Plan Review Details - Permit 07050102
Plan Review Stops For Permit 07050102
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-12-11 Cont ID  
Sent By jgomez Date 2007-12-11 Time 12:50 Rev Time 0.00
Received By jgomez Date 2007-12-11 Time 12:33 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-12-04 Cont ID  
Sent By jgomez Date 2007-12-04 Time 12:52 Rev Time 0.00
Received By jgomez Date 2007-12-04 Time 12:38 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-11-05 Cont ID  
Sent By jgomez Date 2007-11-05 Time 13:38 Rev Time 0.00
Received By jgomez Date 2007-11-05 Time 12:39 Sent To Z
Notes
2007-11-05 13:43:55RESIDENTIAL ADDITION BUILDING REVIEW FOURTH CHECKLIST.
 REVIEW UNDER EXISTING BUILDING 2004 CODE, FLORIDA
 RESIDENTIAL CODE 2004 AND FBC 2004.
  
 1- DESIGN PARAMETERS INFORMATION IS MISSING THE ATTIC
 LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA
 RESIDENTIAL CODE. THIS IS THE FOURTH TIME THAT THIS
 INFORMATION IS REQUESTED. ARCHITECTTO PAY $524.80 AS
 REQUIRED BYFLORIDA STATUTE 553.80(2)(B) FOR PLAN
 REVIEW FEE. SEE ATTACHED COPY.
  
 ***NOTE: ONE COPY OF PLANS WILL BE RETAINED IN THIS
 OFFICE TO BE SUBMITTED TO THE BOARD OF ARCHITECTS FOR
 REVIEW.
  
 2- ARCHITECT SPECIFIED CONSTRUCTION TYPE III.
 CONSTRUCTION TYPE III REQUIRES A TWO HOUR WALL ASSEMBLY
 AS REQUIRED BY TABLE 601 FBC 2004, THEREFORE,NEED TO
 PROVIDE MANUFACTURER'S SPECIFICATIONS FOR 2 HOUR FIRE
 RATED CONCRETE BLOCK.ALSO, ARCHITECT TO SPECIFYIF
 CONSTRUCTION TYPEIS A OR B. SEE TABLE 601 FBC 2004.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE. THIS MAY BE PROVIDED WHEN
 PICKING UP THE PERMIT.
  
 4- ENERGY CALCULATIONS: ONE OF THE COPIES IS MISSING
 THE INFORMATION ON TABLE 6C-1 AND TABLE 6C-2. COMPLETE
 INFORMATION AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-11 Cont ID  
Sent By jgomez Date 2007-10-11 Time 14:04 Rev Time 0.00
Received By jgomez Date 2007-10-11 Time 14:01 Sent To  
Notes
2007-10-11 14:30:38RESIDENTIAL ADDITION BUILDING REVIEW THIRD CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE,
 EXISTING BUILDING CODE 2004AND 2004 FBC 2004 WITH
 2006 REVISIONS.
  
 1-PLANS NEED TO CLEARLY SPECIFY ALL DESIGN LOADS,
 WIND LOADS, LIVE LOADS AND DEAD LOADS,INCLUDING THE
 ATTICLIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004
 FLORIDA RESIDENTIAL CODE.INFORMATION SUBMITTED UNDER
 DESIGN PARAMETERS ON SHEET 1 OF 4 DOESN'T MAKE SENSE.
 ITSHOWS LIVE LOAD OF 30 AND DEAD LOAD OF 15. WHAT ARE
 THESE LOADS FOR?.FLOOR, ROOF?.IT'S NOT CLEAR.ON
 THE OTHER HAND AT BOTTOM OFDESIGN PARAMETERS
 INFORMATION IT STATES "TOTAL ROOF DEAD LOAD OF 45". HOW
 WAS THIS LOAD ACHIEVED?.PROVIDECALCULATIONS.
 SECTION 106.1.2 CITY AMENDMENTS TO FBC 2004.PROVIDE
 CLEAR AND COORDINATEDINFORMATION SHOWING DESIGN LOADS
 FOR ROOF TOP CHORD LIVE AND DEAD LOADS ANDROOF BOTTOM
 CHORD LIVE AND DEAD LOADS. THIS IS THE INFORMATION
 REQUIRED FOR THE DESIGN OF ROOF TRUSSES. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 ***NOTES:A) SEE ATTACHED COPY OF SEC. 553.80(2)(B)
 REGARDING DESIGN PROFESSIONAL DOCUMENTS AND MULTIPLE
 PLAN REVIEW FAILURES.
 B) ONE COPY OF PLANS WILL BE
 RETAINED IN THIS OFFICE FOR FUTURE SUBMITTAL TO THE
 BOARD OF ARCHITECTS FOR REVIEW.
  
