Plan Review Details - Permit 07050620
Plan Review Stops For Permit 07050620
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-01 Cont ID  
Sent By mjacobs Date 2007-08-01 Time 09:15 Rev Time 0.00
Received By mjacobs Date 2007-08-01 Time 08:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-06-22 Cont ID  
Sent By mjacobs Date 2007-06-22 Time 08:50 Rev Time 0.00
Received By mjacobs Date 2007-06-22 Time 08:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-22 Cont ID  
Sent By dpalmer Date 2007-08-22 Time 10:39 Rev Time 0.00
Received By dpalmer Date 2007-08-22 Time 09:57 Sent To PC
Notes
2007-08-22 11:20:09*** REDLINED NOTES ON PLANS.
  
  
 PERMIT IS ISSUED BASED ON THE ATTACHED ORIGINAL LETTER
 FROM OWNER/CEO/PRESIDENT/OFFICER STATING THAT THE
 CONNECTION AND DISCONNECTION OF ANY GENERATOR BACK UP
 POWER WILL ONLY BE DONE BY *QUALIFIED PERSONNEL* AS
 DEFINED IN THE NATIONAL ELECTRICAL CODE. THE
 INSTALLATION OF *KEYED INTERLOCK* BREAKERS AS SHOWN ON
 PLANS ONLY MEETS THE *EXCEPTION* OF 702.6 AND THIS
 REVIEWER UNDER RIGHTS TO INTERPRETATION IN FS 468.619
 IS NOT ISSUING PERMIT BASED ON MEETING 702.6.THE
 KEYED INTERLOCK DOES NOT PROVIDE INADVERTENT CONNECTION
 OF BOTH THE UTILITY AND BACK UP POWER SOURCE BASED ON
 THE FACT THAT MULTIPLE KEYS ARE READILY AVAILABLE FROM
 MANUFACTURE(S) AND KEYED LOCK MANUFACTURE(S).
 THE RULING FROM LAW DEPARTMENT , THE BUILDING OFFICIAL,
 ASSISTANT BUILDING OFFICIAL, CHIEF ELECTRICAL INSPECTOR
 AND THIS REVIEWER IS BASED ON THE EXCEPTION IN 702.6
 THAT ALLOWS THEWORK IS ONLY DONE BY*QUALIFIED
 PERSONNEL* .
 ***** ANY VIOLATION OFMULTIPLE KEYS, ANY IMPROPER
 OPERATION OF EQUIPMENT, CORRECT SIGNAGE AND WORK DONE
 BY UN-QUALIFIED PERSONNEL COULD RESULT IN DEATH AND/OR
 SERIOUS INJURY, PROPERTY AND FIRE DAMAGE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-23 Cont ID  
Sent By dpalmer Date 2007-07-23 Time 11:08 Rev Time 0.00
Received By dpalmer Date 2007-07-23 Time 11:00 Sent To  
Notes
2007-07-23 11:08:58*** UNSAT ***
  
 1) NOTE: PLEASE SEE THE PLANS WERE SUBMITTED BACK
 WITHOUT THE REQUIRED MANUFACTURES SPECS/CUT SHEETS FOR
 THE SERVICE EQUIPMENT BEING PROPOSED.
 PLEASE SUBMIT THIS.
 110.3, 90.7,
 FBC 106.1.2
  
 2) NOTE: PLEASE SUBMIT A SIGNED, NOTARIZED LETTER FOR
 VERIFICATION THAT THE INSTALLATION AND HOOK UP AND
 DISCONNECTING OF THE *PORTABLE GENERATOR* WILL ONLY BE
 DONE BY *QUALIFIED PERSONNEL* AS DEFINED IN THENEC
 702.6, AND 100.
 PLEASE KNOW THIS LETTER NEEDS TO BE FROM ONE OF THE
 OWNERS/OFFICERS OF THE COMPANY CORPORATION.
 THIS DETERMINATION FOR THE REQUIRED DOCUMENTATION IS BY
 THIS REVIEWER, ASSISTANT BUILDING OFFICIAL AND BUILDING
 OFFICIAL IF A *KIRK KEY* IS BEING USED OR PROPOSED.
 PLEASE SEE THE RISER STILL INDICATE THIS AS A MTS,
 PLEASE KNOW THIS HAS YET TO BE VERIFIED FOR LISTING A
 MTS.
  
