Plan Review Stops For Permit 07050377 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2007-05-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2007-05-23 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-05-23 |
Time |
16:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-05-11 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2007-05-11 |
Time |
10:42 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-05-11 |
Time |
10:42 |
Sent To |
|
|
Notes |
2007-05-11 10:57:39 | DENIED BY BUILDING | | | | 1) THE WRONG FLORIDA PRODUCT APPROVAL COVERSHEET WAS | | SUBMITTED. THE CORRECT ONE FOR NOA 03-0501.02 IS FL | | 617-R1. | | | | 2) SPECIFY WHICH ONE OF THE FASTENING OPTIONS ON PAGE | | 28 OF THE NOA WILL BE USED. CIRCLE THE APPROPRIATE ONE | | ON THE NOA. | | | | 3) THE LETTER FOR ENHANCED FASTENING THAT WAS SUBMITTED | | IS NOT ACCEPTABLE. THE NUMBER OF ROWS OF NAILS IS NOT | | SPECIFIED. FOR EXAMPLE : FASTENERS AT 4" OC AT THE LAP | | ANDAT 4" OC IN TWO ROWS IN THE FIELD. THE LETTER | | INCORRECTLY SPECIFIES GENERAL LIMITATION #9,WHICH | | DOES NOT ALLOW DESIGN PRESSURES TO BE INCREASED BY | | ENHANCED FASTENING. REVISE TO REFERENCE LIMITATION | | NUMBER 7. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|
|
|