Plan Review Stops For Permit 07050171 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2007-05-25 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2007-05-25 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2007-05-25 |
Time |
16:07 |
Sent To |
|
|
Notes |
2007-05-25 16:10:07 | PLEASE SPECIFY THE EXACT LOCATION OF THE JOB .WHICH | | UNIT NUMBER IS USED ? | | | | LACRAMIOARA URSU | | MIS - GIS SUPPORT SPECIALIST | | CITY OF WEST PALM BEACH | | OFFICE:822-1239 | | FAX: 822-1249 | | E-MAIL:[email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2007-08-07 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-08-07 |
Time |
06:47 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-08-07 |
Time |
06:05 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2007-06-03 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-06-03 |
Time |
08:03 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-06-03 |
Time |
07:22 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-12-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-12-17 |
Time |
09:28 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-12-17 |
Time |
09:28 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2007-08-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-01 |
Time |
12:32 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-01 |
Time |
12:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-05-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-05-09 |
Time |
16:42 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-05-09 |
Time |
15:51 |
Sent To |
|
|
Notes |
2007-05-09 16:43:03 | ** UNSAT ** | | | | | | 1) NOTE:PLEASE KNOW THAT THE PLANS WILL BE ROUTED | | THROUGH ADDRESSING REVIEW AS THE PLANS AND FLOOR IS | | BEING SPLIT UP INTO THREE NEW TENANTS. THE SUITE/UNIT | | NUMERICAL DESIGNATIONS WILL BE ASSIGNED BY THIS | | OFFICE. | | | | PLEASE SEE PLANS SHOW THE SAME SUITE #400 WITH A, B OR | | C, WHICH DOES COORDINATE TO OUR SYSTEM OF ADDRESSING | | ETC. | | PLEASE BE AWARE OF COMMENTS FROM THIS TRADE AS | | CORRECTIONS TO PLANS MAY BE NEEDED. | | FBC 106.1.2 | | | | 2) NOTE: PLEASE SHOW THE COMPLETED CIRCUITING FOR NEW | | CIRCUITS AND PANELS WHICH THEY ARE GOING TO BE FED | | FROM. | | PLEASE SUBMIT PANEL SCHEDULES FOR NEW CIRCUITS. PLEASE | | CLARIFY HOW THESE WILL BE NEW TENANTS; HOWEVER PLANS DO | | NOT SEEM TO SHOW ANY PROPOSED TENANT METERS ETC? | | 408.4, 310.16, 240.4 | | FBC106.3.5.4 | | | | 3) NOTE: PLEASE INDICATE MAXIMUM TIMES ON THE OCCUPANCY | | DEVICES PER 13-415.1.ABC.1.1. | | | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2007-08-06 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2007-08-06 |
Time |
13:38 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2007-08-06 |
Time |
13:38 |
Sent To |
|
|
Notes |
2007-08-06 13:38:48 | PLANS APPROVED AND STAMPED ON 8/6/07 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2007-05-23 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2007-05-23 |
Time |
10:56 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2007-05-23 |
Time |
10:56 |
Sent To |
|
|
Notes |
2007-05-23 11:00:43 | ***PROVISO*** | | | | 1) PLEASE SEE ELECTRICAL COMMENTS REGARDING ADDRESSING. | | EACH SUITE SHALL COMPLY WITH REQUIREMENTS FOR COMERCIAL | | BUILDINGS. | | | | 2) IN ADDITION TO FIRE SPRINKLER, SEPARATE SHOP | | DRAWINGS AND PERMIT REQUIRED FOR FIRE ALARM REMODEL. IT | | WOULD APPEAR THAT MORE AUDIBLE/VISUAL EQUIPMENT IS | | NEEDED IN LARGEST SUITE. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-12-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-10 |
Time |
15:28 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-10 |
Time |
15:28 |
Sent To |
E |
|
Notes |
2007-12-10 15:29:18 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-07-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-19 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-19 |
Time |
15:47 |
Sent To |
|
|
Notes |
2007-08-01 11:09:09 | TO "BOB"#7 | 2007-07-19 15:48:06 | WAITING FOR "BOB" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2007-06-03 |
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-07 |
Time |
15:24 |
Sent To |
|
|
Notes |
2007-05-07 15:29:22 | TO "BOB"#12 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2007-08-02 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-08-02 |
Time |
08:02 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-08-02 |
Time |
08:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2007-05-08 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-05-08 |
Time |
10:59 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-05-08 |
Time |
10:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2007-08-02 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-08-02 |
Time |
08:17 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-08-02 |
Time |
08:17 |
Sent To |
|
|
Notes |
2007-08-02 08:17:27 | *VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | IMPROVEMENT VALUE. |
|
|