Plan Review Details - Permit 07050617
Plan Review Stops For Permit 07050617
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-11-02 Cont ID  
Sent By shill Date 2009-11-02 Time 10:43 Rev Time 0.00
Received By shill Date 2009-11-02 Time 10:43 Sent To  
Notes
2009-11-02 10:44:15REVISION, CHANGED DRIVEWAY MATERIAL FROM ASPHALT TO
 CONCRETE
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-09-17 Cont ID  
Sent By shill Date 2009-09-17 Time 16:31 Rev Time 0.00
Received By shill Date 2009-09-17 Time 16:31 Sent To  
Notes
2009-09-17 16:32:02LINTEL REPAIR DETAIL DATED 8/19/9
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-01-27 Cont ID  
Sent By mjacobs Date 2009-01-27 Time 14:30 Rev Time 0.00
Received By mjacobs Date 2009-01-27 Time 11:51 Sent To PC
Notes
2009-01-21 14:30:49AFTER A MEETING WITH THE ARCHITECT KARIN MANNCHEN THE
 REMAINDER OF THE CODE ISSUES WRERE ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-11-13 Cont ID  
Sent By mjacobs Date 2008-11-13 Time 12:05 Rev Time 0.00
Received By mjacobs Date 2008-11-13 Time 12:05 Sent To  
Notes
2008-11-13 12:05:22BUILDING PLAN REVIEW
 PERMIT: 07050617
 ADD: 5405 BROADWAY
 CONT: RAY GRAEVE & SONS CONST LLC
 TEL: (561)432-5690
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 11-13-08
 REVIEW 3RD
 ACTION: DENIED
  
 1) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) OK.
  
 3) THE PRODUCT APPROVALS SUBMITTED ARE MISSING THE
 INSTALLATION REPORTS. WHEN RE-SUBMITTING, MATCH THE FL#
 WITH THE CORRECT INSTALLATION REPORT. PROVIDE THE
 PRODUCT APPROVAL FOR THE GLASS BLOCK AND NEW PRECAST
 LINTEL, ALSO INDICATE THE SIZE OF THE LINTIL. IS IT 4",
 6", 8" OR 12". FBC 2104.1.5 THE MINIMUM LENGTH OF END
 SUPPORT FOR LINTELS SHALL BE 4". INDICATE THE OPENING
 DIMENTION. PLEASE CIRCLE OR HI-LIGHT WHICH SYSTEM WILL
 BE USED FROM EACH PRODUCT.
  
 4) FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS. PROVIDE A WALL LEGEND INDICATING WHICH
 WALLS ARE NEW AND WHICH WALLS ARE EXISTING. IN THE
 LEGEND SHOW A DETAIL OF EACH TYPE OF WALL. SUBMIT AN
 EXISTING AND A PROPOSED PLAN OF THE SPACE.
  
 5) THE FOLLOWING INFORMATION REGARDING THE BUILDING IS
 REQUIRED FOR REVIEW.
 A) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 B) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 C) SUBMIT A LIFE SAFETY PLAN SHOWING MEANS OF EGRESS
 EXIT ACCESS ETC.
 D) IF THERE IS AN AUTOMATIC SPRINKLER SYSTEM INSTALLED
 IN THE BUILDING, PROVIDE THE NEW LAYOUT OF THE
 SPRINKLER HEADS. THIS INFORMATION CAN BE SHOWN ON THE
 NEW REFLECTED CEILING PLANS. FBC 106.3.5.1.1(5)
  
 ** NO RESPONSE NOT ADDRESSED**
 6) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.. ARE THE INTERIOR WALLS CONCRETE BLOCK?
  
 7) SEPARATE PERMITS ARE REQUIRED FOR THE FENCE AND
 AWNINGS. WHEN APPLYING FOR THE PERMIT, SUBMIT THE
 FOLLOWING INFORMATION. AWNINGS SHALL BE DESIGNED SO
 THAT FABRIC OR MEMBRANE COVER CAN BE QUICKLY AND EASILY
 REMOVED PER 3105.4.2.1 TIGHTLY WRAPED OR WOVEN CORDS
 ARE ACCEPTABLE, WHEN 2 COPIES OF A DETAILED INSTRUCTION
 GUIDE FOR REMOVAL ARE INCLUDED IN THE SUBMITTAL. IN
 ADDITION 2 COPIES OF A NOTORIZED LETTER OF INTENT TO
 REMOVE AT 75 MPH ARE REQUIRED. THE FENCE SHALL BE
 DESIGNED THE MEET THE REQUIRED WIND LOADS OF THE CITY
 OF WEST PALM BEACH WHICH IS 140 MPH.
  
 8) THE ORDER AND ADJUDGED SECTION OF THE ZONING BOARD
 OF APPEALS PAGE #7 D (V) STATES THAT ALL CHAIN-LINK
 FENCES SHALL BE REMOVED; HOWEVER, THE SITE PLAN SHOWS A
 6? HIGH CHAIN LINK FENCE. CLARIFY.
  
