | | ** PLEASE KNOW AT THIS TIME AS SOME OF THE INSTALLATION | | IS NOT CLEAR, THERE MAY BE COMMENTS IF THE INSTALLATION | | CHANGES AND/OR PERMIT APPLICATION CHANGES. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-06-08 07:35:12 | IN ELEC FOR REVIEW |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-10-24 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2007-10-24 |
Time |
13:11 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2007-10-24 |
Time |
13:11 |
Sent To |
|
|
Notes |
2007-10-24 13:33:11 | ***DENIED*** | | | | SOME OF THE PREVIOUS COMMENTS WERE ADDRESSED DIRECTLY | | ON THE PLANS. (SHT A-1) A RESPONSE LETTER (2ND REQUEST) | | WOULD BE HELPFUL AND AS STATED IN THE FIRST REVIEW WILL | | HELP EXPEDITE THE PLAN REVIEW PROCESS. | | | | 1) OK | | | | 2) OK | | | | 3) OK | | | | 4) COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | MOVE FREQUENTLY AS NECESSARY FOR SAFE OPEARTION. | | | | 5) THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY | | THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES ETC). | | | | 6) CLASSIFY THE HAZARD OF CONTENTS OF | | BUILDING/STRUCTURE AS LOW, ORDINARY OR HIGH. | | | | 7) OK | | | | 8) LOCKS ON EGRESS DOORS SHALL NOT REQUIRE THE USE OF A | | KEY, TOOL OR SPECIAL KNOWLEDGE OR EFFORT OF OPERATION | | FROM THE EGRESS SIDE. (NO DOOR SCHEDULE) | | | | 9) OK | | | | 10) AN EXIT SIGN LIGHT WITH BATTERY BACK-UP CAPABILITY | | SHALL BE REQUIRED TO DIRECT PERSON(S) FROM THE COOKING | | PREPARATION AREA. | | | | 11) SPECIFY THE INTERIOR WALLS AND CEILING FINISH | | MATERIALS IN TERMS OF CLASSA,B OR C. | | | | 12) COMMERCIAL COOKING EQUIPMENT TO COMPLY WITH NFPA | | 96, 2001 EDITION. | | | | 13) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR | | HOOD AND SUPPRESSION SYSTEMS. PLANS INDICATE SEPARATE | | PERMIT FOR FIRE SPRINKLER WHICH PLANS ALSO STATE NOT | | APPLICABLE. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-07-12 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-07-12 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-07-12 |
Time |
08:45 |
Sent To |
|
|
Notes |
2007-07-12 09:18:01 | *****DENIED***** | | | | DUE TO THE ALTERATION, MODERNIZATION, OR RENOVATION TO | | THIS SITE, THE REQUIREMENTS OF A NEW MERCANTILE | | OCCUPANCY SHALL APPLY.IT SHALL BE SUB-CLASSIFIED AS A | | CLASS C MERCALNTILE (GROSS AREA NOT MORE THAN 3000 | | SQUARE FEET). | | | | 01.THE SUITE NUMBER SHALL BE INCLUDED WITH NUMERICAL | | ADDRESS IN THE TITLE BLOCK OF EACH SUBMITTED PLAN | | SHEET. | | | | 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | REFERENCED. | | | | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATION SHALL COMPLY WITH NFPA 241. | | | | 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 05.