Plan Review Details - Permit 07050219
Plan Review Stops For Permit 07050219
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-17 Cont ID  
Sent By shill Date 2007-09-17 Time 18:45 Rev Time 0.00
Received By shill Date 2007-09-17 Time 18:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-26 Cont ID  
Sent By shill Date 2007-07-26 Time 09:38 Rev Time 0.00
Received By shill Date 2007-07-26 Time 09:38 Sent To  
Notes
2007-07-26 09:41:55****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 COMMENT FROM PREVIOUS LIST:
  
 _XX_9.DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS FAC61G15-23.002.YOU MAY USE WIND
 LOADS IN THE BUILDING CODE FOR BUILDINGS UNDER 60', BUT
 IF YOU WOULD LIKE FOR ENGINEERED WIND LOADS TO BE A
 PART OF YOUR PERMIT PACKAGE, ORIGINALS ARE REQUIRED IF
 PREPARED BY AN ENGINEER.
  
 THE SPAN TUBE ENGINEERING AND ONE SET OF WIND LOADS ARE
 NOT SEALED.
  
 NEW COMMENT:
  
 OPENING 1, MOUNTING TYPE B IS FOR CONCRETE ONLY PER
 PRODUCT APPROVAL.SEE SHEET 16 FOR MOUNTINGS FOR WOOD
 SUBSTRATE.
  
 CHECK ALL OPENINGS.THERE MAY BE OTHER ERRORS AS I
 ONLY SPOT CHECK.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-31 Cont ID  
Sent By shill Date 2007-05-31 Time 09:48 Rev Time 0.00
Received By shill Date 2007-05-31 Time 09:48 Sent To  
Notes
2007-05-31 09:52:01****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED,
 FS713.13.
  
 ____2.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002.
  
 ____3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
  
 _XX_5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.PLEASE
 CONTACT ME IN REGARDS TO USE OF THE ALUMINUM SPAN
 TUBE.
  
 ____6.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER.
  
 ____7.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 _XX_8.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 4
 ABOVE.
  
 _XX_9.DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS FAC61G15-23.002.YOU MAY USE WIND
 LOADS IN THE BUILDING CODE FOR BUILDINGS UNDER 60', BUT
 IF YOU WOULD LIKE FOR ENGINEERED WIND LOADS TO BE A
 PART OF YOUR PERMIT PACKAGE, ORIGINALS ARE REQUIRED IF
 PREPARED BY AN ENGINEER.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 14:14 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 14:14 Sent To B
Notes
2007-09-13 14:14:56TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-13 Cont ID  
Sent By adarroug Date 2007-07-13 Time 10:39 Rev Time 0.00
Received By adarroug Date 2007-07-13 Time 10:39 Sent To B
Notes
2007-07-13 10:40:18TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-31 Cont ID  
Sent By shill Date 2007-05-31 Time 09:52 Rev Time 0.00
Received By shill Date 2007-05-08 Time 10:39 Sent To  
Notes
2007-05-08 10:39:56TO "MISC" BOX#1