Plan Review Details - Permit 07050164
Plan Review Stops For Permit 07050164
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-04 Cont ID  
Sent By kconrad Date 2008-03-04 Time 19:24 Rev Time 0.00
Received By kconrad Date 2008-03-04 Time 17:49 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-01-31 Cont ID  
Sent By kconrad Date 2008-01-31 Time 18:55 Rev Time 0.00
Received By kconrad Date 2008-01-31 Time 17:54 Sent To I
Notes
2008-01-31 18:53:38PROJECT: 213 MURRAY ROAD/ # 07050164/ OWNER REVISION
  
 PROJECT DETAIL: ENCLOSE CARPORT, ADD COVERED BREEZEWAY
 AND REMODEL KITCHEN.
  
 APPLICABLE CODE REVIEW: 2004 FLORIDA RESIDENTIAL/
 BUILDING CODE WITH 2006 REVISIONS AND THE 2004 FEBC.
  
 STATUS: FAILED
  
 PLAN REVIEW COMMENTS:
  
 1) PLEASE SUBMIT (2) COPIES OF THE PRODUCT APPROVALS
 FOR THE DOUBLE OUTSWING FRENCHDOORS W/ SIDELITES AND
 TRANSOM AS INDICATED ON SHEET 2.1.
 ALSO, SUBMIT MULLION BAR PRODUCT APPROVALS IF
 APPLICABLE.
  
 2) PLEASE INDICATE THE FINISHED FLOOR ELEVATIONS: NEW
 SUNROOM SHOWS AN ELEVATION TRANSITION OF 6". THE
 INITIAL PLAN INDICATED THE FLOOR TO BE FLUSH WITH THE
 EXISTING FINISHED FLOOR.
  
 3) PLEASE ADJUSTTHE PROJECT VALUATION TO REFLECT THE
 PROPOSED REVISIONS.
  
 4) NOTES ON SHEET 2.1 HAVE BEEN MARKED OUT. THE AOR
 SHALL INITIAL AND DATE OR DELETE FROM PLAN.
  
 5) THERE ARE TWO DETAILS REFERENCING SECTION 2/4.1:
 MISSING A WALL/ROOF FRAMING SECTION DETAIL FOR THE NEW
 SUNROOM HVAC CLOSET AND STORAGE ROOMS.
  
 6) THE REVISION DATE WITHIN THE TITLE BLOCK IS
 1/18/2007 SHOULD BE 1/18/2008??
  
 END OF COMMENTS
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-29 Cont ID  
Sent By kconrad Date 2007-10-29 Time 18:29 Rev Time 0.00
Received By kconrad Date 2007-10-29 Time 16:30 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-09-26 Cont ID  
Sent By kconrad Date 2007-09-26 Time 19:09 Rev Time 0.00
Received By kconrad Date 2007-09-26 Time 17:59 Sent To I
Notes
2007-09-26 18:57:51PROJECT: 213 MURRAY ROAD/ # 07050164
  
 PROJECT DETAIL: ENCLOSE CARPORT, ADD COVERED BREEZEWAY
 AND REMODEL KITCHEN.
  
 APPLICABLE CODE REVIEW: 2004 FLORIDA RESIDENTIAL/
 BUILDING CODE WITH 2006 REVISIONS AND THE 2004 FEBC.
  
 STATUS: APPROVED
  
 PLAN REVIEW COMMENTS:
  
 NOTE: ITEMS MARKED "X" HAVE COMPLIED.
  
  
  
 X1) REQUIRE SHOP DRAWINGS FOR TS COLUMNS AS INDICATED
 ON SHEET 4.1.
  
 X2) PLEASE PROVIDE CLARIFICATION: SHEET 2.1 LOGGIA
 FOUNDATION PLAN INDICATES 3" DIAMETER STEEL COLUMN;
 DETAIL 3/4.1 REFLECTS 3.5 X 3.5" TS COLUMN.
  
 X3) SUBMIT PRODUCT APPROVALS FOR ALL FRAMING
 CONNECTORS.
  
 X4) PROVIDE DETAIL FOR NEW CMU WALLTO EXISTING CMU
 WALL CONNECTION.
  
 X5)SUBMIT EPOXY SPECIFICATIONS.
  
 X6) PROVIDE MECHANICAL ATTACHMENT DETAIL FOR IN-FILL
 WALL FRAMING TO CMU WALL. SEE DETAIL 1/4.1.
  
 X7) SPECIFY GRADE AND SPECIES OF LUMBER USED FOR WALL
 FRAMING, HEADERS AND BEAMS.
  
