Plan Review Details - Permit 07050148
Plan Review Stops For Permit 07050148
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-06 Cont ID  
Sent By mjacobs Date 2007-06-06 Time 11:04 Rev Time 0.00
Received By mjacobs Date 2007-06-05 Time 12:51 Sent To PC
Notes
2007-06-06 11:04:28BUILDING PLAN REVIEW
 PERMIT: 07050148
 ADD: 62347TH ST.
 CONT: TREASURE COAST DESIGN INC.
 TEL: (561)478-7488
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 NOTE: WEST PALM BEACH IS NOT IN THE 130 MPH ZONE.
  
 3)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4)FBC 108.3*THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS
 ICC (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS
 SERVICES.
  
 5)R319.1 LOCATION REQUIRED.
 IN AREAS SUBJECT TO DECAY DAMAGE AS ESTABLISHED BY
 TABLE R301.2(1) , THE FOLLOWING LOCATIONS SHALL REQUIRE
 THE USE OF AN APPROVED SPECIES AND GRADE OF LUMBER,
 PRESSURE TREATED IN ACCORDANCE WITH AWPA C1, C2, C3,
 C4, C9, C15, C18, C22, C23, C24, C28, C31, C33, P1, P2
 AND P3, OR DECAY -RESISTANT HEARTWOOD OF REDWOOD, BLACK
 LOCUST, OR CEDARS. (5.)WOOD SIDING, SHEATHING AND
 WALL FRAMING ON THE EXTERIOR OF A BUILDING HAVING A
 CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE
 GROUND.
  
 6)THE EXTERIOR WALL SECTION ON THE FIRST PAGE DOES
 NOT MATCH THE THE FLOOR PLAN ON THE SECOND SHEET. THE
 FLOOR PLANS SHALL MATCH THE FRAMING PLAN. ALSO, TABLE
 1705.1
 CANNOT BE FOUND IN THE 2004 FBC. CLARIFY.
  
 7) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 ) NUMBER OF BEDROOMS
 ) NUMBER OF ROOMS
 OK ) SQ. FT. LIV SPACE/ FL
 OK) SQ. FT. FOOTPRINT
 OK) SQ. FT. UNDER ROOF (TOTAL)
  
 8) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.THE DESIGNER OF RECORD SHALL
 APPROVE ALL PRODUCT APPROVALS.
 NOTE: ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
 _XX___1.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
  
 _XX___2.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
  
 _XX___ 3.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
 FL#1654-R1 DOES MATCH THE NOA REPORT SEE
 FLORIDABUILDING.ORG FOR MORE INFORMATION. FL#6571
 SUBMITTED STATES "PENDING FBC APPROVAL"
  
 FYI, RAS 150 IS A PRESCRIPTIVE BUILT UP ROOF SYSTEM
 WHICH IS ALLOWED IN HIGH VELOCITY WHEN ADOPTED BY THE
 AHJ (FBC R4402.8) BUT IS NOT ALLOWED OUTSIDE OF HIGH
 VELOCITY (FBC R905.11.3, STATES IN ACCORDANCE WITH
 MANUFACTURER'S INSTRUCTIONS).
  
 9)R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-14 Cont ID  
Sent By dpalmer Date 2007-05-14 Time 10:12 Rev Time 0.00
Received By dpalmer Date 2007-05-14 Time 09:34 Sent To M
Notes
2007-05-14 10:12:49** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE:PLEASE SEE MISSING TITLE BLOCKS FOR THE
 DESIGNER OF RECORD AS REQUIRED PER FAC 61G15-23.002.
 PLEASE SEE THE PLANS APPEAR TO BE SIGNED WITH
 *INITIALS*, IF THIS IS INDEED THE LEGAL SIGNATURE,
 PLEASE PROVIDE A NOTARIZED LETTER FOR SIGNATURE
 VERIFICATION. THE LETTER IS TO BE SIGNED, DATED, SEALED
 AND CORRECTLY NOTARIZED. NOTARY TO PLACE INFORMATION AS
 REQUIRED PER FS 117.05
  
 2) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR NEW LOADS
 TO NEW OR EXISTING SERVICE. IF EXISTING, PLEASE
 INDICATE THE SIZE OF THE EXISTING SERVICE WITH NEW
 LOADS.
 PLEASE SEE NEC 220.87.
  
 3) NOTE: PLEASE SEE THE MISSING DEDICATED BATH CIRCUIT
 PER 210.11C3, 210.52.
 (MUST BE #12 AND 20AMP.)
  
