Plan Review Details - Permit 07050402
Plan Review Stops For Permit 07050402
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-10-21 Cont ID  
Sent By shill Date 2007-10-21 Time 14:27 Rev Time 0.00
Received By shill Date 2007-10-21 Time 14:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By shill Date 2007-06-13 Time 15:38 Rev Time 0.00
Received By shill Date 2007-06-13 Time 15:38 Sent To  
Notes
2007-06-13 15:38:49****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)SPECIFY ANCHOR, DIAMETER AND LENGTH.FBC R 301

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-12 Cont ID  
Sent By btrobaug Date 2007-10-12 Time 16:09 Rev Time 0.00
Received By btrobaug Date 2007-10-12 Time 16:09 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-21 Cont ID  
Sent By btrobaug Date 2007-05-21 Time 11:54 Rev Time 0.33
Received By btrobaug Date 2007-05-21 Time 10:55 Sent To G
Notes
2007-05-21 11:54:40 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} PROVIDE A RISER DIAGRAM SHOWING ELECTRICAL
 CONNECTION OF ALL SERVICE AND GENERATOR EQUIPMENT
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3FBC.
  
 3} 702.5 CAPACITY AND RATING. AN OPTIONAL STANDBY
 SYSTEM SHALL HAVE ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE OPERATED AT ONE
 TIME.PROVIDE A LOAD CALCULATION SHOWING COMPLIANCE
 WITH THIS ARTICLE.
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE
 PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE
 SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-10-19 Cont ID  
Sent By mperson Date 2007-10-19 Time 11:15 Rev Time 0.00
Received By mperson Date 2007-10-19 Time 11:15 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-05-24 Cont ID  
Sent By mperson Date 2007-05-24 Time 16:34 Rev Time 0.45
Received By mperson Date 2007-05-24 Time 16:34 Sent To B
Notes
2007-05-24 16:57:28DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE REFERENCE ZONING COMMENT AND CORRECT.A GAS
 PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING FOR
 THE GENERATOR LOCATION.
  
 2. PLEASE CLEARLY INDICATE THE ABOVE GROUND PIPING
 MATERIAL AND CORRESPONDING LENGTHS OF CUT SECTIONS ON
 THE RESUBMITTED GAS ISOMETRIC OFTHE PROPOSED
 GENERATOR PER FBC-2004 FUEL GAS.
  
 3. PLEASE CLEARLY INDICATE THE SHUT OFF VALVE AND MP
 REGULATOR FOR THE PROPOSED GENERATOR ON THE RESUBMITTED
 GAS ISOMETRIC PER FBC-2004 FUEL GAS, SECTION 409.4 MP
 REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 4. PLEASE CLEARLY INDICATE THE GAS TYPE (LP OR
 NATURAL) ON THE RESUBMITTED GAS ISOMETRIC.
  
 5. PLEASE SUBMIT MANUFACTURER SPECIFICATION OF THE
 PROPOSED GENERATOR TO VERIFY GAS TYPE AND BTU LOAD AND
 INSTALLATION INSTRUCTIONS TO VERIFY SETBACKS TO
 ADJACENT STRUCTURES.
  
 6. PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS OF THE
 PROPOSED 2 PSI TO 0.5 PSI MP REGULATOR INDICATING THE
 MANUFACTURER'S NAME, MODEL NUMBER, MAXIMUM LOAD
 CAPACITY AND SHOW A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY (NRTL).
  
 7. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING (GAS ISOMETRIC) SHALL CLEARLY PRINT AND
 SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 10:05 Rev Time 0.00
Received By adarroug Date 2007-10-10 Time 10:05 Sent To Z
Notes
2007-10-10 10:05:45TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-18 Cont ID  
Sent By adarroug Date 2007-05-18 Time 13:17 Rev Time 0.00
Received By adarroug Date 2007-05-18 Time 13:17 Sent To E
Notes
2007-05-18 13:17:49TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-21 Cont ID  
Sent By shill Date 2007-10-21 Time 14:27 Rev Time 0.00
Received By shill Date 2007-05-14 Time 14:40 Sent To  
Notes
2007-05-14 14:40:43TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-10-19 Cont ID  
Sent By tgordon Date 2007-10-19 Time 12:05 Rev Time 0.20
Received By tgordon Date 2007-10-19 Time 12:05 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-18 Cont ID  
Sent By tgordon Date 2007-05-18 Time 14:21 Rev Time 0.15
Received By tgordon Date 2007-05-18 Time 14:21 Sent To E
Notes
2007-05-18 14:22:30*** DENIED ***
 1) SEE ZONING REVIEV NOTE, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-10-12 Cont ID  
Sent By choops Date 2007-10-12 Time 15:45 Rev Time 0.00
Received By choops Date 2007-10-12 Time 15:45 Sent To E
Notes
2007-10-12 15:46:05***APPROVED - RESUB #1***
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-15 Cont ID  
Sent By choops Date 2007-05-15 Time 16:03 Rev Time 0.00
Received By choops Date 2007-05-15 Time 16:03 Sent To I
Notes
2007-05-15 16:04:21***FAILED***
  
  
 1)PLEASE PROVIDE 2 COPIES OF ACTUAL SURVEYS
 INDICATING SCOPE OF WORK, DIMENSIONS OF SETBACKS TO
 PROPERTY LINES FROM GENERATOR.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720