 2- THIS IS AN ADDITION, NOT ALTERATION LEVEL 3.SEE
 CHAPTER 9 OF EXISTING BUILDING 2004 CODE AND SCOPE OF
 WORK SPECIFIED ON PLANS AND REVISE INFORMATION AS
 REQUIRED.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 4- ARCHITECT PROVIDED PRODUCT APPROVAL WITH THE REVIEW
 STAMP, BUT FAILED TO MARK ACTION TAKEN.STAMP DOESN'T
 STATE IF PRODUCT APPROVALWAS DENIED OR APPROVED.
 PROVIDE INFORMATION AS REQUIRED. SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 5- MISSING THE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 FBC 2004.
  
 6- MISSING PRODUCT APPROVAL FOR SIMPSON CONNECTORS
 SPECIFIED ON PLANS. REQUIRED BY DCA RULE 9B-72.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561) 805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-16 Cont ID  
Sent By jgomez Date 2007-08-16 Time 12:54 Rev Time 0.00
Received By jgomez Date 2007-08-16 Time 12:54 Sent To PC
Notes
2007-08-16 13:42:37ADDITION BUILDING REVIEW SECOND CHECKLIST:
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC
 2004.
  
 1- PROVIDE COPY OF IMPACT FEES PAID RECEIPTAS
 REQUESTED ON PREVIOUS CHECKLIST:
  
 2- PLANS NEED TO SPECIFY ALL DESIGN LOADS, INCLUDING
 THE ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004
 FLORIDA RESIDENTIAL CODE AND AS REQUESTED ON PREVIOUS
 CHECKLIST.
  
 3- SPECIFY TYPE OF CONSTRUCTION AS REQUIRED BY SEC.
 602.1 FBC 2004 AND SEC. 106.3.5.4 OF CITY AMENDMENTS TO
 FBC 2004. THIS ITEM WAS ALSO REQUESTED ON PREVIOUS
 CHECKLIST.
  
 4- STORM SHUTTERS:
 A) INSTALLATION SCHEDULE SUBMITTED:
 (1) PROVIDE COMPLETE AND CORRECTINSTALLATION
 SCHEDULE.
 (2)REVISE PRODUCT APPROVAL NUMBERS ON TOP OF FORM.
 SEE SUBMITTED PRODUCT APPROVAL FOR CORRECT NUMBERS..
 (3) REVISE DESIGN PRESSURES. SEE ARCHITECTURAL PLANS
 FOR CALCULATED DESIGN PRESSURES.
 (4) REVISE INFORMATION GIVEN ON SHUTTER MOUNTING
 COLUMN (COLUMN 4). LOOK AT SHUTTERS DRAWINGS AND
 SPECIFY TYPE OF MOUNTING. EG: WALL MOUNTED, BUILT OUT
 MOUNT, ETC.SPECIFIC MOUNTING CONDITION IS REQUIRED
 SINCE THERE ARE MANY DIFFERENT MOUNTING CONDITIONS AND
 TO VERIFY COMPLIANCE WITH PROPOSED INSTALLATION. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 (5) WHAT'S THE SHUTTER GLASS SEPARATION.SEE
 SHUTTERS DRAWINGS FOR REQUIRED SEPARATION.
 (6) SPECIFY ANCHOR SPACING.
  
 B) CIRCLE ON SHUTTERSDRAWINGS SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE AND SPACING TO BE USED. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 C) PROVIDE LEGIBLE DRAWINGS. DRAWING SUBMITTED ARE
 NOT LEGIBLE.
  
 5- TRUSS PACKAGE:
 A) COMPLETE PACKAGE NEEDS TO HAVE ALL THE ENGINEER'S
 INFORMATION AND ALL DRAWINGS TO BE SIGNED AND SEALED AS
 REQUIRED BY SEC. 61G15-23.002 AND CHAPTER 471 FLORIDA
 STATUTE.
 NOTE: COPY OF SIGNATURE IS NOT ALLOWED.
  
