Plan Review Details - Permit 07050407
Plan Review Stops For Permit 07050407
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-05-27 Cont ID  
Sent By shill Date 2008-05-27 Time 12:54 Rev Time 0.00
Received By shill Date 2008-05-27 Time 12:54 Sent To  
Notes
2008-05-27 12:54:48RESTAMP - PRODUCT APPROVALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-12-18 Cont ID  
Sent By shill Date 2007-12-18 Time 16:34 Rev Time 0.00
Received By shill Date 2007-12-18 Time 16:34 Sent To  
Notes
2007-12-18 16:35:55NOA 03-0501.05, ENHANCED FASTENING & APPROVED ASSEMBLY
 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-24 Cont ID  
Sent By shill Date 2007-09-24 Time 14:32 Rev Time 0.00
Received By shill Date 2007-09-24 Time 14:32 Sent To  
Notes
2007-09-24 14:32:45****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)IMPACT RATED PRODUCTS WERE SUBMITTED.PLEASE
 REMOVE REFERENCES TO HURRICANE SHUTTERS FROM THE PLAN
 AS THEY ARE IN CONFLICT WITH OTHER PAPERWORK PROVIDED.
  
  
 2.)FOR THE FLAT DECK ROOF, INDICATE WHICH APPROVED
 ASSEMBLY YOU ARE USING.SPECIFY ENHANCED FASTENING FOR
 ZONES 2 AND 3.
  
 3.)SHOW HOW THE PARAPET WALL WILL RESIST WIND LOADS
 OF FBC R CHAPTER 3.HOW WILL THE BOLTS KEEP THE WALL
 FROM BEING PUSHED OVER?NO OTHER STRAPPING,
 REINFORCEMENT, OR BRACING IS SHOWN.PROVIDE
 CALCULATIONS.
  
 3RD REVIEW; BRACING WAS ADDED ON ONE SIDE.THIS
 ADDRESSES WIND GOING ONE DIRECTION; PLEASE ADDRESS WIND
 LOADS FROM THE SOUTH.ALSO, IT APPEARS THAT THIS
 BRACING WAS ADDED, BUT NOT CLOUDED.ALL CHANGES ARE TO
 BE CLEARLY INDICATED ON THE PLAN.
  
 4.)ADDRESSED.
  
 NEW COMMENT:
  
 5.)SHOW DIMENSION FROM GRADE TO BOTTOM OF FOOTING,
 FBC R 403.1.4.
  
 A SET HAS BEEN RETAINED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-27 Cont ID  
Sent By shill Date 2007-07-27 Time 15:49 Rev Time 0.00
Received By shill Date 2007-07-27 Time 15:49 Sent To  
Notes
2007-07-27 15:53:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)IMPACT PROTECTION IS NOT REQUIRED FOR THIS JOB,
 FBC R301.2.1.2.IF YOU ARE USING REMOVABLE SHUTTERS
 FOR THE WINDOW, PROVIDE HURRICANE SHUTTER PRODUCT
 APPROVAL AND COMPLETE THE ATTACHED INSTALLATION
 SCHEDULE OR PROVIDE THE INFORMATION IN ANOTHER FORMAT.
  
 2.)FOR THE FLAT DECK ROOF, INDICATE WHICH APPROVED
 ASSEMBLY YOU ARE USING.SPECIFY ENHANCED FASTENING FOR
 ZONES 2 AND 3.
  
 NEW COMMENT:
  
 3.)SHOW HOW THE PARAPET WALL WILLR RESIST WIND LOADS
 OF FBC R CHAPTER 3.HOW WILL THE BOLTS KEEP THE WALL
 FROM BEING PUSHED OVER?NO OTHER STRAPPING,
 REINFORCEMENT, OR BRACING IS SHOWN.PROVIDE
 CALCULATIONS.
  
 4.)SPECIFY TYPE OF FASTENER, NOT "A.B."
  
 A SET HAS BEEN RETAINED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-04 Cont ID  
Sent By shill Date 2007-06-04 Time 11:27 Rev Time 0.00
Received By shill Date 2007-06-04 Time 11:27 Sent To Z
Notes
2007-06-04 12:00:31****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE A SITE PLAN SHOWING THE PROPOSED
 IMPROVEMENT, TO SCALE, WITH DISTANCE TO THE PROPERTY
 LINES AND THE DISTANCE BETWEEN THE PROPOSED GARAGE AND
 THE EXISTING HOUSE, FBC*106.IF THE DISTANCE TO THE
 PROPERTY LINE IS LESS THAN 6', SHOW THE LOCATION OF THE
 BUILDING ON THE ADJACENT PROPERTY FBC R302.2.
  
 2.)DECLARE WIND DESIGN CRITERIA, FBC R301 INCLUDING
 COMPONENT & CLADDING PRESSURES FOR THE ROOF.
  
