Plan Review Details - Permit 07050144
Plan Review Stops For Permit 07050144
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-18 Cont ID  
Sent By jwitmer Date 2007-06-18 Time 13:54 Rev Time 1.22
Received By jwitmer Date 2007-06-18 Time 13:54 Sent To  
Notes
2007-06-18 14:00:57BUILDING PLAN REVIEW
 PERMIT: 07050144
 ADD: 510 ROSELAND DRIVE
 CONT: REGACY COMMUNICATIONS
 TEL: (954)444-2822
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
  
 4) S-1 PLANS INDICATE THE WIND DESIGN TO THE ASCE 7-98
 PLEASE UPDATE AND CORRECT.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-18 Cont ID  
Sent By dpalmer Date 2007-05-18 Time 11:31 Rev Time 0.00
Received By dpalmer Date 2007-05-18 Time 11:00 Sent To  
Notes
2007-05-18 11:32:21** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
  
 ** PLEASE KNOW PLANS AND SPECS/CUT SHEETS ARE BEING
 SUBMITTED WHICH ARE THE SAME AS PREVIOUSLY REVIEWED
 UNDER PERMIT 05111101 WHICH HAS EXPIRED.PLEASE SEE
 NEW COMMENTS AS CODES HAVE CHANGED SINCE LAST APPLIED
 DATE.
  
  
 1) NOTE:PLEASE SEE PLANS MUST REFLECT CURRENT CODES
 IN EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK
 AS SHOWN.
 PLEASE KNOW HOWEVER AT THIS TIME AND AS OF DECEMBER
 8TH, 2006 THE STATE IS UNDER THE 2004 FBC W/2006
 REVISIONS. THESE ARE ONLY REVISIONS TO THE 2004 FBC.
 WE ARE UNDER THE 2005 NFPA-70. (NEC), 2002 NFPA-110
  
 2) NOTE: PLEASE SEE SPECS/CUT SHEETS DO NOT CORRELATE
 WITH PLANS.
 PLEASE SUBMIT THE COMPLETE REQUESTED SPECS AND CUT
 SHEETS FOR ALL EQUIPMENT AS PREVIOUSLY NOTED.
 GEN, ATS, FUEL, ETC.
 SPECS ARE TO HIGH-LIGHT AND INDICATE THE EQUIPMENT IN
 SCOPE OF WORK AS APPLIED AND AS SHOWN ON PLANS.
 110.3, 90.7
 FBC 106.1.2
  
 3) NOTE: PLEASE KNOW AS TO DATE AND AS PREVIOUSLY NOTED
 ON BOTH PREVIOUS REVIEWS, NO ELECTRICAL CONTRACTOR IS
 SIGNED ON AND SEPARATE ELECTRICAL PERMIT WILL BE
 REQUIRED. THE CGC MAY NOT UNDER THIS LICENSE PERFORM
 ANY ELECTRICAL WORK AS SHOWN ON PLANS.
 CILB>ECLB
 FS 489
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By mawillia Date 2007-06-26 Time 11:23 Rev Time 0.00
Received By mawillia Date 2007-06-26 Time 10:52 Sent To  
Notes
2007-06-26 11:23:37*****UNSAT*****
  
  
 1.ON SHEET A-1 THE 2002 EDITION OF NFPA 110 SHALL BE
 REFERENCED.
  
 2.SEE ELECTRICAL PLAN REVIEW NOTE 2 FOR THE MATTER OF
 THE SPECS/CUT SHEETS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-06-11 Cont ID  
Sent By kstevens Date 2007-06-11 Time 09:47 Rev Time 0.00
Received By kstevens Date 2007-06-11 Time 09:47 Sent To  
Notes
2007-06-11 09:48:52PLANS INDICATE DIESEL GENERATOR. NO NATURAL OR LP GAS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-26 Cont ID  
Sent By mawillia Date 2007-06-26 Time 11:17 Rev Time 0.00
Received By mawillia Date 2007-05-04 Time 08:54 Sent To  
Notes
2007-05-16 10:28:25TO "COMM" BD#50
2007-05-04 08:54:31WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-25 Cont ID  
Sent By tgordon Date 2007-05-25 Time 14:02 Rev Time 0.25
Received By tgordon Date 2007-05-25 Time 14:02 Sent To  
Notes
2007-05-25 14:04:15*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #2, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-24 Cont ID  
Sent By adavila Date 2007-05-24 Time 17:32 Rev Time 0.00
Received By adavila Date 2007-05-23 Time 15:39 Sent To  
Notes
2007-05-24 17:32:53PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE ENCLOSURE DETAILS MEETING SECTION 94-444(B)
 AND (C) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
 A. PLEASE NOTE THAT SCREENING SHALL BE CONSTRUCTED OF
 BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE MASONRY,
 OR COMPARABLY WOOD AND STEEL.
 B. PLEASE NOTE THAT WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO (2) FOOT INTERVALS.
 C. WALL OPENINGS SHALL HAVE OBSCURING GATES.
  
 2. SETBACK DIMENSIONS ON THE SURVEY, AND SHEETS A1 AND
 A2 DO NOT MATCH.ALL SETBACK DIMENSIONS SHALL REFLECT
 ACTUAL DIMENSIONS ON ALL PLANS.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.