 B) COMPLETE TRUSS PACKAGE NEED TO BE REVIEWED AND
 APPROVED BY THE ARCHITECT OF RECORD. NOT SIGNED AND
 SEALED BY HIM.
 NOTE: ARCHITECT CAN'T SIGN AND SEAL THESE DRAWINGS
 BECAUSE THEY WERE NOT DONE BY HIM. SEE CHAPTER 481
 FLORIDA STATUTES.
  
 6- SHEET 1 OF 4:
 A) THIS IS AN ADDITION, NOT ALTERATION TYPE 2.SEE
 CHAPTER 9 OF EXISTING FBC 2004 AND REVISE AS REQUIRED.
  
  
 B) TOTAL ROOF DEAD LOAD LINE SHOWS 30PSF, WHILE DEAD
 LOAD LINE SHOWS 25PSF. REVISE AND COORDINATE AS
 REQUIRED.ALSO SEEITEM#2ABOVE.
  
 7- REVISE GABLE END WALL SECTION.
 A) ROOF SHEATHING NAIL SPACING NEEDS TO BE REVISED
 FOR ROOF ZONE 3. SEE SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE AS REQUIRED.
  
 B) USP CONNECTORSPECIFIED DOESN'T MATCH CONNECTOR
 SPECIFIED ON ROOF FRAMING PLAN AND TRUSS ANCHOR
 SCHEDULE. REVISE AS REQUIRED.
  
 8- REVISE ROOF SHEATHING NAIL SPACING SPECIFIED ON
 TYPICAL WALL SECTION.SEE SEC. R803.2.3.1 OF 2004
 FLORIDA RESIDENTIAL CODE FOR NAIL SPACING AT ROOF ZONE
 #3 AND REVISE AS REQUIRED.
  
 9- TYPICAL WALL SECTION TITLE CALLS FOR 1'-6" O.H.
 WHILE TYP. WALL SECTION DRAWINGS SHOW 24" OVERHANG.
 REVISE AS REQUIRED TO MATCH.
  
 10- CLARIFY WHY ARCHITECT REVIEWED AND APPROVED PRECAST
 LINTEL PRODUCT APPROVAL FOR 4", 6 AND 12" PRECAST
 LINTELS IF THERE ARE NOT LINTELS THIS SIZE?. SEE
 PLANS.
  
 11- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By tgordon Date 2007-08-14 Time 12:25 Rev Time 0.00
Received By jgomez Date 2007-06-20 Time 16:45 Sent To PC
Notes
2007-06-20 16:47:57BUILDING REVIEW CHECKLIST:
 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY FOR IMPACT FEES (2300N. JOG RD (561)233-5115).
 BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF
 ADDITIONAL FEES ARE DUE.
  
 2- PERMIT VALUATION WAS UPDATED AS REQUIRED BY SEC.
 108.3CITY AMENDMENTS TO FBC 2004. THEREFORE, OWES
 $80.19 FOR UPDATED VALUATION AND RADON FEES.
  
 3- PLANS NEED TO SPECIFY ALL DESIGN LOADS, INCLUDING
 THE ATTIC LIVE LOADS AS REQUIRED BY TABLE R301.5 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 4- SPECIFY TYPE OF CONSTRUCTION AS REQUIRED BY SEC.
 602.1 FBC 2004.
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) ALL SIMPSON CONNECTORS SPECIFIED ON PLANS.
  
 B) ROOF SHINGLES. NOA 04-0820.01 SUBMITTED WAS
 SUPERSEDED ACCORDING TO DADE COUNTY PRODUCT APPROVAL
 WEBSITE. SEE ATTACHED COPY.NEED TO PROVIDE CURRENT
 NOA OR PRODUCT APPROVAL.
 ***NOTE: IF PROVIDING FLORIDA PRODUCT APPROVAL FL 183
 MAKE SURE NOA SUBMITTED CORRESPONDS TO SAME NOA
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL.GO THE THE
 FLORIDA WEBSITE WWW.FLORIDABUILDING.ORG AND DOWNLOAD
 CORRESPONDING NOA THAT WAS SUBMITTED FOR APPROVAL.
  
 6- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITING BY ARCHITECT OF RECORD.
 ***NOTE: ONE PRODUCT APPROVAL FOR SINGLE HUNG WINDOW IS
 MISSING THE ARCHITECT'S APPROVAL ON ONE COPY.ONLY THE
 APPROVAL STAMP WAS SUBMITTED WITHOUT THE ARCHITECT'S
 SIGNATURE. AND, MAKE SURE PRODUCT APPROVALS LISTED
 ABOVE ARE APPROVED ALSO.
  