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY | | THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES). | | | | 06.CLASSIFY THE HAZARD OF CONTENTS OF | | BUILDING/STRUCTURE AS LOW, ORDINARY, OR HIGH. | | | | 07.DECLARE THE OCCUPANT LOAD IN NUMBER OF PERSONS FOR | | WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE | | REQUIRED. | | | | 08.LOCKS ON EGRESS DOORS SHALL NOT REQUIRE THE USE OF | | A KEY, A TOOL, OR SPECIAL KNOWLEDGEOR EFFORT OF | | OPERATION FROM THE EGRESS SIDE. | | | | 09.A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN A | | CLASS C MERCANTILE PROVIDED THAT THE 75' TRAVEL | | DISTANCE TO THE EXIT IS NOT EXCEEDED.PLEASE | | DEMONSTRATE | | | | 10.AN EXIT SIGN LIGHT, WITH BATTERY BACK-UP | | CAPABILITY, SHALL BE REQUIRED TO DIRECT PERSON(S) FROM | | THE COOKING PREPARATION AREA. | | | | 11.SPECIFY THE INTERIOR WALL AND CEILING FINISH | | MATERIALS IN TERMS OF CLASS A OR CLASS B. | | | | 12.COMMERCIAL COOKING EQUIPMENT SHALL BE ACCORDANCE | | WITH NFPA 96 - 2001 EDITION. | | | | 13.SEPARATE PLANS AND PERMIT REQUIRED FOR BOTH THE | | COOKING HOOD INSTALLATION AND THE HOOD'S SUPPRESSION | | SYSTEM. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLANS EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2007-11-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-11-03 |
Time |
17:07 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-11-03 |
Time |
17:07 |
Sent To |
|
|
Notes |
2007-11-03 17:13:22 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | ****FROM PREVIOUS REVIEW: | | | | 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | INFORMATION IS REQUIRED FOR THE GAS PERMIT: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | ****RESPONSE NOTED, BUT COMMENT NOT COMPLETLY | | ADDRESSED. LENGTHS OF PIPE NOT SHOWN. | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE | | NOTED, BUT COMMENT NOT ADDRESSED. PIPE TYPE NOT | | INDICATED ON LEGEND. | | | | C. OK | | | | D. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | ****RESPONSE NOTED, BUT THIS WILL BE VERIFIED WHEN ALL | | CUT SECTION LENGTHS ARE INDICATED ON THE GAS ISOMETRIC | | RISER DIAGRAM. | | | | E. OK | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE | | MANUF. SPECIFICATION SHEETS FOR ALL GAS APPLIANCES | | INCLUDING THE RTU ARE REQUIRED AND SHALL SHOW A LISTING | | AS WELL AS THE BTU LOAD OF THE APPLIANCE. | | | | G. N/A | | H. N/A | | | | I. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | ****RESPONSE NOTED, BUT THE COMMENT IS NOT ADDRESSED. | | | | **********NEW COMMENTS*********** | | | | 1B. SEDIMENT TRAPS REQUIRED BY SECTION 408.4 SHALL BE | | SHOWN ON THE GAS RISER DIAGRAM. | | | | 2B. SHUT OFF VALVES SHALL BE PROVIDED FOR EACH GAS | | APPLIANCE. SECTION 409.5. PLEASE SHOW THE SHUT OFF | | VALVE FOR THE RTU UNIT. ALL SHUT OFF VALVES SHALL BE | | ACCESSIBLE PER SECTION 409.5. | | | | 3B. SEE ATTACHED SHEET CONCERNING THE DESIGN | | PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A | | NOTICE ONLY AT THIS TIME. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2007-11-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-06-20 |
Time |
14:48 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-06-20 |
Time |
14:48 |
Sent To |
|
|
Notes |