 X8) INDICATE LENGTH OF CARRIAGE BOLTS AND THE DIAMETER
 OF WASHERS TO BE INSTALLED. SEE WALL LEGEND, SHEET
 2.1.
  
 X9) SHOW DETAILS OF 3X12 WOOD BEAM: MECHANICAL
 ATTACHMENT PATTERN AND SPLICE LOCATIONS IF APPLICABLE.
  
 X10) PROVIDE DETAILS INDICATING THE ATTACHMENT OF THE
 NEW LOGGIA ROOF TO THE EXISTING GARAGE ROOF FRAMING.
  
 X11) PLEASE SHOW SECTION MARK 2/4.1 ON SHEET 2.1 OR
 3.1.
  
 X12) PLAN INDICATES 4043 SINGLE HUNG WINDOW
 INSTALLATION; THE SUBMITTED P/A'S ARE FOR CASEMENT
 WINDOWS. PLEASE CLARIFY.
  
 X13) PROVIDE COLUMN WRAP DETAIL.
  
 X14)WOOD BUCKS SHALL CONFORM TO THE FOLLOWING
 BUILDING CODE SECTION:
  
 1714.5.4.2 MASONRY, CONCRETE OR OTHER STRUCTURAL
 SUBSTRATE.
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1?
 INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR
 SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S
 PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE
 SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE
 OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS
 OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
 WHERE THE WOOD BUCK THICKNESS IS 1? INCHES (38 MM) OR
 GREATER, THE BUCK SHALL BE SECURELY FASTENED TO
 TRANSFER LOAD TO THE MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBTRATE AND THE BUCK SHALL EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME.WINDOW
 AND DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN
 FRAME OR BY JAMB CLIP OR SUBFRAME SYSTEM OR THROUGH THE
 FLANGE TO THE SECURED WOOD BUCK IN ACCORDANCE WITH THE
 MANUFACTURER?S PUBLISHED INSTALLATION INSTRUCTIONS.
 UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME ASSEMBLY
 TO THE SECURED WOOD BUCK.
  
 X15)607.2REDUCTION OF STRENGTH.
 ALTERATIONS SHALL NOT REDUCE THE STRUCTURAL STRENGTH OR
 STABILITY OF THE BUILDING, STRUCTURE, OR ANY INDIVIDUAL
 MEMBER THEREOF.
 EXCEPTION: SUCH REDUCTION SHALL BE ALLOWED AS LONG AS
 THE STRENGTH AND THE STABILITY OF THE BUILDING ARE NOT
 REDUCED TO BELOW THE FLORIDA BUILDING CODE, BUILDING
 LEVELS.
  
 607.3NEW STRUCTURAL MEMBERS.
 NEW STRUCTURAL MEMBERS IN ALTERATIONS, INCLUDING
 CONNECTIONS AND ANCHORAGE, SHALL COMPLY WITH THE
 FLORIDA BUILDING CODE, BUILDING.
  
 X16) PLEASE SHOW ALLEXTERIOR BUILDING ELEVATIONS:
  
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; AND ALL
 EXTERIOR ELEVATIONS:
  
 RESIDENTIAL (ONE- AND TWO-FAMILY):STRUCTURAL
 REQUIREMENTS SHALL INCLUDE:
 WALL SECTION FROM FOUNDATION THROUGH ROOF, INCLUDING
 ASSEMBLY AND MATERIALS CONNECTOR TABLES WIND
 REQUIREMENTS STRUCTURAL CALCULATIONS (IF REQUIRED) .
 RESIDENTIAL (ONE- AND TWO-FAMILY)
  
  
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 FAX:561.805.6676
2007-09-26 18:06:06PROJECT:

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-21 Cont ID  
Sent By kconrad Date 2007-06-21 Time 20:05 Rev Time 0.00
Received By kconrad Date 2007-06-21 Time 16:19 Sent To I
Notes
2007-06-21 19:28:00PROJECT: 213 MURRAY ROAD/ # 07050164
  
 PROJECT DETAIL: ENCLOSE CARPORT, ADD COVERED BREEZEWAY
 AND REMODEL KITCHEN.
  
 APPLICABLE CODE REVIEW: 2004 FLORIDA RESIDENTIAL/
 BUILDING CODE WITH 2006 REVISIONS AND THE 2004 FEBC.
  