 7- STORM SHUTTERS:
 A) PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE AND COMPLETE ALL THE INFORMATION.
  
 B) CIRCLE ON ENGINEERED DRAWINGS SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE AND SPACING TO BE USED. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 C) PROVIDE LEGIBLE DRAWINGS.
  
 8- ENERGY CALCULATIONS:
 A) PROVIDE REVISED FORM 600C-04 R.
  
 B) COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 C) REVISE PREDOMINANT EAVE OVERHANG LENGTH. SEE
 PLANS.
  
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 9- TRUSS PACKAGE:
 A) COMPLETE PACKAGE NEEDS TO HAVE ALL THE ENGINEER'S
 INFORMATION AND NEEDSTO BE SIGNED AND SEALED AS
 REQUIRED BYCHAPTER 471 FLORIDA STATUTE AND SEC.
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE.BOTH
 COPIES.
  
 B) COMPLETE TRUSS PACKAGE NEEDS TO BE APPROVED BY THE
 ARCHITECT OF RECORD.
  
 C) PROVIDE COMPLETE AND CORRECT TRUSS PACKAGE
 INFORMATION TO THE BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
  
  
 10- SHEET 1 OF 4:.
 A)THIS IS NOT AN ALTERATION LEVEL 2. SEE SEC. 307 OF
 EXISTING BUILDING CODE AND REVISE AS REQUIRED.
  
 B) TOTAL ROOF DEAD LOAD LINE IN DESIGN PARAMETERS
 INFORMATION IS BLANK. REVISE AS REQUIRED.
  
 11- SHEET 2 OF 4: THIS IS NOT A FLOOR PLAN ADDITION
 REVISION TO PERMIT 06080496. THIS IS A COMPLETE
 SEPARATE PERMIT. REVISE NOTES AS REQUIRED.
  
 12- SHEET 3 OF 4:
 A) FOUNDATION PLAN NOTE REGARDING 8"X12" POURED
 COLUMN DOESN'T MATCH INFORMATION SHOWN ON WALL AND BEAM
 ATTACHMENT DETAIL ON SHEET 4 OF 4. REVISE AS REQUIRED
 TO MATCH.
  
 B) GABLE END DETAIL:
 * WHERE IS THE ROOF SHEATHING AND WALL SHEATHING
 SCHEDULE?.
 ** USP STRAP SPECIFIED DOESN'T MATCH INFORMATION
 GIVEN ON ROOF FRAMING PLAN. REVISE AS REQUIRED TO MATCH
 AND SEE TRUSS CONNECTOR CATALOG FOR PROPER SIZE AND
 NUMBER OF FASTENERS REQUIRED. SEC. 106.1.2 CITY
 AMENDMENTS STO FBC 2004.
  
 13- SHEET 4 OF 4:
 A) INFORMATION ON FOOTING ATTACHMENT DETAIL IS NOT
 LEGIBLE. SEE MINIMUM EMBEDEMENT. REVISE AS REQUIRED.
  
 B) TYPICAL WALL SECTION:
 * INSTALLING SHINGLES OR CEMENT TILE.ROOF LOADING
 IS DIFFERENT. REVISE AS REQUIRED.
  
 ** REVISE TYPE OF NAIL REQUIRED FOR ROOF SHEATHING.
 SEE SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE
 FOR MIN. TYPE OF NAIL REQUIRED.
  
 *** REVISE TRUSS CONNECTOR TO MATCH TRUSS ANCHOR
 SCHEDULE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-12-11 Cont ID  
Sent By btrobaug Date 2007-12-11 Time 13:10 Rev Time 0.00
Received By btrobaug Date 2007-12-11 Time 08:00 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-11-26 Cont ID  
Sent By btrobaug Date 2007-11-26 Time 07:45 Rev Time 0.00
Received By btrobaug Date 2007-11-26 Time 06:47 Sent To B
Notes
2007-11-26 07:42:58 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE REVISION IS NOT CLEARLY INDICATED BY CLOUDING,
 DELTA'S OR ANY OTHER USUAL TYPE OF MARKING THAT WOULD
 INDICATE THE CHANGES TO THE PLAN. PLEASE INDICATE SAME
 AND RESUBMIT. 106.1.1 FBC AS AMENDED.
  