2007-11-03 14:50:22 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | INFORMATION IS REQUIRED FOR THE GAS PERMIT: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | D. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | E. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | G. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | H. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | | | I. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-09-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-14 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-14 |
Time |
09:27 |
Sent To |
|
|
Notes |
2007-10-05 17:19:16 | TO "COMM" BD#22 | 2007-09-14 09:27:40 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-07-12 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-07-12 |
Time |
08:45 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-05-17 |
Time |
15:52 |
Sent To |
|
|
Notes |
2007-06-06 15:21:40 | TO "COMM" BD#55 | 2007-05-17 15:54:09 | WAITING FOR "COMM" BD--RESTAURANT |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2007-11-05 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-11-05 |
Time |
11:18 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-11-05 |
Time |
07:53 |
Sent To |
PC |
|
Notes |
2007-11-05 11:18:01 | REVIEW #: 2ND | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC | | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | NOTE: THERE WAS NO WRITTEN RESPONSE TO PREVIOUS | | MECHANICAL REVIEW COMMENTS IN THIS SUBMITTAL PACKAGE. | | PLANS WILL BE REVIEWED TO DETERMINE IF PREVIOUS | | COMMENTS WERE ADDRESSED. | | | | 1. NOT ADDRESSED. INFORMATION IS STILL MISSING ON | | PLANS. | | | | 2. NOT ADDRESSED. | | | | 3. NO VENTILATION (OUTSIDE AIR) CALCULATIONS OR | | INFORMATION PROVIDED. OCCUPANCY AND OCCUPANT LOAD FOR | | PURPOSES OF VENTILATION SHALL BE DETERMINED IN | | ACCORDANCE WITH FBC,M TABLE 403.3 PROVIDE CALCULATIONS | | SHOWING OCCUPANCY, OCCUPANT LOAD, O.A. REQUIRED AND | | O.A. PROVIDED. ALSO, PROVIDE BATHROOM EXHAUST FAN | | INFORMATION ON EQUIPMENT SCHEDULE SHOWING MAKE/MODEL, | | CFM AND MEANS OF CONTROL. ALSO SHOW DISCHARGE LOCATION | | OF BATH EXHAUST IN ACCORDANCE WITH FBC,M 401.5. NOTE: | | BATH EXHAUST FAN IS NOT SHOWN ON ELECTRICAL PLANS. HOW | | WILL THIS FAN BE POWERED? | | | | 4. AIR BALANCE SCHEDULE FOR THE SPACE HAS NOT BEEN | | PROVIDED. PLEASE READ PREVIOUS COMMENT AND PROVIDE ALL | | REQUESTED INFORMATION TO SHOW COMPLIANCE WITH THE CODE | | SECTIONS AS PREVIOUSLY REFERENCED. NOTE: IT IS | | PROHIBITED TO HAVE RETURN AIR IN THE KITCHEN FOR | | NON-DEDICATED KITCHEN HVAC SYSTEMS IN ACCORDANCE WITH | | FBC,M 407.1. | | | | 5. NOT ADDRESSED. NO INFORMATION PROVIDED. SEE PREVIOUS | | REVIEW COMMENT. | | | | 6. WITHOUT A WRITTEN RESPONSE, THE FOLLOWING IS NOTED | | BASED ON INFORMATION ON PLANS AND SUBMITTALS: | | A) PLAN INDICATES A/C IS NEW AND EXISTING. ONLY ONE | | SYSTEM IS SHOWN ON PLAN. ARE THERE TWO SYSTEMS? ONLY | | ONE IS LISTED ON EQUIPMENT SCHEDULE. | | B) FLOOR PLAN SHOWS A ?CU #5 ON ROOF.? IS THIS A | | ROOFTOP PACKAGE UNIT AS INDICATED BY EQUIPMENT SCHEDULE | | AND MANUAL J FORM OR A SPLIT SYSTEM WITH AHU AND CU? IS | | THIS THE NEW SYSTEM OR THE EXISTING SYSTEM? | | C) THE RTU LISTED ON PLAN DOES NOT MATCH THE RTU LISTED | | ON MANUAL J FORM. | | D) THE GAS RISER DIAGRAM SHOWS AN EXISTING 4 TON RTU ON | | ROOF. THIS DOES NOT MATCH ANY OF THE OTHER SUPPLIED | | INFORMATION. THERE IS ALSO A GAS LINE SHOWN GOING TO | | THE RTU FOR HEAT WHILE THE ELECTRICAL PLAN SHOWS A 5KW | | HEAT STRIP. | | E) ELECTRICAL PLAN SHOWS SERVICE FOR ONE AHU AND ONE CU | | FOR ONE SPLIT SYSTEM. WHERE IS THE 2ND SYSTEM ON | | ELECTRICAL PLANS? THE LETTER FROM A & J TECHNOLOGIES, | | INC. INDICATES THAT A NEW UNIT IS SIZED TO PROVIDE | | ADDITIONAL COOLING REQUIRED BY THE KITCHEN. IS THE ONE | | EXISTING SYSTEM BEING REPLACED OR IS THIS AN ADDITIONAL | | SYSTEM? IN ANY EVENT, THE ELECTRICAL SHOWS ONLY ONE | | SPLIT SYSTEM. THE ACTUAL NATURE OF THE WORK TO BE | | PERFORMED CAN NOT BE DETERMINED AT THIS TIME. | | F) THE LETTER INDICATES THAT A & J TECHNOLOGIES HAS | | DESIGNED THIS A/C SYSTEM. IN ORDER TO PERFORM DESIGN OF | | THIS COMMERCIAL SYSTEM, THEY ARE REQUIRED TO BE | | LICENSED AS AN ENGINEERING BUSINESS UNDER FS 471 OR AS | | A MECHANICAL CONTRACTOR UNDER FS 489. PROVIDE ALL | | RELEVANT LICENSE INFORMATION FOR THIS COMPANY. SEE FBC | | 105.3.1.2(4). | | | | 7. AIRFLOW ON SCHEDULE NOW SHOWS 1300 CFM, BUT WE STILL | | DON?T KNOW THE CFM OF THE 6 INCH DROP IN THE KITCHEN. | | THIS NEEDS TO BE ADJUSTED BASED ON WHAT EQUIPMENT IS | | ACTUALLY BEING USED AND WHAT IS REQUIRED BASED ON THE | | MANUAL J SUBMITTED. | | | | 8. NOTE 9 HAS BEEN REMOVED. THERE IS NO LONGER A | | CONFLICT. HOWEVER, NOTE 4 NOW STATES 1\ INCH R-6 DUCT. | | GENERALLY 1 ? INCH IS REQUIRED TO ACHIEVE R-6. PLEASE | | CORRECT NOTE OR PROVIDE DUCT MANUFACTURER?S SUBMITTAL | | TO VERIFY THIS INFORMATION. | | | | 9 AND 10. NO INFORMATION WAS PROVIDED REGARDING THE | | COMMERCIAL KITCHEN EXHAUST SYSTEM OTHER THAN A NOTE FOR | | CFM ON HE MANUAL J FORM. PROVIDE INFORMATION FOR A | | COMPLETE COMMERCIAL KITCHEN EXHAUST SYSTEM, | | DEMONSTRATING COMPLIANCE WITH FBC,M SECTIONS 505 | | THROUGH 509. | | | | 11. THIS COMMENT STILL STANDS AS SIGNIFICANT | | INFORMATION IS STILL MISSING. | | | | ENERGY CALCULATIONS: METHOD A COMPLIANCE FORM IS NOT | | AVAILABLE FOR THIS PROJECT AS THIS IS NOT A WHOLE | | BUILDING. SHOW COMPLIANCE WITH MINIMUM PRESCRIPTIVE | | REQUIREMENTS FOR ALL NEW COMPONENTS BEING INSTALLED IN | | ACCORDANCE WITH FBC 13-400.0.C.4. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-06-16 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-06-16 |
Time |
11:45 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-06-16 |
Time |
10:11 |
Sent To |
|
|
Notes |
2007-06-16 11:44:25 | ------------------DENIED-------------------- | | | | FBC 2004 CODE FAMILY W/ 2006 REVISIONS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PLEASE SHOW SIZE OF OUTSIDE AIR DUCT FROM 12X12 | | O.A.I. TO R/A PLENUM. ALSO, PLEASE SHOW CFM OF 6" DROP | | IN BACK OF SPACE. FBC 106.1.1. | | | | 2. SUPPLY TRUNK LINE SHOWS ONE TRANSITION FROM 1/12 TO | | 12/10. IS THE TRUNK LINE TO REMAIN THAT SIZE FOR THE | | REMAINING 3 DROPS? FBC 106.1.2. | | | | 3.PLEASE SHOW VENTILATION CALCULATIONS WHICH | | DEMONSTRATE COMPLIANCE WITH FBC,M 403.3. ALSO, BATHROOM | | EXHAUST IS ALSO REQUIRED BY THIS SECTION. PLEASE SHOW | | MEANS OF EXHAUST, CFM AND DISCHARGE LOCATION. | | | | 4. PLEASE SHOW AN AIR BALANCE SCHEDULE