 4) NOTE: PLEASE SHOW THE SMOKE DEVICES AS SA OR SD.
 PLEASE SEE NFPA-72 DEFINITIONS FOR TYPE OF DEVICES
 WHICH ARE BEING INSTALLED. PLANS SHOW THESE AS SD WHICH
 WOULD MEAN THESE DEVICES ARE SMOKE DETECTION DEVICES
 ONLY AND WOULD ONLY SEND SIGNAL TO SOUNDING DEVICES OR
 FIRE ALARM SYSTEM WHICH IS NOT ON PLANS. PLEASE KNOW IF
 THESE ARE INDEED SA WHICH IS SMOKE ALARMS, THESE WOULD
 DETECT AND SOUND THE ALARM.
 PLEASE CLARIFY.
 ** PLEASE ALSO SEE FBC R313 AS THE EXISTING DWELLING IS
 REQUIRED TO BE BROUGHT UP TO CODE. PLEASE SHOW A LAYOUT
 OF THE EXISTING DWELLING WHICH WILL REQUIRE SMOKE
 DEVICES INSIDE AND OUTSIDE ALL BEDROOMS.
 NFPA-72 11.5.1.1, 11.8.3
  
 5) NOTE: PLEASE SEE THAT PLANS ARE REQUIRED TO STATE
 ALL RELEVANT CODES WITH RESPECT TO SCOPE OF WORK.
 PLEASE SEE THIS PROJECT IS UNDER THE FBC 2004 W/2006
 REVISIONS.
 PLEASE ALSO INCLUDE THE 2005 NEC AND THE 2002 NFPA-72.
  
 6) NOTE: PLEASE PROVIDE A PANEL SCHEDULE SHOWING ALL
 EXISTING AND NEW CIRCUITS. CIRCUITS ARE REQUIRED TO
 MINIMUM PER NEC AND TO BE SPECIFIC TO ROOMS AND AREAS
 IN WHICH THEY FEED.
 PLEASE SEE 408.4, 310.16, 240.4.
  
 7) NOTE: PLEASE SEE MISSING EGRESS LIGHTING FIXTURES
 FOR BOTH ROOMS PER 210.70 AND NFPA-101 7.8.
 PLEASE SEE PLANS ONLY SHOW A FAN IN BOTH LOCATIONS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-07 Cont ID  
Sent By adarroug Date 2007-05-07 Time 16:22 Rev Time 0.00
Received By adarroug Date 2007-05-07 Time 16:22 Sent To  
Notes
2007-05-07 16:22:43TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-06-06 Time   Rev Time 0.00
Received By adarroug Date 2007-05-04 Time 11:57 Sent To  
Notes
2007-05-04 12:02:22TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-15 Cont ID  
Sent By tgordon Date 2007-05-15 Time 13:41 Rev Time 0.25
Received By tgordon Date 2007-05-15 Time 13:41 Sent To P
Notes
2007-05-15 13:52:23*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.2.2.
  
 2) MECHANICAL PLANS NEED TO BE SUBMITTED AT THIS TIME
 NOT LATER,PER 2004 FBC CITY OF WPB AMEND. 106.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS, 106.3.5.4
 RESIDENTIAL #10
 MECHANICAL: ENERGY CALCULATIONS, EQUIPMENT SCHEDULE,
 DUCT LAYOUT SIZE/GRILL SIZE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-18 Cont ID  
Sent By mperson Date 2007-05-18 Time 08:16 Rev Time 0.45
Received By mperson Date 2007-05-18 Time 08:16 Sent To B
Notes
2007-05-18 08:32:05DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 1:THE SUBMITTED SANITARY ISOMETRIC RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IS IS NOT CODE
 COMPLIANT. PLEASE REFERENCE THE RED LINE SANITARY
 ISOMETRIC RISER DIAGRAM THAT REFLECTS THE FLOOR PLAN
 AND IS CODE COMPLIANT.
 NOTE: 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2. PLEASE REFERENCE ELECTRICAL PLAN REVIEW COMMENTS #1
 AND #5 AND COMPLY ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-07 Cont ID  
Sent By choops Date 2007-05-07 Time 14:43 Rev Time 0.00
Received By choops Date 2007-05-07 Time 14:43 Sent To I
Notes
2007-05-07 14:47:30***FAILED***
  
  
 1)PLEASE CLEARLY INDICATE THE SCOPE OF WORK ON THE 2
 COPIES OF SURVEYS.INCLUDING DIMENSIONS OF PROPOSED
 WORK, AND DIMENSIONS FROM PROPERTY LINES TO PROPOSED
 WORK.
  
 2)**MUST OBTAIN SEPERATE PERMIT FOR DRIVEWAY**
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720
  
  