 2} PER FLORIDA STATUTE 481.221 (4):NO REGISTERED
 ARCHITECT SHALL AFFIX, OR PERMIT TO BE AFFIXED, HER OR
 HIS SEAL OR SIGNATURE TO ANY FINAL CONSTRUCTION
 DOCUMENT OR INSTRUMENT OF SERVICE WHICH INCLUDES ANY
 PLAN, SPECIFICATION, DRAWING, OR OTHER DOCUMENT WHICH
 DEPICTS WORK WHICH SHE OR HE IS NOT COMPETENT TO
 PERFORM. THE SIGNATURE ON THE PLANS IS NOT THE SAME
 SIGNATURE ON THE PERMITTED SET. SUBMIT DOCUMENTATION
 INDICATING THE SIGNATURE OF THE ARCHITECT OF RECORD,
 SIGNED AND NOTORIZED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-11-05 Cont ID  
Sent By btrobaug Date 2007-11-05 Time 07:48 Rev Time 0.00
Received By btrobaug Date 2007-11-05 Time 06:47 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-12-11 Cont ID  
Sent By btrobaug Date 2007-11-05 Time 07:45 Rev Time 0.00
Received By btrobaug Date 2007-11-05 Time 07:45 Sent To E
Notes
2007-11-05 07:45:11 
  
 OPENED IN ERROR./WRT.
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-01 Cont ID  
Sent By btrobaug Date 2007-10-01 Time 12:29 Rev Time 0.00
Received By btrobaug Date 2007-10-01 Time 11:57 Sent To B
Notes
2007-10-01 12:29:10 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE WATER HEATER IS NOT INCLUDED IN THE LOAD
 CALCULATION PER 220.82(A)(4). INDICATE WHY THE WATER
 HEATER IS NOT IN THE 150 AMP PANEL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-14 Cont ID  
Sent By btrobaug Date 2007-08-14 Time 07:38 Rev Time 0.00
Received By btrobaug Date 2007-08-13 Time 16:52 Sent To M
Notes
2007-08-14 07:38:26 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THESE COMMENTS ARE UNANSWERED FROM THE PREVIOUS
 REVIEW.
  
 COMMENTS MARKED WITH* ARE ADDITIONAL
  
 1} LOCATE THE NEW WATER HEATER AND DISCONNECTON THE
 PLAN SO THAT COMPLIANCE WITH 110.26 AND 240.24 CAN BE
 DETERMINED.
  
 2} THE 2 #4 FEEDERS TO THE WATER HEATER DISCONNECTON
 THE RISER DO NOT CORRELATE WITH THE #8CONDUCTORS IN
 THE PANEL SCHEDULE, AND A #6 ON A NOTE ON THE PLAN.
 CORRELATE SAME.REMOVE ALL NOTES AND CALCULATIONS NOT
 PERTINENT FOR RECORD KEEPING FROM THE PLAN FOR
 CLARITY.
  
 3} THE FEEDER FOR THE WATER HEATER MUST GROUNDED PER
 250.110 SIZED PER 250.122.
  
 4} OK
  
 5} THE FACT THAT THE 60 AMP DISCONNECT IS SHOWN "DOUBLE
 LUGGED" FROM THE METER, REQUIRES THAT IT BE SERVICE
 RATED PER 225.36. AND * GROUPED PER 230.70(A)(1)
  
 6} 225.34(A) GENERAL THE TWO TO SIX DISCONNECTS AS
 PERMITTED IN 225.33 SHALL BE GROUPED. EACH DISCONNECT
 SHALL BE MARKED TO INDICATE THE LOAD SERVED. ALSO SEE
 230.72(A)
  
 7} THE WATER HEATER IS LISTEDIN THE PANEL SCHEDULE ON
 A 40 AMP BREAKER, BUT INDICATED AS HAVING A SEPARATE
 DISCONNECT ON THE RISER, CORRELATE SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-07 Cont ID  
Sent By btrobaug Date 2007-05-07 Time 09:52 Rev Time 1.00
Received By btrobaug Date 2007-05-07 Time 07:13 Sent To M
Notes
2007-05-07 07:53:43 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} LOCATE THE NEW WATER HEATER AND DISCONNECTON THE
 PLAN SO THAT COMPLIANCE WITH 110.26 AND 240.24 CAN BE
 DETERMINED.
  
 2} THE 2 #4 FEEDERS TO THE WATER HEATER DISCONNECTON
 THE RISER DO NOT CORRELATE WITH THE #8CONDUCTORS IN
 THE PANEL SCHEDULE, AND A #6 ON A NOTE ON THE PLAN.
 CORRELATE SAME.REMOVE ALL NOTES AND CALCULATIONS NOT
 PERTINENT FOR RECORD KEEPING FROM THE PLAN FOR
 CLARITY.
  