 9) THE LOCATION OF THE GAZEBO APPEARS TO BE REDUCING
 THE ACCESSIBLE ROUTE TO THE BUILDING. ON SHEET #4
 INDICATE THE DIMENSION BETWEEN THE BUILDING AND THE
 GAZEBO TO SHOW THE CLEAR WIDTH OF THE ACCESS ROUTE. THE
 MINIMUM CLEAR WIDTH OF AN ACCESSIBLE ROUTE SHALL BE 36
 INCHES. IF A PERSON IN A WHEELCHAIR MUST MAKE A TURN
 AROUND AN OBSTRUCTION, THE MINIMUM CLEAR WIDTH OF THE
 ACCESSIBLE ROUTE SHALL BE AS SHOWN IN FIGURE 7(A) AND
 FIGURE 7(B). 11-4.3.3
  
 10) A FINISH SCHEDULE SHALL BE SUBMITTED FOR THE DOOR
 AND ROOM FINISHED. FBC 1210.2 WALLS WITHIN 2 FEET OF
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE
 FLOOR. SHOW COMPLIANCE.
  
 11) SHEET #4. SUBMIT DETAIL INFORMATION FOR THE
 STRUCTURAL FOUNDATION OF THE GAZEBO AND THE TRASH CAN
 ENCLOSURE. ALSO STATE WHAT TYPE OF FASTENERS WILL BE
 USED TO FASTEN THE TRASH CAN ENCLOSURE GATE TO THE
 EXISTING BUILDING. ADDITIONAL INFORMATION REQUIRED
 106.1.2*
  
 12) SUBMIT DETAIL DRAWING SHOWING ALL MATERIALS TO BE
 USED FOR BLOCKING UP THE OPENINGS. THE PREVIOUS
 DRAWINGS SHOWED GLASS BLOCK; IT IS NOT CLEAR WHAT TYPE
 OF MATERIALS WILL BE USED ON THE NEW DRAWINGS.
 ADDITIONAL INFORMATION REQUIRED. 106.1.2*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561) 805-6726
 FAX (561)805-6676
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-19 Cont ID  
Sent By mjacobs Date 2007-09-19 Time 18:19 Rev Time 0.00
Received By mjacobs Date 2007-09-18 Time 06:14 Sent To  
Notes
2007-09-18 12:59:08BUILDING PLAN REVIEW
 PERMIT: 07050617
 ADD: 5405 BROADWAY
 CONT: RAY GRAEVE & SONS CONST LLC
 TEL: (561)432-5690
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) F.S. 481.221 (2) ALL FINAL CONSTRUCTION DOCUMENTS
 AND INSTRUMENTS OF SERVICE WHICH INCLUDE DRAWINGS,
 PLANS SPECIFICATIONS, OR REPORTS PREPARED OR ISSUED BY
 THE REGISTERED ARCHITECT AND BEING FILED FOR PUBLIC
 RECORD SHALL BEAR THE SIGNATURE AND SEAL OF THE
 REGISTERED ARCHITECT WHO PREPARED OR APPROVED THE
 DOCUMENT AND THE DATE ON WHICH THEY WERE SEALED. NOTE:
 ONE OF THE SHEET IS NOT SIGN OR DATED.
  
 3) THE PRODUCT APPROVALS SUBMITTED ARE MISSING THE
 INSTALLATION REPORTS. WHEN RE-SUBMITTING, MATCH THE FL#
 WITH THE CORRECT INSTALLATION REPORT. PROVIDE THE
 PRODUCT APPROVAL FOR THE GLASS BLOCK AND NEW PRECAST
 LINTEL, ALSO INDICATE THE SIZE OF THE LINTIL. IS IT
 4",6",8" OR 12". FBC 2104.1.5 THE MINIMUM LENGTH OF END
 SUPPORT FOR LINTELS SHALL BE 4". INDICATE THE OPENING
 DIMENTION.
  
 4) FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS. PROVIDE A WALL LEGEND INDICATING WHICH
 WALLS ARE NEW AND WHICH ONES ARE EXISTING. IN THE
 LEGEND SHOW A DETAIL OF EACH TYPE OF WALL.
  
 5) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
  
 6) STATE THE LEVEL OF ALTERATION IN ACCORDANCE WITH
 CH.3 OF THE 2004 EXISTING FBC. ARE THE INTERIOR WALLS
 CONCRETE BLOCK?
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By mjacobs Date 2007-06-09 Time 07:17 Rev Time 0.00
Received By mjacobs Date 2007-06-09 Time 05:08 Sent To  
Notes
2007-06-09 07:17:21BUILDING PLAN REVIEW
 PERMIT: 07050617
 ADD: 5405 BROADWAY
 CONT: RAY GRAEVE & SONS CONST LLC
 TEL: (561)432-5690
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2)F.S. 481.221 (2)ALL FINAL CONSTRUCTION DOCUMENTS
 AND INSTRUMENTS OF SERVICE WHICH INCLUDE DRAWINGS,
 PLANS SPECIFICATIONS, OR REPORTS PREPARED OR ISSUED BY
 THE REGISTERED ARCHITECT AND BEING FILED FOR PUBLIC
 RECORD SHALL BEAR THE SIGNATURE AND SEAL OF THE
 REGISTERED ARCHITECT WHO PREPARED OR APPROVED THE
 DOCUMENT AND THE DATE ON WHICH THEY WERE SEALED. NOTE:
 ONE OF THE SHEET IS NOT SIGN OR DATED.
  