 STATUS: DENIED
  
  
 PLAN REVIEW COMMENTS:
  
  
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION PLAN;
 FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; AND ALL
 EXTERIOR ELEVATIONS:
  
 RESIDENTIAL (ONE- AND TWO-FAMILY):
 6. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
  WALL SECTION FROM FOUNDATION THROUGH ROOF, INCLUDING
 ASSEMBLY AND MATERIALS CONNECTOR TABLES WIND
 REQUIREMENTS STRUCTURAL CALCULATIONS (IF REQUIRED)
  
  
 1) REQUIRE SHOP DRAWINGS FOR TS COLUMNS AS INDICATED ON
 SHEET 4.1.
  
 2) PLEASE PROVIDE CLARIFICATION: SHEET 2.1 LOGGIA
 FOUNDATION PLAN INDICATES 3" DIAMETER STEEL COLUMN;
 DETAIL 3/4.1 REFLECTS 3.5 X 3.5" TS COLUMN.
  
 3) SUBMIT PRODUCT APPROVALS FOR ALL FRAMING
 CONNECTORS.
  
 4) PROVIDE DETAIL FOR NEW CMU WALLTO EXISTING CMU
 WALL CONNECTION.
  
 5) SUBMIT EPOXY SPECIFICATIONS.
  
 6) PROVIDE MECHANICAL ATTACHMENT DETAIL FOR IN-FILL
 WALL FRAMING TO CMU WALL. SEE DETAIL 1/4.1.
  
 7) SPECIFY GRADE AND SPECIES OF LUMBER USED FOR WALL
 FRAMING, HEADERS AND BEAMS.
  
 8) INDICATE LENGTH OF CARRIAGE BOLTS AND THE DIAMETER
 OF WASHERS TO BE INSTALLED. SEE WALL LEGEND, SHEET
 2.1.
  
 9) SHOW DETAILS OF 3X12 WOOD BEAM: MECHANICAL
 ATTACHMENT PATTERN AND SPLICE LOCATIONS IF APPLICABLE.
  
 10) PROVIDE DETAILS INDICATING THE ATTACHMENT OF THE
 NEW LOGGIA ROOF TO THE EXISTING GARAGE ROOF FRAMING.
  
 11) PLEASE SHOW SECTION MARK 2/4.1 ON SHEET 2.1 OR
 3.1.
  
 12) PLAN INDICATES 4043 SINGLE HUNG WINDOW
 INSTALLATION; THE SUBMITTED P/A'S ARE FOR CASEMENT
 WINDOWS. PLEASE CLARIFY.
  
 13) PROVIDE COLUMN WRAP DETAIL.
  
 14)WOOD BUCKS SHALL CONFORM TO THE FOLLOWING BUILDING
 CODE SECTION:
  
 1714.5.4.2 MASONRY, CONCRETE OR OTHER STRUCTURAL
 SUBSTRATE.
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1?
 INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR
 SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S
 PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE
 SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE
 OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS
 OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
 WHERE THE WOOD BUCK THICKNESS IS 1? INCHES (38 MM) OR
 GREATER, THE BUCK SHALL BE SECURELY FASTENED TO
 TRANSFER LOAD TO THE MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBTRATE AND THE BUCK SHALL EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME.WINDOW
 AND DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN
 FRAME OR BY JAMB CLIP OR SUBFRAME SYSTEM OR THROUGH THE
 FLANGE TO THE SECURED WOOD BUCK IN ACCORDANCE WITH THE
 MANUFACTURER?S PUBLISHED INSTALLATION INSTRUCTIONS.
 UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME ASSEMBLY
 TO THE SECURED WOOD BUCK.
  
 15)607.2REDUCTION OF STRENGTH.
 ALTERATIONS SHALL NOT REDUCE THE STRUCTURAL STRENGTH OR
 STABILITY OF THE BUILDING, STRUCTURE, OR ANY INDIVIDUAL
 MEMBER THEREOF.
 EXCEPTION: SUCH REDUCTION SHALL BE ALLOWED AS LONG AS
 THE STRENGTH AND THE STABILITY OF THE BUILDING ARE NOT
 REDUCED TO BELOW THE FLORIDA BUILDING CODE, BUILDING
 LEVELS.
  
 607.3NEW STRUCTURAL MEMBERS.
 NEW STRUCTURAL MEMBERS IN ALTERATIONS, INCLUDING
 CONNECTIONS AND ANCHORAGE, SHALL COMPLY WITH THE
 FLORIDA BUILDING CODE, BUILDING.
  