INCLUDING | | SUPPLY, RETURN, OUTSIDE AIR, BATHROOM EXHAUST, KITCHEN | | EXHAUST WITH MAKE-UP AIR TO SHOW PRESSURIZATION OF | | SPACE PER FBC 13-409.1.ABC.2 AND COMPLIANCE WITH | | KITCHEN SPACE REQUIREMENTS OF 13-409-1.ABC 3.6.1. | | | | 5.PLEASE SHOW MEANS/LOCATION OF CONDENSATE DISPOSAL IN | | COMPLIANCE WITH FBC,M 307.2 (ALL SECTIONS) INCLUDING | | SECONDARY/AUXILIARY DRAIN PROTECTION PER 307.2.3. | | | | 6. ELECTRICAL PLAN INDICATES A/C EQUIPMENT IS EXISTING, | | BUT SCOPE OF WORK AS DESCRIBED ON PERMIT APPLICATION | | STATES "SPACE IS CURRENTLY GUTTED."ALSO, HVAC NOTE #6 | | SUGGESTS A/C EQUIPMENT IS NEW, NOT EXISTING. WHICH ONE | | IS CORRECT? FBC 106.1.1. | | | | 7. EQUIPMENT SCHEDULE SHOWS INDOOR AIRFLOW AT 1000 CFM | | BUT FLOOR PLAN SHOWS 1300 CFM, NOT INCLUDING THE 6" | | DROP WHICH DOESN'T SHOW CFM. PLEASE SHOW CORRELATION | | BETWEEN SCHEDULE AND FLOOR PLAN. | | | | 8. HVAC NOTE #4 IS IN CONFLICT WITH NOTE #9. PLEASE | | CLARIFY. | | | | 9. SCOPE OF WORK ON PERMIT APPLICATION INDICATES GAS | | AND KITCHEN EQUIPMENT. PLEASE SHOW ALL VENTS AND | | KITCHEN EXHAUST PER FBC 106.3.5.1.4. ALSO, A COMMERCIAL | | KITCHEN GREASE EXHAUST VENTILATION SYSTEM W/ AUTOMATIC | | FIRE SUPPRESSION SYSTEM IS REQUIRED PER FBC,M 507.2.1 | | AND 509.1. | | | | 10. PLEASE SEE FBC,M 507.9 FOR CLEARANCE REQUIREMENTS | | RELATED TO TYPE I KITCHEN HOODS INCLUDING REQUIREMENTS | | FOR WALL SURFACES ADJASCENT TO THE HOOD AND COOKING | | EQUIPMENT. | | | | 11. SIGNIFICANT INFORMATION IS MISSING FROM PLANS TO | | SHOW A CODE COMPLIANT BUILDING/SPACE AT THIS TIME. | | ADDITIONAL COMMENTS ARE POSSIBLE BASED ON THE | | ADDITIONAL INFORMATION WHEN IT IS PROVIDED. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-11-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-11-03 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-11-03 |
Time |
16:21 |
Sent To |
|
|
Notes |
2007-11-03 17:07:29 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | ****FROM PREVIOUS REVIEW. THE COMMENT NUMBER SHALL | | REMAIN THE SAME AS 1ST REVIEW: | | | | 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT. | | OF BUSINESS REGULATION, (DBR), DIVISION OF HOTEL AND | | RESTAURANT FOOD SERVICE FOR REVIEW. A MINIMUM OF TWO | | STAMPED PLANS WITH "TWO PAGE WORKSHEETS" ATTATCHED TO | | STAMPED PAGE SHALL BE SUBMITTED FOR REVIEW TO CITY WPB. | | SECTION 102.2.1. | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. | | | | 2. THE GREASE INTERCEPTOR SHALL BE SIZED BY | | ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO, | | (561) 822-2272,[email protected] OR CALVIN WILLIAMS, | | (561) 822-2284 [email protected]. THEIR FAX NUMBER IS | | (561) 822-2287. PLEASE INDICATE THEIR DETERMINATION | | WHEN RESUBMITTING. ARTICLE III SECTION 90-124. PLEASE | | SUBMIT A DETAIL FOR THE GREASE INTERCEPTOR. (SEE | | ATTACHED SHEET SHOWING WPB UTILITY STANDARD FOR | | INTERCEPTORS). | | ****RESPONSE NOTED, BUT THE GREASE INTERCEPTOR IS STILL | | SHOWN ON THE PLANS. ALSO IF THE GREASE INTERCEPTOR IS | | TO BE WAIVED, THEN AS REQUIRED A SAMPLE POINT SHALL BE | | INSTALLED ON THE GREASE LINE PRIOR TO CONNECTING INTO | | THE SANITARY DRAIN AND THE GREASE INTERCEPTOR SHOULD BE | | DELETED FROM THE RISER DIAGRAM. | | | | 3. ALL SHEETS. THE ADDRESS OF THE ARCHITECT OF RECORD | | DOES NOT REFLECT THE ADDRESS RECORDED ON THE STATE OF | | FLORIDA DBPR WEBSITE. (SEE ATTACHED SHEET). PLEASE | | UPDATE THE DBPR WEBSITE OR THE TITLE BLOCKS ON EACH | | SHEET SO THE ADDRESS CORRELATES. FAC 61G1-16.004(1) & | | FS 481-2055. | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED ON ALL | | SHEETS WITH THE ARCHITECT FIRM TITLE BLOCK. ALL SHEETS | | SHALL SHOW THE CORRECT ADDRESS. | | | | 4. OK | | 5. OK | | | | 6. INDICATE CODE REFERENCES THAT THE PLANS HAVE BEEN | | DESIGNED TO. FBC-2004 W/2006 AMENDMENTS MINIMUM. | | ****RESPONSE NOTED, BUT THE CODE ADOPTED IS NOT 2007 | | BUILDING CODE. PLEASE CORRECT CODE REFERENCE. | | | | 7. SHT A-1 TOILET ROOM. THE TURNING AREA SHALL BE | | UNOBSTRUCTED AND THE TOILET SHALL NOT BE IN THE TURNING | | AREA. SECTION 11-4.22.3. | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. REMOVING | | THE TURNING AREA IS NOT A CORRECT RESPONSE TO SHOW | | COMPLIANCE. PLEASE SHOW THE REQUIRED TURNING AREA AND | | THE TOILET SHALL NOT BE IN THE TURNING AREA. | | | | 8. SUBMIT A DETAIL FOR THE TOILET ROOM SHOWING | | COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22 | | WITH ALL SUBSECTIONS. THE DETAIL SHALL SHOW THE FLOOR | | PLAN AND ELEVATIONS WITH ALL REQUIRED MEASUREMENTS. THE | | W/C SHALL BE 18" OFF THE WALL TO THE CENTERLINE OF THE | | FIXTURE, AND THE LAV SHALL BE A MINIMUM 15" OFF THE | | WALL TO THE CENTERLINE OF THE FIXTURE. SEE FIGS 28 & | | 29. | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. SHOW | | COMPLIANCE WITH THE FOLLOWING: | | ___FOR THE W/C: | | A. 11-4.16.3 HEIGHT | | B. 11-4.16.4 GRAB BARS | | C. 11-4.16.5 FLUSH CONTROLS | | D. 11-4.16.6 DISPENSERS | | ___FOR THE LAV: | | A. 11-4.19.2 HEIGHT & CLEARANCES | | B. 11-4.19.3 CLEAR FLOOR SPACE | | C. 11-4.19.4 EXPOSED PIPES & SURFACES | | D. 11-4.19.5 FAUCETS | | E. 11-4.19.6 MIRRORS | | | | 9. SUBMIT A FINISH SCHEDULE FOR THE TOILET ROOM SHOWING | | COMPLIANCE WITH SECTIONS 1210.1 & 1210.2. WALLS WITHIN | | 2 FEET OF THE WATER CLOSET SHALL BE A SMOOTH, HARD AND | | NONABSORBENT SURFACE. | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. | | | | 10. SHT A-2 THE GREASE RISER DIAGRAM DOES NOT REFLECT | | THE FIXTURE LAYOUT ON THE FLOOR PLAN. PLEASE SHOW A | | PIPING LAYOUT ON THE FLOOR PLAN AND THE GREASE RISER | | ISOMETRIC DIAGRAM SHALL REFLECT THE PIPING LAYOUT. | | SECTION 106.1.1. | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. | | | | 11. SHT A-2 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT | | CONNECT TO THE BUILDING DRAIN. SHOW THE CONNECTION FOR | | THE BRANCH LINE TO THE BUILDING DRAIN . SECTION | | 106.1.1. | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. | | | | 12. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, | | VALVES, AND WATER HAMMER ATTESTORS, (REQD BY SECTIONS | | 604.9). SECTION 106.3.5.1.3(3)(8)(10)(13). ****RESPONSE | | NOTED, BUT COMMENT NOT ADDRESSED. | | | | 13. SUBMIT A WATER HEATER DETAIL SHOWING COMPLIANCE | | WITH SECTIONS 503.1, 504.6.1 & 607.3.2 (THERMAL | | EXPANSION CONTROL). | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE | | REQUIREMENT FOR SECTION 503.1 IS A SHUT OFF VALVE FOR | | WATER HEATER. THE VALVE AS SHOWN WILL SHUT OFF MORE | | THAN THE WATER HEATER. THE PLACE OF DISPOSAL FOR THE | | T&P VALVE DISCHARGE LINE IS NOT INDICATED, NOR IS THE | | EMERGENCY PAN DRAIN LINE TERMINATION POINT. | | | | 14. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE | | TO THE SPACE. SECTION 608.13.2. PLEASE INDICATE ON THE | | PLANS. | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO | | REFERENCE TO THE RPZV BACKFLOW IS FOUND ON SHT A-1. | | | | 15. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | INFORMATION IS REQUIRED FOR THE GAS PERMIT: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | ****RESPONSE NOTED, BUT COMMENT NOT COMPLETLY | | ADDRESSED. LENGTHS OF PIPE NOT SHOWN. | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE | | NOTED, BUT COMMENT NOT ADDRESSED. PIPE TYPE NOT | | INDICATED ON LEGEND. | | | | C. OK | | | | D. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | ****RESPONSE NOTED, BUT THIS WILL BE VERIFIED WHEN ALL | | CUT SECTION LENGTHS ARE INDICATED ON THE GAS ISOMETRIC | | RISER DIAGRAM. | | | | E. OK | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE | | MANUF. SPECIFICATION SHEETS FOR ALL GAS APPLIANCES | | INCLUDING THE RTU ARE REQUIRED AND SHALL SHOW A LISTING | | AS WELL AS THE BTU LOAD OF THE APPLIANCE. | | | | G. N/A | | H. N/A | | | | I. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | ****RESPONSE NOTED, BUT THE COMMENT IS NOT ADDRESSED. | | | | **********NEW COMMENTS*********** | | | | 1B. SEDIMENT TRAPS REQUIRED BY SECTION 408.4 SHALL BE | | SHOWN ON THE GAS RISER DIAGRAM. | | | | 2B. SHUT OFF VALVES SHALL BE PROVIDED FOR EACH GAS | | APPLIANCE. SECTION 409.5. PLEASE SHOW THE SHUT OFF | | VALVE FOR THE RTU UNIT. ALL SHUT OFF VALVES SHALL BE | | ACCESSIBLE PER SECTION 409.5. | | | | 3B. SEE ATTACHED SHEET CONCERNING THE DESIGN | | PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A | | NOTICE ONLY AT THIS TIME. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-06-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-06-20 |
Time |
06:38 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-06-19 |
Time |
12:46 |
Sent To |
|
|
Notes |
2007-06-20 07:23:18 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT. | | OF BUSINESS REGULATION, (DBR), DIVISION OF HOTEL AND | | RESTAURANT FOOD SERVICE FOR REVIEW. A MINIMUM OF TWO | | STAMPED PLANS WITH "TWO PAGE WORKSHEETS" ATTATCHED TO | | STAMPED PAGE SHALL BE SUBMITTED FOR REVIEW TO CITY WPB. | | SECTION 102.2.1. | | | | 2. THE GREASE INTERCEPTOR SHALL BE SIZED BY | | ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO, | | (561) 822-2272,[email protected] OR CALVIN WILLIAMS, | | (561) 822-2284 [email protected]. THEIR FAX NUMBER IS | | (561) 822-2287. PLEASE INDICATE THEIR DETERMINATION | | WHEN RESUBMITTING. ARTICLE III SECTION 90-124. PLEASE | | SUBMIT A DETAIL FOR THE GREASE INTERCEPTOR. (SEE | | ATTACHED SHEET SHOWING WPB UTILITY STANDARD FOR | | INTERCEPTORS). | | | | 