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-08 Cont ID  
Sent By dpalmer Date 2007-06-08 Time 07:27 Rev Time 0.00
Received By dpalmer Date 2007-06-07 Time 20:50 Sent To  
Notes
2007-06-08 07:28:38*** UNSAT ***
  
 1) NOTE:
 A) PLEASE SEE THE ADDRESS AS APPLIED IS FOR *SUITE
 #200*, HOW IS THIS POSSIBLE WHEN THE SCOPE OF WORK IS
 TO SERVICE THE BUILDING? THIS SHOULD NOT CONTAIN ANY
 SUITE/OR UNIT NUMBER.
 PLEASE CLARIFY SCOPE OF WORK AND PERMIT BEING APPLIED
 FOR ANY OTHER AREAS/UNITS/SUITES.
 PLEASE ALSO SEE THE OWNER INFORMATION AS STATED ON
 APPLICATION IS NOT CORRECT, PLEASE ADJUST OR PROVIDE
 INFORMATION ON OWNERSHIP.
  
 B) PLEASE SEE THE PERMIT APPLICATION MENTIONS THE WORK
 FOR A TRANSFER SWITCH ONLY WHICH WILL HAVE A *PORTABLE
 GENERATOR* UNIT. THIS IS BEING ASSUMED THE GENERATOR
 WILL BEONLY AT TIMES OF EMERGENCY YET THE PERMIT IS
 APPLIED FOR BY A GC?
 AS THE MAIN SCOPE OF WORK IS ELECTRICAL AND THE SLAB
 WORK IS MINOR IT SEEMS THIS SHOULD BE REVERSED BASED ON
 SCOPE AS SHOWN? THE PERMIT AS APPLIED SHOULD BE APPLIED
 FOR BY THE ELECTRICAL CONTRACTOR WITH THE GC SIGNED ON
 AS A SUB-CONTRACTOR FOR SLAB WORK. THIS WOULD BE AN
 *ELECTRICAL* PERMIT ONLY FOR ELECTRICAL CONTRACTOR AND
 *MISC* TYPE PERMIT FOR GC FOR CONCRETE WORK. AS
 APPLIED, INDICATES AT THIS TIME COMMERCIAL GENERATOR
 AND GENERATOR ELECTRICAL PERMIT.
 AS THE SCOPE OF WORK IS NOT CLEAR AT THIS TIME, THE
 REVIEW CAN ONLY BE BASED ON THE INFORMATION AS
 SUBMITTED ON PLANS AND PERMIT APPLICATION.
  
 2) NOTE: PLEASE STATE ALL OF THE RELEVANT CODES AS
 ADOPTED FROM THE STATE OF FLORIDA AS OF DECEMBER 8TH,
 2006.
 PLEASE LIST THE FOLLOWING AT A MINIMUM ON ELECTRICAL
 SHEETS AS WELL AS ARCHITECTURAL.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70 (NEC).
 2002 NFPA-110
  