 16) PLEASE SHOW ALLEXTERIOR BUILDING ELEVATIONS:
  
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; AND ALL
 EXTERIOR ELEVATIONS:
  
 RESIDENTIAL (ONE- AND TWO-FAMILY)
  
  
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 FAX:561.805.6676

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-03-03 Cont ID  
Sent By btrobaug Date 2008-03-03 Time 08:40 Rev Time 0.00
Received By btrobaug Date 2008-03-03 Time 08:23 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-01-30 Cont ID  
Sent By btrobaug Date 2008-01-30 Time 12:16 Rev Time 0.00
Received By btrobaug Date 2008-01-30 Time 11:51 Sent To M
Notes
2008-01-30 12:16:23 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-25 Cont ID  
Sent By btrobaug Date 2007-10-25 Time 07:27 Rev Time 0.00
Received By btrobaug Date 2007-10-25 Time 06:48 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-18 Cont ID  
Sent By btrobaug Date 2007-09-18 Time 15:30 Rev Time 0.00
Received By btrobaug Date 2007-09-18 Time 15:22 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-11 Cont ID  
Sent By btrobaug Date 2007-05-11 Time 12:17 Rev Time 0.33
Received By btrobaug Date 2007-05-11 Time 12:15 Sent To M
Notes
2007-05-11 12:17:45 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-02-28 Cont ID  
Sent By adarroug Date 2008-02-28 Time 09:46 Rev Time 0.00
Received By adarroug Date 2008-02-28 Time 09:46 Sent To Z
Notes
2008-02-28 09:46:43TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 11:27 Rev Time 0.00
Received By shill Date 2008-01-25 Time 11:27 Sent To Z
Notes
2008-01-25 11:27:44TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 16:11 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 16:11 Sent To Z
Notes
2007-10-17 16:11:31TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-12 Cont ID  
Sent By adarroug Date 2007-09-12 Time 12:15 Rev Time 0.00
Received By adarroug Date 2007-09-12 Time 12:15 Sent To Z
Notes
2007-09-12 12:15:46TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-10 Cont ID  
Sent By adarroug Date 2007-05-10 Time 10:11 Rev Time 0.00
Received By adarroug Date 2007-05-10 Time 10:11 Sent To E
Notes
2007-05-10 10:11:28TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-22 Cont ID  
Sent By kconrad Date 2007-06-22 Time 15:32 Rev Time 0.00
Received By kconrad Date 2007-05-07 Time 14:34 Sent To I
Notes
2007-05-07 14:34:57TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-03-03 Cont ID  
Sent By tgordon Date 2008-03-03 Time 11:25 Rev Time 0.20
Received By tgordon Date 2008-03-03 Time 11:24 Sent To B
Notes
2008-03-03 11:25:44REVISION TO MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-01-30 Cont ID  
Sent By tgordon Date 2008-01-30 Time 16:33 Rev Time 0.30
Received By tgordon Date 2008-01-30 Time 16:33 Sent To B
Notes
2008-01-30 16:41:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** MECHANICAL REVISION **
 *** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS AS A NEW
 SYSTEM IS BEING INSTALLED, SEE 2004 FBC 13-607.1.ABC.1
 OR 13-407.1.ABC.1.
  
 2) PLEASE SHOW THE LOCATION OF THE NEW A/C CONDENSER
 UNIT ON PLAN 3.1, SEE 2004 FBC/R M1307.3.
  
 3) PLEASE SHOW AN A/C EQUIPMENT SCHEDULE ON PLAN 3.1
 WITH ALL PERTINENT INFORMATION, SEE 2004 WPB AMEND.
 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-10-26 Cont ID  
Sent By tgordon Date 2007-10-26 Time 08:14 Rev Time 0.30
Received By tgordon Date 2007-10-26 Time 08:14 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-09-19 Cont ID  
Sent By tgordon Date 2007-09-19 Time 09:21 Rev Time 0.30
Received By tgordon Date 2007-09-19 Time 09:21 Sent To P
Notes
2007-09-19 09:38:50PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW, ENERGY CALCULATIONS NEED TO
 BE ON FORM600C-04R NOT FORM 600-04, SEE 2004 FBC
 13-600.3.C.
  
 2) WHEN SUBMITTING THE 'CORRECT' ENERGY CALCULATIONS
 HAVE THEM SIGNED BY THE OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2.
  