 3} THE FEEDER FOR THE WATER HEATER MUST GROUNDED PER
 250.110 SIZED PER 250.122.
  
 4} THE CIRCUIT NUMBERS ON THE PANEL SCHEDULE ARE
 INCORRECT AND ARE DUPLICATED. SEE 408.4 2005 NEC
 REGARDING"SPECIFIC PURPOSE OR USE".
  
 5} THE FACT THAT THE 60 AMP DISCONNECT IS SHOWN "DOUBLE
 LUGGED" FROM THE METER, REQUIRES THAT IT BE SERVICE
 RATED PER 225.36.
  
 6} 225.34(A) GENERAL THE TWO TO SIX DISCONNECTS AS
 PERMITTED IN 225.33 SHALL BE GROUPED. EACH DISCONNECT
 SHALL BE MARKED TO INDICATE THE LOAD SERVED. ALSO SEE
 230.72(A)
  
 7} THE WATER HEATER IS LISTEDIN THE PANEL SCHEDULE ON
 A 40 AMP BREAKER, BUT INDICATED AS HAVING A SEPARATE
 DISCONNECT ON THE RISER, CORRELATE SAME.
  
 8} THE ADDITION TO THE BEDROOMS DO NOT COMPLY WITH
 210.52(A)(1) & (2) FOR RECEPTACLE SPACING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-10 Time 14:01 Rev Time 0.00
Received By adarroug Date 2007-12-10 Time 14:01 Sent To E
Notes
2007-12-10 14:02:15TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-21 Cont ID  
Sent By adarroug Date 2007-11-21 Time 08:45 Rev Time 0.00
Received By adarroug Date 2007-11-21 Time 08:45 Sent To E
Notes
2007-11-21 08:45:41TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-02 Cont ID  
Sent By adarroug Date 2007-11-02 Time 11:53 Rev Time 0.00
Received By adarroug Date 2007-11-02 Time 11:53 Sent To E
Notes
2007-11-02 11:53:52TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-27 Cont ID  
Sent By adarroug Date 2007-09-27 Time 10:13 Rev Time 0.00
Received By adarroug Date 2007-09-27 Time 10:13 Sent To Z
Notes
2007-09-27 10:13:42TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 16:49 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 16:49 Sent To E
Notes
2007-08-06 16:50:25TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-20 Cont ID  
Sent By jgomez Date 2007-06-20 Time 16:48 Rev Time 0.00
Received By jgomez Date 2007-05-03 Time 14:14 Sent To  
Notes
2007-05-03 14:16:34TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2007-08-14 Cont ID  
Sent By tgordon Date 2007-08-14 Time 10:38 Rev Time 0.20
Received By tgordon Date 2007-08-14 Time 10:38 Sent To B
Notes
2007-08-14 10:42:52MECHANICAL PERMIT #07050104 HAS BEEN VOIDED AND NO
 MECHANICAL WORK IS TO BE DONE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-07 Cont ID  
Sent By tgordon Date 2007-05-07 Time 11:55 Rev Time 0.25
Received By tgordon Date 2007-05-07 Time 11:55 Sent To P
Notes
2007-05-07 11:57:55*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM600C-04R,
 SEE 2004 FBC 13-600.3.C (12-8-06 REVISION).
  
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) MECHANICAL PERMIT #07050104 HAS BEEN APPLIED FOR BUT
 NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY
 OF WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-05-10 Cont ID  
Sent By jleech Date 2007-05-10 Time 07:11 Rev Time 0.00
Received By jleech Date 2007-05-10 Time 07:09 Sent To B
Notes
2007-05-10 07:11:37NO PLUMBING SHOWN ON PLANS

Review Stop Z ZONING
Rev No 2 Status P Date 2007-10-01 Cont ID  
Sent By choops Date 2007-10-01 Time 09:11 Rev Time 0.00
Received By choops Date 2007-10-01 Time 09:11 Sent To E
Notes
2007-10-01 09:13:05***PASSED - RESUB #2***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-05-04 Cont ID  
Sent By choops Date 2007-05-04 Time 11:21 Rev Time 0.00
Received By choops Date 2007-05-04 Time 11:21 Sent To E
Notes
2007-05-04 11:27:52BUILDING HEIGHT NOT TO EXCEED 30'