 3) NOTE: PLEASE SEE THE SPECS/CUT SHEETS SUBMITTED SEEM
 TO INDICATE SOME KIND OF KEYED INTERLOCK AND THE PLANS
 CLEARLY STATE A MANUAL TRANSFER SWITCH (MTS). PLEASE
 CLARIFY AS THERE ARE SEVERAL *KEYED INTERLOCKS* ON THE
 MARKET WHICH DO NOT PROVIDE THE FAIL SAFE OR
 INADVERTENT MECHANICAL CONNECTION OF THE POWER ON THE
 NORMAL AND EMERGENCY SIDE. THIS JURISDICTION AND
 SEVERAL OTHERS HAVE FOUND MANY OF THESE TYPES OF
 DEVICES BEING SENT FROM THE MANUFACTURE WITH MORE THAN
 ONE KEY, MORE THAN ONE KEY AVAILABLE EITHER FROM THE
 MANUFACTURE OR THE LOCKING COMPANY WHICH COMPLETELY
 VOIDS ANY LISTING FOR INADVERTENT CONNECTION. AT THIS
 TIME BASED ON THE INFORMATION ANY KEYED INTERLOCK WHICH
 CAN BE TURNED IN THE *ON* POSITION AT THE SAME TIME OR
 ALLOWS MULTIPLE KEYS FROM NUMEROUS LOCATIONS CAN NO BE
 USED OR INSTALLED.
 702.6
 110.3, 90.7. PLEASE PROVIDE MORE INFORMATION ON THE MTS
 BEING INDICATED ON PLANS.
  
 4) NOTE: PLEASE PROVIDE NOTES FOR NEW SIGNAGE TO BE
 LOCATED AT BOTH LOCATIONS OF SERVICE EQUIPMENT. THE
 OLD/PREVIOUS SERVICE LOCATION AS THESE ARE NOW FEEDERS
 AND ARE CONSIDERED UNDER 225 AND NEW LOCATION AS THIS
 IS CONSIDERED THE NEW SERVICE LOCATION.
 230.2, 225.30-40.
  
 ** PLEASE KNOW AT THIS TIME AS SOME OF THE INSTALLATION
 IS NOT CLEAR, THERE MAY BE COMMENTS IF THE INSTALLATION
 CHANGES AND/OR PERMIT APPLICATION CHANGES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-07 21:00:30NOTES TO FOLLOW ON 6/8

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-08 Cont ID  
Sent By mawillia Date 2007-08-08 Time 15:00 Rev Time 0.00
Received By mawillia Date 2007-08-08 Time 14:51 Sent To  
Notes
2007-08-08 14:56:01*****APPROVED*****
  
  
 PLAN SHEET E-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-06-25 Cont ID  
Sent By mawillia Date 2007-06-25 Time 23:37 Rev Time 0.00
Received By mawillia Date 2007-06-25 Time 23:26 Sent To  
Notes
2007-06-25 23:37:01*****APPROVED*****
  
  
 THE APPROPIATE PLAN SHEET(S) WILL BE FIRE-STAMPED WHEN
 ALL OTHER REVIEWERS HAVE BEEN SATISFIED.

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2007-06-08 Cont ID  
Sent By rregueir Date 2007-06-08 Time 07:34 Rev Time 0.00
Received By rregueir Date 2007-06-08 Time 07:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-14 Cont ID  
Sent By adarroug Date 2007-08-14 Time 15:49 Rev Time 0.00
Received By adarroug Date 2007-08-14 Time 15:48 Sent To E
Notes
2007-08-14 15:49:58TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-06 Cont ID  
Sent By adarroug Date 2007-07-06 Time 10:21 Rev Time 0.00
Received By adarroug Date 2007-07-06 Time 10:21 Sent To  
Notes
2007-07-18 16:08:13TO "COMM" BD#36
2007-07-06 10:22:02WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-25 Cont ID  
Sent By mawillia Date 2007-06-25 Time 23:29 Rev Time 0.00
Received By mawillia Date 2007-05-17 Time 09:56 Sent To  
Notes
2007-06-05 14:30:00TO "COMM" BD#41
2007-05-17 09:57:04WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 2 Status N Date 2007-08-03 Cont ID  
Sent By astelly Date 2007-08-03 Time 08:39 Rev Time 0.00
Received By astelly Date 2007-08-03 Time 08:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-06-29 Cont ID  
Sent By astelly Date 2007-06-29 Time 15:40 Rev Time 0.00
Received By astelly Date 2007-06-29 Time 15:42 Sent To  
Notes
***NONE***