 3) ENERGY CALCULATIONS LINE 9A1 SHOW WALL INSULATION IS
 R-5. PLANS PAGE 4.1 DETAIL 2/4.1 SHOWS NO INSULATION ON
 THE WALLS, SEE FBC 13-103.2. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-15 Cont ID  
Sent By tgordon Date 2007-05-15 Time 14:03 Rev Time 0.20
Received By tgordon Date 2007-05-15 Time 14:03 Sent To P
Notes
2007-05-15 14:12:24*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM600C-04R,
 SEE 2004 FBC 13-600.3.C (12-8-06 REVISION).
  
 2) WHEN SUBMITTING REVISED ENERGY CALCULATIONS HAVE
 THEM SIGNED BY THE OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status N Date 2007-09-26 Cont ID  
Sent By mperson Date 2007-09-26 Time 15:56 Rev Time 0.00
Received By mperson Date 2007-09-26 Time 15:56 Sent To B
Notes
2007-09-26 15:58:26NOTE: RESUBMITTED PERMIT APPLICATION DELETED KITCHEN
 REMODEL. THERE IS NO PLUMBING ON RESUBMITTED PLANS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-18 Cont ID  
Sent By mperson Date 2007-05-18 Time 08:47 Rev Time 0.33
Received By mperson Date 2007-05-18 Time 08:47 Sent To B
Notes
2007-05-18 09:02:40DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE PERMIT APPLICATION IS INDICATING "REMODEL
 KITCHEN". THE SUBMITTED PRINTS DO NOT INDICATE ANY
 KITCHEN REMODEL.
 NOTE: MORE INFORMATION IS REQUIRED. PLEASE
 INDICATE ON THE DRAWING THE EXISTING KITCHEN LAYOUT,
 AND ON A SEPERATE DRAWING PLEASE INDICATE THE NEW
 PROPOSED
 KITCHEN LAYOUT.
 A} IF KITCHEN REMODEL PLUMBING LAYOUT IS THE SAME
 WITH NO CHANGES, PLEASE INDICATE THIS ON
 THE DRAWING.
 B} IF KITCHEN REMODEL PLUMBING LAYOUT IS THE
 SAME AND THE PLUMBING FIXTURES ARE TO BE
 CHANGED, PLEASE INDCATE ON THE DRAWING.
 "EXACT FIXTURE CHANGE OUT ONLY."
 C} IF THE PROPOSED KITCHEN REMODEL PLUMBING LAYOUT IS
 DIFFERENT FROM THE EXISTING PLEASE FOLLOW WHAT IS
 REQUIRED IN COMMENT #2.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 5 Status P Date 2008-02-28 Cont ID  
Sent By choops Date 2008-02-28 Time 13:57 Rev Time 0.00
Received By choops Date 2008-02-28 Time 13:57 Sent To E
Notes
2008-02-28 13:59:13***APPROVED - REVISION - CHANGE WINDOWS TO DOORS IN SUN
 ROOM, ADD A/C CLOSET***
  
 PROVISOS:
 1)APPROVED TO ENCLOSE EXISTING CARPORT, ALL NEW
 CONSTRUCTION SHALL MEET CURRENT SETBACK REGULATIONS
 FOUND IN SECTION 94-74 OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS.
 2)NO NEW NONCONFORMITY SHALL BE CREATED.NO
 EXISTING NONCONFORMITY SHALL BE ENLARGED OR INCREASED.
  
 3)MECHANICAL EQUIPMENT SHALL NOT PROJECT MORE THAN 4
 FEET INTO A REQUIRED SETBACK.
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 4 Status F Date 2008-01-28 Cont ID  
Sent By choops Date 2008-01-28 Time 14:11 Rev Time 0.00
Received By choops Date 2008-01-28 Time 14:11 Sent To E
Notes
2008-01-28 14:06:49*** FAILED - REVISION - CHANGE WINDOWS TO DOORS IN SUN
 ROOM, ADD A/C CLOSET***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY SHOWING
 THE LOCATION OF THE PROPOSED WITH DIMENSIONS AND
 SETBACK DIMENSIONS TO ALL PROPERTY LINES.NOTE:ANY
 NEW CONSTRUCTION MUST MEET CURRENT REGULATIONS, SETBACK
 REQUIREMENTS CAN BE FOUND IN SECTION 94-74 OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS).
  
 2)AS THE EXISTING STRUCTURE IS A NONCONFORMING
 STRUCTURE, NOTHING NEW WILL BE PERMITTED TO BE BUILT
 UNLESS IT MEETS CURRENT REGULATIONS FOUND IN THE
 AFOREMENTIONED SECTION OF THE ZLDRS.THE NEWLY
 SUBMITTED PLANS SHOW AN EXTENSION OF THE EXISTING
 NONCONFORMING STRUCTURE OTHER THAN WHAT WAS ORIGINALLY
 PERMITTED.THIS IS NOT ALLOWABLE, NO NEW NONCONFORMITY
 SHALL BE CREATED OR EXISTING NONCONFORMITY ENLARGED.
  