 3)THE PRODUCT APPROVALS SUBMITTED ARE MISSING THE
 INSTALLATION REPORTS. WHEN RE-SUBMITTING, MATCH THE FL#
 WITH THE CORRECT INSTALLATIONREPORT. PROVIDE THE
 PRODUCT APPROVAL FOR THE GLASS BLOCK AND NEW PRECAST
 LINTEL, ALSO INDICATE THE SIZE OF THE LINTIL. IS IT
 4",6",8" OR 12". FBC 2104.1.5 THE MINIMUM LENGTH OF END
 SUPPORT FOR LINTELS SHALL BE 4". INDICATE THE OPENING
 DIMENTION.
  
 4)FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS.PROVIDE A WALL LEGEND INDICATING WHICH
 WALLS ARE NEW AND WHICH ONES ARE EXISTING. IN THE
 LEGEND SHOW A DETAIL OF EACH TYPE OF WALL.
  
 5)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
  
 6)STATE THE LEVEL OF ALTERATION IN ACCORDANCE WITH
 CH.3 OF THE 2004 EXISTING FBC. ARE THE INTERIOR WALLS
 CONCRETE BLOCK?
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-01-13 Cont ID  
Sent By btrobaug Date 2009-01-13 Time 09:26 Rev Time 0.00
Received By btrobaug Date 2009-01-13 Time 08:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-11-21 Cont ID  
Sent By btrobaug Date 2008-11-21 Time 15:31 Rev Time 0.00
Received By btrobaug Date 2008-11-21 Time 14:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-17 Cont ID  
Sent By btrobaug Date 2007-09-17 Time 13:13 Rev Time 0.00
Received By btrobaug Date 2007-09-17 Time 10:43 Sent To  
Notes
2007-09-17 12:22:42 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THESE COMMENTS WERE PART OF THE PREVIOUS REVIEW
 COMMENTS.
  
 2} SHEET #2 OF THE ENERGY GAUGE INPUT DATA REPORT NOTES
 A MANUAL CONTROL , IT MUST AUTOMATICALLY TURN LIGHTS
 OFF WITHIN 30 MINUTES OF ALL OCCUPANTS LEAVING THE
 SPACE PER 13-415.1ABC.1.2(A). DESIGNATE WHICH
 MANUFACTURER AND MODELS ARE BEING SPECIFIED FOR THIS
 PROJECT BY THE DESIGNER.
  
 NEW COMMENT THIS REVIEW.
  
 1} THE ARCHITECT ONLY SIGNED AND SEALED ONE SET OF
 ENERGY CALCULATIONS. ONE SET IS A COPY OF THE SIGNATURE
 AND CONTAINS NO SEAL. BOTH SETS MUST BE SIGNED AND
 SEALED PER 481 FS
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-24 Cont ID  
Sent By btrobaug Date 2007-05-24 Time 16:27 Rev Time 0.75
Received By btrobaug Date 2007-05-24 Time 15:49 Sent To  
Notes
2007-05-24 16:27:17 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} SHEET #2 OF THE ENERGY GAUGE ONLY LISTS 2
 FLUORESCENTS, AND NOTE THAT ALTHOUGH A MANUAL CONTROL
 IS LISTED, IT MUST AUTOMATICALLY TURN LIGHTS OFF WITHIN
 30 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE PER
 13-415.1ABC.1.2(A). DESIGNATE WHICH MANUFACTURER AND
 MODELS ARE BEING SPECIFIED FOR THIS PROJECT BY THE
 ENGINEER.
  
 3} THE FIXTURE TYPES AND QUANTITIES ON THE MUST MATCH
 WHAT IS INDICATED ON THE ENERGY GAUGE SHEET #2 IN THE
 ENERGY CALCULATIONS.
  
 4} SUBMIT FORMS WITH 13-415.2B OR 13-415.2.C.1
 DENSITIES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2010-10-12 Cont ID  
Sent By mgonzale Date 2010-10-12 Time 13:35 Rev Time 0.50
Received By mgonzale Date 2010-10-12 Time 13:35 Sent To  
Notes
2010-10-12 13:36:51PASSED
 STANDARD DETAILS ATTACHED.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2008-11-18 Cont ID  
Sent By mgonzale Date 2008-11-18 Time 16:21 Rev Time 1.00
Received By mgonzale Date 2008-11-18 Time 16:22 Sent To ENG
Notes
2008-11-18 16:20:29- PASSED WITH PROVISO -
  
 NEW DRIVEWAY MUST COMPLY WITH CITY OF WPB ENGINEERING
 SERVICES -ROW DIVISION.
 PLEASE CONTACT WINDEL PALMER, ROW TECHNICIAN TO OBTAIN
 LATEST DETAILS AND ROW
 PERMIT. (561) 494-1040
  
 LOCATION LOOKS ACCEPTABLE.
  