 3.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 4.)FRONT WALL SECTION, WALL SECTION, SPECIFIES
 SHEATHING NAILING AS 6"OC.THIS IS IN CONFLICT WITH
 THE SCHEDULE (PLYWOOD SHEATHING FASTENER SCHEDULE) AND
 WITH FBC R2304.9.1.
  
 5.)THE GARAGE DOOR HAS A DESIGN PRESSURE LIMITATION
 OF +46.6, REQUIREMENT PER PLAN IS +49.
  
 6.)IMPACT PROTECTION IS REQUIRED, FBC R301.2.1.2.IF
 YOU ARE USING REMOVABLE SHUTTERS FOR THE WINDOW,
 PROVIDE HURRICANE SHUTTER PRODUCT APPROVAL AND COMPLETE
 THE ATTACHED INSTALLATION SCHEDULE OR PROVIDE THE
 INFORMATION IN ANOTHER FORMAT.
  
 7.)FOR THE FLAT DECK ROOF, INDICATE WHICH APPROVED
 ASSEMBLY YOU ARE USING.SPECIFY ENHANCED FASTENING FOR
 ZONES 2 AND 3.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-05-10 Cont ID  
Sent By ssherman Date 2007-05-10 Time 16:29 Rev Time 0.00
Received By ssherman Date 2007-05-10 Time 16:29 Sent To  
Notes
2007-05-10 16:29:40HISTORICAL APPROVAL PER GALINA JUDGE NO FEE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-16 Cont ID  
Sent By adarroug Date 2008-05-16 Time 09:56 Rev Time 0.00
Received By adarroug Date 2008-05-16 Time 09:56 Sent To B
Notes
2008-05-16 09:56:24TO "SHILL" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-06 Cont ID  
Sent By adarroug Date 2007-12-06 Time 10:40 Rev Time 0.00
Received By adarroug Date 2007-12-06 Time 10:40 Sent To Z
Notes
2007-12-06 10:40:30TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-18 Cont ID  
Sent By adarroug Date 2007-09-18 Time 15:55 Rev Time 0.00
Received By adarroug Date 2007-09-18 Time 15:55 Sent To Z
Notes
2007-09-18 15:55:26TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 15:20 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 15:20 Sent To Z
Notes
2007-07-18 15:21:14TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-07 Cont ID  
Sent By adarroug Date 2007-06-05 Time 09:14 Rev Time 0.00
Received By adarroug Date 2007-05-15 Time 08:57 Sent To  
Notes
2007-05-15 08:57:52TO "MISC" BOX#1

Review Stop Z ZONING
Rev No 4 Status P Date 2007-12-10 Cont ID  
Sent By choops Date 2007-12-10 Time 09:37 Rev Time 0.00
Received By choops Date 2007-12-10 Time 09:37 Sent To B
Notes
2007-12-10 09:33:02***APPROVED - RESUB #3***
  
 RESTAMPED PLANS
  
  
  
 SENT TO "B" - SH

Review Stop Z ZONING
Rev No 3 Status P Date 2007-09-20 Cont ID  
Sent By choops Date 2007-09-20 Time 16:02 Rev Time 0.00
Received By choops Date 2007-09-20 Time 16:02 Sent To B
Notes
2007-12-10 09:32:48***APPROVED - RESUB #2***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-07-20 Cont ID  
Sent By choops Date 2007-07-20 Time 17:36 Rev Time 0.00
Received By choops Date 2007-07-20 Time 17:36 Sent To B
Notes
2007-07-20 17:41:52***FAILED - RESUB #1***
  
  
 1)RESUBMITTED PLANS NEED TO BE RE-APPROVED/STAMPED
 BY HISTORIC PRESERVATION (5TH FLOOR CITY HALL)
  
 2)PROPOSED GARAGE DOES NOT MEET MINIMUM SETBACK
 REQUIREMENT FOR ACCESSORY STRUCTURES.REQUIRED REAR
 AND SIDE SETBACKS ARE A MINIMUM OF 5' AS PER THE CITY
 OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS, SECTION 94-304(B)(2)
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-05 Cont ID  
Sent By choops Date 2007-06-05 Time 10:31 Rev Time 0.00
Received By choops Date 2007-06-05 Time 10:31 Sent To I
Notes
2007-06-05 10:37:14***FAILED***
  
  
 1)PLEASE SHOW SETBACK DIMENSIONS FROM PROPOSED
 GARAGE TO PROPERTY LINES.
 NOTE: MUST BE A MINIMUM OF 10.2 FT. FROM REAR PROPERTY
 LINE, AND A MINIMUM OF 5 FT FROM SIDE PROPERTY LINE.
  
 2)PLEASE SHOW THE DISTANCE FROM THE RESIDENCE TO THE
 PROPOSED GARAGE.
 NOTE:MINIMUM SETBACK DIMENSIONS LISTED ABOVE APPLY IF
 GARAGE IS 6 FT. OR MORE FROM PRIMARY STRUCTURE)
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720