 3)INDICATE SETBACK DIMENSIONS FROM ANY PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-22 Cont ID  
Sent By choops Date 2007-10-22 Time 13:50 Rev Time 0.00
Received By choops Date 2007-10-22 Time 13:50 Sent To E
Notes
2007-10-22 13:50:57***APPROVED - RESUB #2***
  
 PROVISO - NO NEW NONCONFORMITY SHALL BE CREATED OR
 EXISTING NONCONFORMITY ENLARGED.
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status F Date 2007-09-14 Cont ID  
Sent By choops Date 2007-09-14 Time 11:33 Rev Time 0.00
Received By choops Date 2007-09-14 Time 11:33 Sent To E
Notes
2007-09-14 11:49:06***FAILED - RESUB #1***
  
  
 1)PLEASE PROVIDE A FLOOR PLAN SHOWING THE REMODEL OF
 THE KITCHEN AND 2ND FLOOR ABOVE THE CARPORT SHOWING THE
 INTERCONNECTIVITY WITH THE REMAINDER OF THE HOUSE.
 (REPEAT COMMENT)
  
 2)CLARIFY IF PROPOSED DRIVEWAY IS TO BE INCLUDE IN
 THE SCOPE OF WORK UNDER THIS PERMIT.IF SO, ADD TO
 VALUE AND ADJUST FEES AND PROVIDE SQUARE FOOTAGE OF
 PROPOSED AND EXISTING, ALSO INDICATE IF APPROACH TO BE
 DONE OR NOT.IF NOT INCLUDED IN SCOPE OF WORK LABEL
 "TO BE PERMITTED SEPARATELY"(REPEAT COMMENT)
  
 3)SHEETS 1.1 AND 5.1 SHOW PROPOSED LOGGIA STILL
 CONNECTING THE PRINCIPAL STRUCTURE AND THE GUEST
 HOUSE...REVISE TO SHOW A MINIMUM OF 6' SEPARATION.
  
 4)SURVEYS AND SITE PLANS DO NOT MATCH.SURVEY,
 INCLUDING NORTH ELEVATION OF SHEET AD.1 SHOWS PROPOSED
 LOGGIA EXTENDING FROM PRINCIPAL STRUCTURE...OTHER PAGES
 SHOW EXTENDING FROM GUEST HOUSE.CLARIFY.
  
 5)PLEASE PROVIDE FLOOR PLAN OF GUEST HOUSE.CITY
 RECORDS SHOW IT ORIGINALLY CONSTRUCTED AS A UTILITY
 BUILDING.PROVIDE PROOF (RECORDS OF BUILDING PERMIT)
 THAT IT WAS LEGALLY CONVERTED.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-08 Cont ID  
Sent By choops Date 2007-05-08 Time 17:10 Rev Time 0.00
Received By choops Date 2007-05-08 Time 17:10 Sent To I
Notes
2007-05-08 17:17:45***FAILED ***
  
  
 1)PLEASE PROVIDE FLOOR PLANS SHOWING REMODEL OF
 KITCHEN, ALSO SHOWING IF CARPORT IS 2 STORIES OR NOT.
  
 2)SHOW ELEVATIONS FOR ALL SIDES
  
 3)PLEASE SHOW SCOPE OF WORK ON BOTH COPIES OF SURVEYS
 WITH DIMENSIONS OF PROJECTS, AND DIMENSIONS TO PROPERTY
 LINES.
  
 4)DRIVEWAY MUST BE UNDER A SEPERATE PERMIT.
  
 5)SPECIFY IF GARAGE IS A GARAGE OR A GUEST HOUSE
  
 6)THE CONNECTION OF THIS ROOFED BREEZEWAY FROM
 RESIDENCE TO GARAGE QUALIFIES THE GARAGE AS A PRINCIPAL
 STRUCTURE AND IS SUBJECT TO THE PRINCIPAL STRUCTURE'S
 SETBACK REQUIREMENTS (WHICH IT DOES NOT MEET) THE ONLY
 WAY IT WOULD BE PERMITTED IS IF THE BREEZEWAY IS
 COVERED(ROOFED) BY CANVAS, NOT ACTUALLY ROOFED IN.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720