 MANUEL J GONZALEZ, PROJECT COORDINATOR
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1040
 45TH DIRECT: 561-494-1085
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-6723
 CITY HALL DIRECT: (561) 805-6327
 CITY HALL FAX: (561) 805-6731 OR 805-6676
 NEXTEL: 561-644-7301
 NEXTEL DIRECT CONNECT: 159*28165*38
 EMERGENCIES:
 CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210
 E-MAIL:
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-01-22 Cont ID  
Sent By mwennerg Date 2009-01-22 Time 14:36 Rev Time 0.00
Received By mwennerg Date 2009-01-22 Time 14:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-11-25 Cont ID  
Sent By mwennerg Date 2008-11-25 Time 15:07 Rev Time 0.00
Received By mwennerg Date 2008-11-25 Time 15:07 Sent To  
Notes
2008-11-25 15:26:15***PROVISO***
  
 7) FLOOR FINISH IS INDICATED AS CLASS A ON SHEET 3.
 FLOOR FINISH SHALL BE EITHER CLASS I OR CLASS II.
 CLEARLY PROVIDE MINIMUM INTERIOR FINISH FOR WALLS AND
 CEILING APPLICABLE FOR THIS PROJECT IN TERMS OF CLASS
 A,B ORC.
  
  
 PLANS WILL BE STAMPED WHEN RETURNED WITH THESE AND
 OTHER REVIEW CORRECTIONS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-24 Cont ID  
Sent By mawillia Date 2007-09-24 Time 10:50 Rev Time 0.00
Received By mawillia Date 2007-09-24 Time 10:16 Sent To  
Notes
2007-09-24 10:49:58******UNSAT*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 5.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 BROADWAY AVENUE, DISPLAY/SHOW THE NUMERICAL ADDRESS. AS
 PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
 SHOW ON SHEET 3
  
  
 7.BASED UPON THE ASSUMPTION THAT THIS STRUCTURE IS AN
 EXISTING BUSINESS OCCUPANCY, THE INTERIOR WALL AND
 CEILING MATERIALS SHALL BE CLASS A OR CLASS B IN EXITS
 AND EXIT ACCESS CORRIDORS, AND SHALL BE CLASS A, CLASS
 B, OR CLASS C IN ALL OTHER AREAS.BE SPECIFICFINISH
 FLOORING SHALL BE CLASS I OR CLASSII, NOT CLASS A AS
 INDICATED ON SHEET 3;NO MENTION OF THE WALL FINISH
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By mawillia Date 2007-06-11 Time 17:25 Rev Time 0.00
Received By mawillia Date 2007-06-11 Time 16:11 Sent To  
Notes
2007-06-11 17:19:04******DENIED*****
  
  
 1.THE SUBMITTED PLANS DO NOT INDICATE WHAT THE
 MODIFICATIONS TO THE EXISTING STRUCTURE ARE TO BE
 CONDUCTED.
  
 2.THE 2003 EDITION OF NFPA 101 AND THE 2004 EDITION
 OF THE FLORIDA FIRE PREVENTION CODE SHALL BE
 REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 BROADWAY AVENUE, DISPLAY/SHOW THE NUMERICAL ADDRESS. AS
 PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
 6.IF THE BUILDING OR PORTION OF THE BUILDING IS TO BE
 OCCUPIED DURING THE SCOPE OF WORK, REQUIRED MEANS OF
 EGRESS AND REQUIRED FIRE PROTECTION FEATURES SHALL BE
 OPERATIONAL AND MAINTAINED.
  
 7.BASED UPON THE ASSUMPTION THAT THIS STRUCTURE IS AN
 EXISTING BUSINESS OCCUPANCY, THE INTERIOR WALL AND
 CEILING MATERIALS SHALL BE CLASS A OR CLASS B IN EXITS
 AND EXIT ACCESS CORRIDORS, AND SHALL BE CLASS A, CLASS
 B, OR CLASS C IN ALL OTHER AREAS.BE SPECIFIC
  
 8.PROVIDE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) SATISFYING THE 75' TRAVEL DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2010-09-29 Cont ID  
Sent By jwitmer Date 2010-09-29 Time 10:37 Rev Time 0.00
Received By jwitmer Date 2010-09-29 Time 10:37 Sent To  
Notes
2010-09-29 10:38:20SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2010-07-01 Cont ID  
Sent By vmolina Date 2010-07-01 Time 10:19 Rev Time 0.00
Received By vmolina Date 2010-07-01 Time 10:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-10-26 Cont ID  
Sent By shill Date 2009-10-26 Time 17:05 Rev Time 0.00
Received By shill Date 2009-10-26 Time 17:05 Sent To  
Notes
2009-10-26 17:05:25TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-01-08 Cont ID  
Sent By adarroug Date 2009-01-08 Time 16:29 Rev Time 0.00
Received By adarroug Date 2009-01-08 Time 16:29 Sent To  
Notes
2009-01-08 16:29:54TO "COMM" BD#53

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-30 Cont ID  
Sent By adarroug Date 2008-10-30 Time 09:51 Rev Time 0.00
Received By adarroug Date 2008-10-30 Time 09:51 Sent To  
Notes
2008-10-30 09:51:44TO "COMM" BD#36--SCOPE OF WORK INCREASED TO INCLUDE
 EXTERIOR MODIFICATIONS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 09:55 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 09:55 Sent To  
Notes
2007-09-10 13:52:59TO "BOB"#1
2007-08-30 09:56:12WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-11 Cont ID  
Sent By mawillia Date 2007-06-11 Time 16:19 Rev Time 0.00
Received By mawillia Date 2007-05-17 Time 09:38 Sent To  
Notes
2007-05-24 10:15:27TO "BOB"#11
2007-05-17 09:42:19WAITING FOR "BOB"

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-01-22 Cont ID  
Sent By rkussner Date 2009-01-22 Time 11:30 Rev Time 0.00
Received By rkussner Date 2009-01-22 Time 11:02 Sent To  
Notes
2009-01-22 12:03:19***LANDSCAPE REVIEW PASSED WITH PROVISO:
  
 1. A SEPARATE IRRIGATION PERMIT IS REQUIRED.
  
 2. LANDSCAPE PLAN SHALL BE REVISED AND APPROVED TO
 REFLECT CHANGES TO -LAYOUT SHOWN ON SITE PLAN PRIOR TO
 THE ISSUANCE OF C/O.
  
 3. SIX (6) RUBRA SHALL BE CENTERED IN EXPANDED
 LANDSCAPE AREA ADJACENT TO PARKING.
  
 4. ONE (1) ORANGE GEIGER TREE SHALL BE CENTERED WITHIN
 THAT EXPANDED LANDSCAPE AREA.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-11-06 Cont ID  
Sent By rkussner Date 2008-11-06 Time 15:55 Rev Time 0.00
Received By rkussner Date 2008-11-06 Time 15:54 Sent To  
Notes
2008-11-06 16:09:59***LANDSCAPE REVIEW FAILED***
  
 PROVIDE SOD AND IRRIGATION IN RIGHT-OF-WAY ADJACEN TO
 53RD STREET.
  
 IF YOU HAVE ANY QUESTIONS REGARDING THIS COMMENT,
 PLEASE CONTACT ROBERT KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-10-30 Cont ID  
Sent By tgordon Date 2008-10-30 Time 14:43 Rev Time 0.45
Received By tgordon Date 2008-10-30 Time 14:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-09-11 Cont ID  
Sent By tgordon Date 2007-09-11 Time 08:51 Rev Time 0.25
Received By tgordon Date 2007-09-11 Time 08:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-24 Cont ID  
Sent By tgordon Date 2007-05-24 Time 11:40 Rev Time 0.40
Received By tgordon Date 2007-05-24 Time 11:40 Sent To  
Notes
2007-05-24 11:48:28*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) SHOW ON MECHANICAL PLANS, OUTDOOR AIR CALCULATIONS
 AND PROVIDE FOR OUTDOOR AIR, SEE 2004 FBC/M 401.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-01-27 Cont ID  
Sent By kstevens Date 2009-01-27 Time 08:51 Rev Time 0.00
Received By kstevens Date 2009-01-27 Time 08:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-11-14 Cont ID  
Sent By kstevens Date 2008-11-14 Time 08:02 Rev Time 0.00
Received By kstevens Date 2008-11-14 Time 08:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-09-15 Cont ID  
Sent By jleech Date 2007-09-15 Time 09:51 Rev Time 0.00
Received By jleech Date 2007-09-15 Time 09:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-07 Cont ID  
Sent By jleech Date 2007-06-07 Time 10:11 Rev Time 0.00
Received By jleech Date 2007-06-07 Time 09:58 Sent To  
Notes
2007-06-07 10:32:39DENIED;
 1. PLUMBING RISER DIAGRAM;BACK TO BACK TOILETS CAN
 NOT BE INSTALLED AS DRAWN. SEE SECTION 706.3.
 2. BREAK SINK SHALL MEET THE FBC-2004 ACCESSIBLITY
 CODE. CHANGE THE KITCHEN ELEVATION TO SHOW THE
 FOLLOWING INFORMATION;
 11-4.24.2 HEIGHT OF SINK RIMNO HIGHER THAN 34"
 AFF.
 11-4.24.3 KNEE CLEARANCE, 27" HIGH, 30" WIDE
 AND 19" DEEP UNDER SINK. ( NO CABINET DOORS)
 11-4.24.4 SINK SHALL BE A MAX. OF 6 1/2 " DEEP.
 ( SPEC. SINK ON PLANS)
 11-4.24.5 SHOW CLEAR FLOO SPACE ON FLOOR PLAN.
 11-4.24.6 INSULATE PLUMBING PIPES AS REQUIRED.
 11-4.24.7 LEVER OPERATED FAUSET IS REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 5 Status P Date 2009-10-29 Cont ID  
Sent By eschneid Date 2009-10-29 Time 16:08 Rev Time 0.10
Received By eschneid Date 2009-10-29 Time 16:08 Sent To B
Notes
2009-10-29 16:09:23ASPHALT TO CONCRETE PARKING REVISION.

Review Stop Z ZONING
Rev No 4 Status P Date 2009-01-21 Cont ID  
Sent By eschneid Date 2009-01-21 Time 17:25 Rev Time 0.50
Received By eschneid Date 2009-01-21 Time 17:25 Sent To  
Notes
2009-01-21 17:34:38PASSED W/PROVISO
  
 1) REVISE GAZEBO SIZE OR LOCATION TO PROVIDE FOR
 ACCESSABLE ROUTE TO THE BUILDING AT THE REAR OF THE
 PROPERTY. STAFF STILL RECOMMENDS A STATUE, FOUNTAIN OR
 LANDSCAPE TREATMENT AS THE FOCAL POINT TO TEMINATE THE
 PEDESTRIAN WALKWAY BEHIND THE GATE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status F Date 2008-11-06 Cont ID  
Sent By adavila Date 2008-11-06 Time 16:45 Rev Time 0.00
Received By adavila Date 2008-11-06 Time 16:45 Sent To  
Notes
2008-11-06 16:46:16PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. THE PARKING SPACES IN THE WESTERN PARKING ROW SHALL
 BE REDUCED TO 8.5 FEET TO PROVIDE THE LAST PARKING
 SPACE AMPLE BACK-OUT AREA AS IT CURRENTLY SHOWS BAKING
 OUT INTO THE PROPOSED GAZEBO.
  
 2. PROVIDE CIRCULATION DETAILS OF THE GAZEBO TO ENSURE
 ADA ACCESSIBILITY. PLEASE NOTE THAT WHILE STAFF
 APPRECIATES THE GAZEBO AS A FOCAL POINT TO MEET THE
 CONDITIONS OF THE FINAL ORDER DATED AUGUST 7, 2009,
 STAFF RECOMMENDS THAT A STATUTE, FOUNTAIN OR LANDSCAPE
 TREATMENT BE CONSIDERED AT THE END OF THE PEDESTRIAN
 WALKWAY DUE TO THE SITE RESTRICTIONS.
  
 3. THE DECORATIVE ELEMENTS ON TOP OF THE COLUMNS NEXT
 TO THE GATE ALONG BROADWAY AVENUE SHALL NOT EXCEED 0.6
 FEET FROM THE TOP OF THE COLUMNS (10 PERCENT OF THE
 PERMITTED HEIGHT FOR WALLS AND FENCES PER BMUD
 REGULATIONS).
  
 4. PER THE APPROVED BULLNOSE AWNING WAIVER LETTER DATED
 AUGUST 7, 2008, THE BULLNOSE AWNINGS SHALL PROJECT A
 MINIMUM OF 4 FEET FROM THE BUILDING FA?ADE.
  
 5. ALL SIGNS SHALL BE APPROVED ON A SEPARATE PERMIT,
 AND SHALL COMPLY WITH THE BMUD REGULATIONS OUTLINED IN
 SECTION 94-221(E) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2007-09-19 Cont ID  
Sent By adavila Date 2007-09-19 Time 15:43 Rev Time 0.00
Received By adavila Date 2007-09-17 Time 13:53 Sent To  
Notes
2007-09-19 15:44:22PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 2. (REPEAT COMMENT) PROVIDE CLEAR GLAZING AREA
 PERCENTAGE.
  
 3. (REPEAT COMMENT)PROVIDE WINDOW AND OPENING DETAILS
 MEETING SECTION 94-221(D)(6) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS) FOR ALL PROPOSED
 WINDOWS AND OPENINGS.
  
 4. (REPEAT COMMENT)FINAL FLOOR TO CEILING HEIGHT
 DIMENSION SHALL BE NO LESS THAN THE EXISTING FLOOR TO
 CEILING HEIGHT DIMENSION.FLOOR TO CEILING HEIGHT
 SHALL BE NO LESS THAN 9 FEET 3 INCHES AND 9 FEET 1 INCH
 AS INDICATED ON SHEET 1 OF 3.PLEASE CLARIFY WHICH
 SECTIONS OF THE BUILDING HAVE A CEILING HEIGHT OF 9
 FEET 3 INCHES AND 9 FEET 1 INCH.
  
 5. PLEASE CLARIFY WHAT IS TO BE REMOVED ON THE
 NORTHWEST CORNER OF THE BUILDING.
  
 6. PURSUANT TO SECTION 94-221(B)(1) OF THE ZLDRS,
 BUILDING LOCATED AT PRIMARY INTERSECTIONS SHALL BE
 BUILT ALONG A MINIMUM OF 80% OF THE BROADWAY FRONTAGE
 LINE, WITH A SETBACK NO GREATER THAN 5 FEET.THE
 EXISTING BUILDING DOES NOT COMPLY WITH THIS PROVISION.
 THEREFORE, THE MAIN ENTRANCE ALONG THE EAST SIDE OF THE
 BUILDING MAY NOT BE RECESSED IN.
  
 7. PURSUANT TO SECTION 94-485(G) OF THE ZLDRS, CURBS,
 WHEEL STOPS, OR BOLLARDS SHALL BE INSTALLED TO PROTECT
 LANDSCAPE AREAS, PEDESTRIAN AREA, BUILDINGS AND
 PROPERTY LINES.A CURB SHALL BE PROVIDED ALONG SOUTH
 SIDE OF THE SMALL BUILDING AS WELL AS THE PEDESTRIAN
 WALKWAYS.
  
 8. PURSUANT TO SECTION 94-221(F)(3) OF THE ZLDRS, ALL
 SURFACE PARKING AREAS SHALL BE CONCEALED WITH A
 STREETWALL ALONG ALL STREET FRONTAGES.PLEASE NOTE
 THAT STREETWALLS AND FENCES BUILT IN LINE WITH THE
 FRONT BUILDING FACADE SHALL BE 34 TO 72 INCHES IN
 HEIGHT.STREETWALLS AND FENCES IN FRONT OF THE
 BUILDING FACADE SHALL BE 34 TO 42 INCHES IN HEIGHT.
 STREETWALLS OR FENCES SHALL CONSIST OF A MATERIAL
 MATCHING THE ADJACENT BUILDING OR ONE OF THE FOLLOWING:
 INDIGENOUS ROCK; BLOCK AND STUCCO; DECORATIVE METAL; OR
 PAINTED, STAINED OR PRESSURE TREATED WOOD PICKETS.
 CHAIN LINK, BARBED WIRE, RAZOR WIRE, ELECTRONIC
 ELEMENTS OR OTHER HAZARDOUS MATERIALS ARE PROHIBITED
 [SECTION 94-221(D)(2) OF THE ZLDRS].
  
 9. PURSUANT TO SECTION 94-485(J) OF THE ZLDRS, PARKING
 SPACES AT A 90 DEGREE ANGLE SHALL BE NO LESS THAN 8
 FEET 6 INCHES IN WIDTH.IN ADDITION, PER SECTION
 94-485(N), IF THE TOTAL PARKING REQUIREMENTS OF ANY USE
 OR STRUCTURE IS LESS THAN 20 SPACES, NO SMALL CAR
 SPACES ARE PERMITTED.
  
 10. PURSUANT TO SECTION 94-485(J) OF THE ZLDRS, THERE
 SHALL BE 12 INCHES BETWEEN THE DOUBLE STRIPING (SEE
 ATTACHED DIAGRAM FOR REFERENCE).
  
 11. HANDICAP SYMBOL SHALL BE 3 FEET OR 5 FEET HIGH AND
 SHALL BE PAINTED IN WHITE.
  
 12. HANDICAP SYMBOL SHALL BE 2 FEET FROM THE OPEN END
 OF THE PARKING SPACE.
  
 13. PURSUANT TO SECTION 94-443(B)(1) OF THE ZLDRS, A 5
 FOOT LANDSCAPE BUFFER SHALL BE INSTALLED ALONG THE
 ENTIRE EDGE OF A PROPERTY ADJACENT TO A PUBLIC
 THOROUGHFARE AND OTHER NONRESIDENTIAL ZONING DISTRICTS.
 A LANDSCAPE BUFFER SHALL BE PROVIDED ALONG THE NORTH
 PROPERTY LINE.
  
 14. PURSUANT TO SECTION 94-443(C)(3)(A) OF THE ZLDRS,
 EACH ROW OF PARKING SPACE SHALL BE TERMINATED BY
 LANDSCAPE ISLANDS OF NO LESS THAN 5 FEET IN WIDTH AND
 NOT LESS THAN THE LENGTH OF THE ADJACENT PARKING STALL.
 A TERMINAL ISLAND SHALL BE PLACED ON THE NORTH END OF
 BOTH PARKING ROWS.
  
 15. PURSUANT TO SECTION 94-443(C)(3)(A) OF THE ZLDRS,
 TERMINAL ISLANDS SHALL BE 5 FEET WIDE BY THE DEPTH OF
 THE PARKING SPACE.THE TERMINAL ISLAND AT THE SOUTH
 END OF THE WEST PARKING ROW SHALL COMPLY WITH THIS
 REQUIREMENT.
  
 16. PURSUANT TO SECTION 94-443(C)(5)(A) OF THE ZLDRS,
 LANDSCAPE AREAS SHALL BE SEPARATED FROM VEHICULAR USE
 AREAS BY NONMOUNTABLE, CONCRETE CURBING OF THE TYPE
 CHARACTERIZED AS "TYPE D".A TYPE D CURB SHALL BE
 PROVIDED ON THE LANDSCAPE BUFFER ALONG THE SOUTH
 PROPERTY LINE.
  
 17. PURSUANT TO SECTION 94-443(C)(5)(B) OF THE ZLDRS,
 WHEEL STOPS SHALL BE 2 FEET FROM THE CURB TO THE BACK
 OF THE WHEEL STOP, AND SHALL BE 6FEET WIDE AND 6
 INCHES TALL.
  
 18. ALL TREES LOCATED WITHIN THE VISIBILITY TRIANGLE
 SHALL BE APPROVED IN WRITING BY THE ENGINEERING
 SERVICES DEPARTMENT.
  
 19. ALL TREES SHALL BE PLANTED PURSUANT TO THE CITY OF
 WEST PALM BEACH SUSTAINABLE PLANTING PLANS (SEE
 ATTACHED DIAGRAM FOR REFERENCE).
  
 20. PLEASE STATE THE REQUIRED DISTANCE SEPARATION FROM
 THE NORTH PROPERTY LINE BASED ON THE NUMBER OF OPENINGS
 ON THE NORTH BUILDING FACADE.
  
 21. PLEASE NOTE THE PER SECTION 94-305(B)(4) OF THE
 ZLDRS, MECHANICAL EQUIPMENT (INCLUDING A/C UNITS) MAY
 NOT ENCROACH MORE THAN 4 FEET INTO A SETBACK.
  
 22. THE EXISTING DUMPSTER MAY NOT BE USED BY BOTH
 PROPERTIES WITHOUT A UNITY OF TITLE.PLEASE CONTACT
 THE ENGINEERING SERVICES DEPARTMENT FOR DUMPSTER
 LOCATION AND TRASH PICK-UP ALTERNATIVE OPTIONS.PLANS
 STAMPED APPROVED BY THE ENGINEERING SERVICES DEPARTMENT
 SHALL BE SUBMITTED FOR DUMPSTER SIZE AND LOCATION.
 PLEASE NOTE THAT IF BOTH PROPERTIES ARE UNIFIED, THE
 NORTHERN PROPERTY SHALL ALSO COMPLY WITH THE LANDSCAPE
 REGULATIONS.
  
 23. ALL NEW FENCES/WALLS SHALL BE APPROVED ON A
 SEPARATE PERMIT.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-06 Cont ID  
Sent By adavila Date 2007-06-06 Time 17:22 Rev Time 0.00
Received By adavila Date 2007-06-01 Time 17:15 Sent To  
Notes
2007-06-06 17:22:32PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY.
  
 2. PER SECTION 94-221(D)(5) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, STOREFRONTS ARE REQUIRED ALONG
 FRONTAGE LINES AND SHALL BE DIRECTLY ACCESSIBLE FROM
 SIDEWALKS.EACH STOREFRONT MUST HAVE CLEAR GLAZED
 AREAS, ALONG A MINIMUM OF 70% OF ITS FA?ADE LENGTH,
 BETWEEN TWO AND EIGHT FEET FROM THE GROUND.EXISTING
 WINDOW AND DOOR OPENINGS ON THE EAST BUILDING FA?ADE
 MAY NOT BE BLOCKED IN.
  
 3. PER SECTION 94-221(D)(4) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, ALL BUILDINGS SHALL HAVE THEIR
 PRINCIPAL PEDESTRIAN ENTRANCES FACING THE BROADWAY
 FRONTAGE LINE.AT LEAST ONE DOOR SHALL REMAIN ON THE
 BROADWAY FRONTAGE.
  
 4. PROVIDE CLEAR GLAZING AREA PERCENTAGE.
  
 5. PROVIDE WINDOW AND OPENING DETAILS MEETING SECTION
 94-221(D)(6) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR ALL PROPOSED WINDOWS AND OPENINGS.
  
 6. PROVIDE EXISTING WALL TO CEILING HEIGHT DIMENSION.
  
  
 7. PROVIDE FINAL WALL TO CEILING HEIGHT DIMENSION.
 PLEASE NOTE THAT THE FINAL WALL TO CEILING HEIGHT
 DIMENSION SHALL BE NO LESS THAN THE EXISTING WALL TO
 CEILING HEIGHT DIMENSION.
  
 8. PROVIDE TOTAL VALUE OF THE EXTERIOR RENOVATIONS.
 PLEASE NOTE THAT PER SECTION 94-219(D)(9)(A) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS, ALL PROPERTIES
 SHALL BE BROUGHT INTO COMPLIANCE WITH THE LANDSCAPE
 REGULATIONS IN ARTICLE XIV OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, CURRENTLY WITH EXTERIOR
 BUILDING IMPROVEMENTS EXCEEDING $10,000.00.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.