Plan Review Details - Permit 07050315
Plan Review Stops For Permit 07050315
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-05-22 Cont ID  
Sent By rmcdouga Date 2007-05-22 Time 13:36 Rev Time 0.00
Received By rmcdouga Date 2007-05-22 Time 13:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-09 Cont ID  
Sent By rmcdouga Date 2007-05-09 Time 14:27 Rev Time 0.00
Received By rmcdouga Date 2007-05-09 Time 14:27 Sent To  
Notes
2007-05-09 14:44:46DENIED BY BUILDING
  
 1)CIRCLE THE APPROVED SYSTEM THAT WILL BE INSTALLED
 AND CIRCLE THE FASTENING OPTION AND ITS DESIGN PRESSURE
 ON THE NOA.
  
 2) THE LETTER FOR ENHANCED FASTENING THAT WAS SUBMITTED
 IS NOT CLEAR AND SHOULD BE ADDRESSED TO THE CITY OF
 WEST PALM BEACH CONSTRUCTION SERVICES DEPARTMENT. THE
 LETTER NEEDS TO SPECIFY THE FASTENER SPACING FOR THE
 SIDE LAP AND THE CENTER ROWS. SPECIFY THE NUMBER OF
 CENTER ROWS. THE HANDWRITTEN CHANGE ON THE LETTER FROM
 2" TO 4" LAP IS NOT ACCEPTABLE. THE LETTER SHOULD HAVE
 THE CORRECT SIDE LAP SPECIFIED. THE LETTER SHOULD ALSO
 INCLUDE THE NOA NUMBER OF THE ROOFING MATERIAL IT IS
 ADDRESSING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-17 Cont ID  
Sent By adarroug Date 2007-05-17 Time 15:07 Rev Time 0.00
Received By adarroug Date 2007-05-17 Time 15:06 Sent To B
Notes
2007-05-17 15:07:14TO "RMCDOUGAL" DESK/RESUB