3. ALL SHEETS. THE ADDRESS DOES NOT REFLECT THE ADDRESS | | RECORDED ON THE STATE OF FLORIDA DBPR WEBSITE. (SEE | | ATTACHED SHEET). PLEASE UPDATE THE DBPR WEBSITE OR THE | | TITLE BLOCKS ON EACH SHEET SO THE ADDRESS CORRELATES. | | FAC 61G1-16.004(1) & FS 481-2055. | | | | 4. SHT A-1 EQUIPMENT SCHEDULE ITEM K11 NOT SHOWN ON THE | | FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1. | | | | 5. INDICATE THE OCCUPANCY LOAD AND SEATING ON THE | | PLANS. SECTIONS 1004.3 & 1004.7. | | | | 6. INDICATE CODE REFERENCES THAT THE PLANS HAVE BEEN | | DESIGNED TO. FBC-2004 W/2006 AMENDMENTS MINIMUM. | | | | 7. SHT A-1 TOILET ROOM. THE TURNING AREA SHALL BE | | UNOBSTRUCTED AND THE TOILET SHALL NOT BE IN THE TURNING | | AREA. SECTION 11-4.22.3. | | | | 8. SUBMIT A DETAIL FOR THE TOILET ROOM SHOWING | | COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22 | | WITH ALL SUBSECTIONS. THE DETAIL SHALL SHOW THE FLOOR | | PLAN AND ELEVATIONS WITH ALL REQUIRED MEASUREMENTS. THE | | W/C SHALL BE 18" OFF THE WALL TO THE CENTERLINE OF THE | | FIXTURE, AND THE LAV SHALL BE A MINIMUM 15" OFF THE | | WALL TO THE CENTERLINE OF THE FIXTURE. SEE FIGS 28 & | | 29. | | | | 9. SUBMIT A FINISH SCHEDULE FOR THE TOILET ROOM SHOWING | | COMPLIANCE WITH SECTIONS 1210.1 & 1210.2. WALLS WITHIN | | 2 FEET OF THE WATER CLOSET SHALL BE A SMOOTH, HARD AND | | NONABSORBENT SURFACE. | | | | 10. SHT A-2 THE GREASE RISER DIAGRAM DOES NOT REFLECT | | THE FIXTURE LAYOUT ON THE FLOOR PLAN. PLEASE SHOW A | | PIPING LAYOUT ON THE FLOOR PLAN AND THE GREASE RISER | | ISOMETRIC DIAGRAM SHALL REFLECT THE PIPING LAYOUT. | | SECTION 106.1.1. | | | | 11. SHT A-2 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT | | CONNECT TO THE BUILDING DRAIN. SHOW THE CONNECTION FOR | | THE BRANCH LINE TO THE BUILDING DRAIN . SECTION | | 106.1.1. | | | | 12. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, | | VALVES, AND WATER HAMMER ATTESTORS, (REQD BY SECTIONS | | 604.9). SECTION 106.3.5.1.3(3)(8)(10)(13). | | | | 13. SUBMIT A WATER HEATER DETAIL SHOWING COMPLIANCE | | WITH SECTIONS 503.1, 504.6.1 & 607.3.2 (THERMAL | | EXPANSION CONTROL). | | | | 14. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE | | TO THE SPACE. SECTION 608.13.2. PLEASE INDICATE ON THE | | PLANS. | | | | 15. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | INFORMATION IS REQUIRED FOR THE GAS PERMIT: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | D. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | E. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | G. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | H. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | | | I. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2007-06-11 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2007-06-11 |
Time |
16:25 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2007-06-11 |
Time |
16:25 |
Sent To |
|
|
Notes |
2007-06-11 16:26:37 | ZONING REVIEW: NOT REQUIRED | | | | * INTERIOR DEMOLITION ONLY | | * NO MODIFICATION TO EXTERIOR FACADE | | | | MATT FLIS - 822-1445 |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |