Plan Review Details - Permit 07050076
Plan Review Stops For Permit 07050076
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-17 Cont ID  
Sent By jwitmer Date 2007-12-17 Time 11:48 Rev Time 0.55
Received By jwitmer Date 2007-12-17 Time 11:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-13 Cont ID  
Sent By jwitmer Date 2007-09-13 Time 13:06 Rev Time 2.22
Received By jwitmer Date 2007-09-13 Time 13:06 Sent To  
Notes
2007-09-13 13:14:52BUILDING PLAN REVIEW
 PERMIT: 07050076
 ADD: 1817 S DIXIE HWY
 CONT: JEFFERY GOMERSALL BUILDING
 TEL: (561718-1867
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 NEW COMMENT:THE FIRST GENERATION OF PLANS SUBMITTED
 INDICATED HANDICAPPED PARKING AND ACCESSIBLE AISLES,
 THIS 2ND SET OF PLANS DOESN'T INDICATE ANY ACCESSIBLE
 SPACES.11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED AREAS SHALL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20 % OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX
 OR A SINGLE UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STORAGE OR ALARMS.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-15 Cont ID  
Sent By jwitmer Date 2007-06-15 Time 17:05 Rev Time 1.11
Received By jwitmer Date 2007-06-15 Time 17:05 Sent To PC
Notes
2007-06-15 17:17:25BUILDING PLAN REVIEW
 PERMIT: 07050076
 ADD: 1817 S DIXIE HWY
 CONT: JEFFERY GOMERSALL BUILDING
 TEL: (561718-1867
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 NOTE: SITE WALL WAS STRUCK FROM THE PERMIT APPLICATION
 AND THE VALUE DROPPED TO REFLECT SUCH WORK BEING
 DROPPED. PLEASE REMOSE THE S1 AND S2 THAT PERTAIN TO
 THE SITE WALL.
 SITE WALL WILL REQUIRE A SEPERATE PERMIT, FEES AND
 REVIEW.
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2)) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE
 FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF
 THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) 3) PLEASESEE AREA CALCULATION, LS1 INDICATES 2293
 SQ FT AND E0THE AREA INDICATED ON THE PLANS IS 2421.
  
 4) PLANS SUBMITTED AFTER DEC 8, 2006 ARE TO BE DESIGNED
 TO THE 2006 FBC, BUILDING.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-07-08 Cont ID  
Sent By btrobaug Date 2008-07-08 Time 15:04 Rev Time 0.00
Received By btrobaug Date 2008-07-08 Time 14:52 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-03-14 Cont ID  
Sent By dpalmer Date 2008-03-14 Time 08:01 Rev Time 0.00
Received By dpalmer Date 2008-03-14 Time 08:01 Sent To PC
Notes
2008-03-14 08:02:15REV #3

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-31 Cont ID  
Sent By dpalmer Date 2007-10-31 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2007-10-31 Time 16:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-04 Cont ID  
Sent By dpalmer Date 2007-09-04 Time 08:20 Rev Time 0.00
Received By dpalmer Date 2007-09-04 Time 07:38 Sent To  
Notes
2007-09-04 08:20:382007-09-04 08:20:38
  
 ** DENIED2ND REVIEW**
  
 ** PLEASE SEE THE COMMENT BELOW FROM THE PREVIOUS
 REVIEW.
  
 1) NOTE: PLEASE BE SURE WHEN TYPING RESPONSE LETTERS TO
 ACCURATELY DEPICT THE NOTES FORM THE REVIEWER AS TYPED
 OR NOTED. PLEASE SEE NOTE #8 FROM THE PREVIOUS REVIEW
 WHICH HAS CODES AND SECTIONS MIS-QUOTED FORM THE
 PREVIOUS REVIEW.
 THIS COULD VERY WELL LEAD TO CONFUSION OR
 MISUNDERSTANDING OF THE NOTES.
  
 2) NOTE: PLEASE SEE NOTE #8 FROM THE PREVIOUS REVIEW.
 THE RESPONSE FROM DESIGNER SPEAKS OFLOADS AS BEING
 DETERMINED FROM THE NEC FOR LOAD CALCULATIONS WHEREAS
 THE NOTE HAD TO DO THE FBC CHAPTER 13 FOR LIGHTING
 LOADS.
 THE*MINIMUM* LOADS FIGURED FOR LIGHTING IN THE
 SERVICE CALCULATIONS FOR SIZING A SERVICE AND BRANCH
 CIRCUITS AS REQUIRED IN THE NEC (220) IS COMPLETELY
 DIFFERENT THAN THE MAXIMUM LOADS FOR LIGHTING
 ALLOWANCES PER THE FLORIDA ENERGY CODE.
 PLEASE SEE THE PREVIOUS REVIEW NOTE #8 WHICH SPOKE OF
 THE LOADS TO BE FIGURED FOR TRACK LIGHTING PER
 13-415.2.ABC.1.2. THIS IS A MAXIMUM ALLOWANCE BASED ON
 THE TRACK LIGHTING FIXTURES OR LENGTH OF TRACK BASED ON
 A MINIMUM AS SET FORTH BY THE FBC DEPENDING ON THE TYPE
 OF TRACK LIGHTING BEING INSTALLED.
 PLEASE ALSO SEE THE MAXIMUM LIGHTING ALLOWANCES PER
 13-415.2
 PLEASE PROVIDE THE INFORMATION FOR THESE MAXIMUM
 LIGHTING LEVELS.
  
 3) NOTE: PLEASE SEE AS OF THE THREE NEW SETS SUBMITTED
 ONLY TWO SETS ARE COMPLETED BEING SIGNED, AND SEALED.
 PLEASE KNOW ONLY TWO ARE NEEDED HOWEVER IF THREE IS
 BEING SUBMITTED AND WANTING TO BE STAMPED FOR
 PERMITTING AND CONTRACTOR'S FIELD SETS THESE WOULD ALL
 NEED TO BE SIGNED, DATED AND SEALED.
 *PLEASE SEE THE A-SHEETS IN ONE SET.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-04 07:38:232007-09-04 07:38:23
  
 IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-17 Cont ID  
Sent By dpalmer Date 2007-05-17 Time 10:50 Rev Time 0.00
Received By dpalmer Date 2007-05-17 Time 08:58 Sent To  
Notes
2007-05-17 10:50:57** UNSAT**
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE: PLEASE SEE PLANS MUST REFLECT CURRENT CODES IN
 EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK AS
 SHOWN.
 PLEASE KNOW HOWEVER AT THIS TIME AND AS OF DECEMBER
 8TH, 2006 THE STATE IS UNDER THE 2004 FBC W/2006
 REVISIONS. THESE ARE ONLY REVISIONS TO THE 2004 FBC.
 PLEASE ALSO SEE THE PLANS INDICATE * PALM BEACH COUNTY*
 LOCAL AMENDMENTS.
 SOME OF THESE ARE STATED ON ELECTRICAL HOWEVER SHOULD
 ALSO BE ON COVER SHEETS.
 WE ARE UNDER THE 2005 NFPA-70. (NEC).
 PLEASE ALSO LIST THE FOLLOWING.
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE VERIFY THE LOCATION OF PROJECT AS THE
 SITE/LOCATION PLAN INDICATES TWO LOCATIONS.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK IS TO INCLUDE ALL LABOR AND MATERIALS EVEN IF ANY
 EQUIPMENT/MATERIALS ETC ARE OWNER SUPPLIED.
 FBC 108.3
  
 4) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE
 SUBMITTED IS NOT COMPLETE AND NEEDS TO CONTAIN
 SPECIFICS FOR CIRCUITING TO ROOMS AND AREAS IN WHICH
 THEY FEED.
 PLEASE ALSO INCLUDE EXISTING CIRCUITING AS THERE ARE
 REQUIRED ITEMS MISSING NOT ON PANEL SCHEDULE. *SEE NOTE
 FOR LOAD CALCULATIONS.
  
 5) NOTE: PLEASE SEE 600.5 FOR MISSING SIGN CIRCUIT. NEW
 ORE EXISTING?
 408.4, 220, ETC.
  
 6) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER
 210.62. NEW OR EXISTING?
 PLEASE ALSO SEE 220.43 FOR LOADS.
  
 7) NOTE: PLEASE COMPLETE AND COORDINATE LOAD
 CALCULATIONS. PLEASE SEE THE CODE SECTIONS REFLECTED
 ARE THAT FROM THE PREVIOUS CODE. PLEASE SEE THE
 RECEPTACLE LOAD MAY NOT BE USED AS 1VA PER FT, WHEN A
 KNOWN RECEPTACLE LOAD IS AVAILABLE. PLEASE SEE THAT THE
 PLANS MENTIONS ALL RECEPTACLES ARE EXISTING, HOWEVER
 NOT SHOWN, SO PLEASE CORRELATE.
 PLEASE SEE OTHER NOTES FOR RECEPTACLES.
 PLEASE SEE THAT LOADS SHOWN BELOW PANEL SCHEDULE DO NOT
 CORRELATE WITH THAT OF THE LOAD CALCULATIONS ON THE
 SAME SHEET.
 PLEASE SEE THE 2005 NEC.220.
  
 8) NOTE: PLEASE CLARIFY THE BUILDING. AT THIS TIME THIS
 SPACE APPEARS TO BE PART OF A LARGER BUILDING AND MAY
 NOT MEET THE DEFINITION OF BUILDING.
 PLEASE SEE FBC CHAPTER 1313-415.1.ABC.1.1, .1.2 AND
 .1.3 FOR POSSIBLE LIGHTING CONTROLS REQUIRED. PLEASE
 SEE 13-415.2 AS PERFORMANCE CALCULATIONS ARE REQUIRED
 FOR ANY SIZE BUILDING.
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING LOADS TO
 BE SHOWN. (HIGHER OF THE TWO AS SHOWN BASED ON FIXTURES
 OR LINEAR FT OF TRACK) FOR 120V SYSTEMS.
  
 ** PLEASE KNOW AS SOME ITEMS ARE NOT CLEAR AT THIS
 TIME, ALL COMMENTS FOR CODE COMPLIANCE AND REVIEW CAN
 NOT BE DONE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2007-12-04 Cont ID  
Sent By rchokshi Date 2007-12-04 Time 09:12 Rev Time 0.00
Received By rchokshi Date 2007-12-04 Time 09:09 Sent To  
Notes
2007-12-04 09:12:43THIS IS ALL INTERIOR WORK.OUTSIDE WORK, SIDEWALK,
 DRIWAY, SILT FENCE ETC ARE IN PERMIT# 07050649.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2007-11-06 Cont ID  
Sent By rchokshi Date 2007-11-06 Time 14:55 Rev Time 0.00
Received By rchokshi Date 2007-11-06 Time 14:46 Sent To  
Notes
2007-11-06 14:55:21**FAILED **
  
 1. PLEASE ADD CITY STANDARDS NOTES ON DRAWINGS FOR
 PARKING, DRIVEWAY, SIDEWALK, SIDEWALK SLOPE ETC. YOU
 CAN GET CITY'S STANDARDS NOTES IN A C. D. FROM 45TH
 STREET, 494-1040
 OUR RESPONSE:ACCORDING TO YOUR RESPONSE, SEE SHEET
 A0. SHEET A0 DOES NOT SHOW CITY STANDARD NOTES AS WE
 ASKED FOR.
  
 2. YOU NEED TO SHOW SIDEWALK, PARKINGS, DRIVEWAYETC.,
 ON YOUR DRAWINGS.
 PER YOUR RESPONSE SEE SHEET A0.SHEET A0DOES NOT
 SHOW , THIS ITEM 2
  
 4. NEED TO SHOW THE DETAILS OF SILT FENCE, CLOTHES
 USED,HEIGHT, POST FOR SILT FENCE ETC FOR POLLUTION
 PREVENTION. NOT JUST SILT FENCE AROUND SITE.
 OUR RESPONSE: SHEET A0DOESNOT SHOWDETAILS OF SILT
 FENCE, WE ASKED LAST TIME.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-09-11 Cont ID  
Sent By rchokshi Date 2007-09-11 Time 11:15 Rev Time 0.00
Received By rchokshi Date 2007-09-11 Time 11:04 Sent To  
Notes
2007-09-11 11:15:35**FAILED **
  
 1. IT APPEARS THAT THE SIDEWALK IS IN CITY'S RIGHT OF
 WAY.YOU NEED AN APPROVAL FROM WINDEL PALMER, BEFORE
 WE LOOK AT IT,1000 45TH STREET,, 494-1040,ENG
 DEPT.
 2. PLEASE ADD CITY STANDARDS NOTES ON DRAWINGS FOR
 PARKING, DRIVEWAY, SIDEWALK, SIDEWALK SLOPE ETC. YOU
 CAN GET CITY'S STANDARDS NOTES IN A C. D. FROM 45TH
 STREET, 494-1040
 3. YOU NEED TO SHOW SIDEWALK, PARKINGS, DRIVEWAYETC.,
 ON YOUR DRAWINGS.
 4. NEED TO SHOW THE DETAILS OF SILT FENCE, CLOTHES
 USED,HEIGHT, POST FOR SILT FENCE ETC FOR POLLUTION
 PREVENTION. NOT JUST SILT FENCE AROUND SITE.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-06-01 Cont ID  
Sent By rchokshi Date 2007-06-01 Time 11:10 Rev Time 0.00
Received By rchokshi Date 2007-06-01 Time 10:54 Sent To  
Notes
2007-06-01 11:10:01**FAILED **
  
 1. NEED PROPERTY SURVEY TO DETERMINE WHETHER THE SIDE
 WALK IS IN YOUR PROPERTY OR IT IS IN CITY'S RIRGT OF
 WAY.
 2. IF THE SIDEWALK IS IN CITY'S RIGHT OF WAY, THEN YOU
 NEED AN APPROVAL FROM WINDEL PALMER, BEFORE WE LOOK AT
 IT,1000 45TH STREET,, 494-1040,ENG DEPT.
 3. PLEASE ADD CITY STANDARDS NOTES ON DRAWINGS FOR
 PARKING, DRVEWAY, SIDEWALK, SIDEWALK SLOPE ETC. YOU CAN
 GET CITY'S STANDARDS NOTES IN A C. D. FROM 45TH STREET
  
 4. NEED A POLLUTION PREVENTION DETAILS, SILT FENCE
 AROUND THE SITE.
  
 RASIK CHOKSHI 805-6723
2007-05-17 09:07:02REPLACING SIDE WALK ON SOUTH SIDE OF BUILDING, NEEDS
 ENG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-11-02 Cont ID  
Sent By mwennerg Date 2007-11-02 Time 10:56 Rev Time 0.00
Received By mwennerg Date 2007-11-02 Time 10:56 Sent To  
Notes
2007-11-02 10:56:42PLANS APPROVED ON 9/24/07. NEW LS SHEET STAMPED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-09-24 Cont ID  
Sent By mawillia Date 2007-09-24 Time 13:34 Rev Time 0.00
Received By mawillia Date 2007-09-24 Time 13:06 Sent To  
Notes
2007-09-24 13:33:54*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN SATISFIED;PLAN SHEETS A-2, LS-1, AND E-1 WERE
 STAMPED, INITIALED, AND DATED.PLEASE BE ADVISED THAT
 ONLY TWO OF THREE SUBMITTED PLAN SETS WERE
 FIRE-STAMPED, THE THIRD NOT STAMPED DUE TO ABSENCE OF
 SIGN AND SEAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-14 Cont ID  
Sent By mcarsill Date 2007-06-14 Time 12:07 Rev Time 0.00
Received By mcarsill Date 2007-06-14 Time 11:59 Sent To  
Notes
2007-06-14 12:07:191. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 2. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 3. PLANS DO NOT DECLARE ANY EXISTING OR NEW FIRE
 SPRINKLER OR FIRE ALARM EQUIPMENT. PLEASE PROVIDE
 INFORMATION.
  
 4. ELEVATION DRAWINGS DO NOT DISPLAY BUILDING ADDRESS.
 THE BUILDING ADDRESS IS REQUIRED ON THE PROPER
 ELEVATION. THE NUMBERS NEED TO BE AT LEAST SIX INCHES
 HIGH AND AT LEAST ONE INCH WIDE.
  
 5. PLEASE ENSURE THAT THE EXISTING EXIT SIGNS ARE
 FUNCTIONING PROPERLY.
  
 MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-06-25 Cont ID  
Sent By adarroug Date 2008-06-25 Time 11:09 Rev Time 0.00
Received By adarroug Date 2008-06-25 Time 11:09 Sent To E
Notes
2008-06-25 11:09:21TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-10 Cont ID  
Sent By spalmer Date 2008-01-10 Time 09:08 Rev Time 0.00
Received By spalmer Date 2008-01-10 Time 09:08 Sent To Z
Notes
2008-01-10 09:08:25TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-21 Cont ID  
Sent By adarroug Date 2007-11-21 Time 11:30 Rev Time 0.00
Received By adarroug Date 2007-11-21 Time 11:30 Sent To  
Notes
2007-11-30 13:50:40TO "COMM" BD#49
2007-11-21 11:30:50WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 16:20 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 16:20 Sent To  
Notes
2007-10-30 15:05:50TO "COMM" BD#19
2007-10-11 16:21:11WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 13:18 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 13:18 Sent To  
Notes
2007-08-31 08:55:02TO "COMM" BD#8
2007-08-06 13:19:05WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-30 Cont ID  
Sent By rbrown Date 2007-07-30 Time 09:16 Rev Time 0.00
Received By rbrown Date 2007-05-03 Time 15:41 Sent To  
Notes
2007-05-15 09:14:35TO "COMM" BD#23
2007-05-03 15:41:39WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-05-31 Cont ID  
Sent By tgordon Date 2007-05-31 Time 09:39 Rev Time 0.20
Received By tgordon Date 2007-05-31 Time 09:39 Sent To  
Notes
2007-05-31 09:40:06NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-09-22 Cont ID  
Sent By kstevens Date 2007-09-22 Time 07:28 Rev Time 0.00
Received By kstevens Date 2007-09-22 Time 07:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By kstevens Date 2007-06-09 Time 14:52 Rev Time 0.00
Received By kstevens Date 2007-06-09 Time 14:52 Sent To  
Notes
2007-06-09 15:48:42DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE STATUS OF THE FIRM
 LICENSE NUMBER, (CERTIFICATE OF AUTHROIZATION), IS
 LISTED AS DELINQUENT. PLEASE HAVE STATUS UPGRADED PRIOR
 TO RESUBMITTING. FAC 61G1-16.004(4) & FS 481.219,
 481.2055.
  
 2. SHT A.O INDICATES A NEW DRINKING FOUNTAIN. PLEASE
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15
 AND ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 3. SHT LS.1 DETAIL 2 KITCHENETTE SINK. SHOW COMPLIANCE
 FOR THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE
 D. 11-4.24.7 FAUCETS
  
 4. A TURNING AREA IS REQUIRED IN THE KITCHENETTE AREA
 PER SECTION 11-4.2.3.
  
 5. SHT LS.1 DETAIL 2 CODE REFERENCE IS FBC-2001. THE
 CODE ADOPTED IS FBC-2004. PLEASE CORRECT CODE
 REFERENCE.
  
 6. SUBMIT A SANITARY RISER ISOMETRIC DIAGRAM FOR THE
 DRAINAGE WASTE & VENT FOR THE NEW DRINKING FOUNTAIN PER
 SECTION 106.3.5.1.3(4)(6)(13). SHOW ALL PIPE SIZES,
 TRAPS, VENTS AND POINT OF CONNECTION.
  
 7. SUBMIT A WATER RISER ISOMETRIC DIAGRAM FOR THE
 DRINKING FOUNTAIN. SHOW ALL PIPE SIZES, VALVES, AND
 INDICATE THE LOCATION OF THE REQUIRED RPZV BACKFLOW.
 SECTION 106.3.5.1.3(3)(8)(10)(13).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 2008-01-14 Cont ID  
Sent By adavila Date 2008-01-14 Time 17:25 Rev Time 0.00
Received By adavila Date 2008-01-11 Time 17:28 Sent To B
Notes
2008-01-14 17:26:10PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 INTERIOR RENOVATIONS ONLY.

Review Stop Z ZONING
Rev No 4 Status F Date 2007-12-04 Cont ID  
Sent By adavila Date 2007-12-04 Time 10:06 Rev Time 0.00
Received By adavila Date 2007-12-04 Time 09:44 Sent To  
Notes
2007-12-04 09:53:40PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.BASED ON THE REVISED WORK VALUE DATED OCTOBER 11,
 2007, THE NEW INSIDE COST IS $54,354.43 AND THE OUTSIDE
 PERMIT COST IS $60,000.BOTH OF THESE VALUES ADD UP TO
 $114,354.43, WHICH EXCEEDS 50 PERCENT OF THE
 IMPROVEMENT VALUE ($113,234.00).PLEASE ADDRESS.
  
 A. PLEASE NOTE THAT PURSUANT TO SECTION 94-441(C) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS,
 RENOVATIONS, REPAIRS, ALTERATIONS OR REDEVELOPMENTS
 WHICH EXCEED 50 PERCENT OF THE VALUE OF THE STRUCTURE
 SHALL COMPLY WITH THE PROVISIONS OF ARTICLE XIV,
 LANDSCAPING, LAND CLEARING, AND TREE PROTECTION, OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS.
 I. A LANDSCAPE PLAN, PREPARED, SIGNED AND SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT, AND MEETING THE
 PROVISIONS OF ARTICLE XIV, LANDSCAPING, LAND CLEARING,
 AND TREE PROTECTION, OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS SHALL BE PROVIDED.
 II. THE LANDSCAPE REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-09-20 Cont ID  
Sent By adavila Date 2007-09-20 Time 13:28 Rev Time 0.00
Received By adavila Date 2007-09-20 Time 09:01 Sent To  
Notes
2007-09-20 13:28:35PLANNING AND ZONING DEPARTMENT
  
 ***PASSED***
  
 TREE ALTERATION PERMIT RECEIVED ON SEPTEMBER 4, 2007.
 ALL CONDITIONS OF THE TREE ALTERATION PERMIT SHALL BE
 MET PRIOR TO C.O.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-08-29 Cont ID  
Sent By adavila Date 2007-08-29 Time 13:16 Rev Time 0.00
Received By adavila Date 2007-08-29 Time 09:04 Sent To  
Notes
2007-09-07 11:26:37ADDITIONAL COMMENTS:
  
 1.TREE REMOVAL APPLICATION PERMIT RECEIVED ON
 09/04/2007.
  
 2.IT CAME TO STAFF'S ATTENTION THAT THE RENOVATION
 VALUE OF ALL PERMITS APPLIED FOR THIS SITE EXCEEDS 50%
 OF THE IMPROVEMENT VALUE OF THE STRUCTURE.CURRENT
 INFORMATION BY THE PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE STATES THAT THE IMPROVEMENT VALUE OF
 THE STRUCTURE IS $226,468.THEREFORE, COMMENT NO. 5
 FROM THE PREVIOUS REVIEW (1ST REVIEW DATED MAY 30,
 2007) STILL NEEDS TO BE ADDRESSED (SEE BELOW).
  
 3. PURSUANT TO SECTION 94-441(C) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, RENOVATIONS, REPAIRS,
 ALTERATIONS OR REDEVELOPMENTS WHICH EXCEED 50 PERCENT
 OF THE VALUE OF THE STRUCTURE SHALL COMPLY WITH THE
 PROVISIONS OF ARTICLE XIV, LANDSCAPING, LAND CLEARING,
 AND TREE PROTECTION, OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
 A. A LANDSCAPE PLAN, PREPARED, SIGNED AND SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT, AND MEETING THE
 PROVISIONS OF ARTICLE XIV, LANDSCAPING, LAND CLEARING,
 AND TREE PROTECTION, OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS SHALL BE PROVIDED.
 B. THE LANDSCAPE REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM.
 C. PLEASE PROVIDE THE APPRAISED VALUE OF THE STRUCTURE.
 THE TOTAL VALUE OF THE PERMITS FOR THE RENOVATION OF
 THE BUILDING WILL BE CALCULATED TO DETERMINE THE 50
 PERCENT THRESHOLD.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
2007-08-29 13:16:25PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.(REPEAT COMMENT) A TREE REMOVAL LICENSE APPLICATION
 SHALL BE SUBMITTED TO THE PLANNING AND ZONING
 DEPARTMENT FOR ALL TREES (7 PALMS) THAT WILL BE REMOVED
 AND/OR RELOCATED.
  
 2.THE TREE ALTERATION PERMIT SHALL BE SUBMITTED TO
 THE PLANNING AND ZONING DEPARTMENT PRIOR TO BUILDING
 PERMIT APPROVAL.PLEASE SUBMIT THE FOLLOWING WITH THE
 TREE ALTERATION PERMIT:
 A. A TREE SURVEY.
 B. LIST OF TREES TO BE RELOCATED ON OR OFF SITE.
 C. LOCATION OF TREES TO BE RELOCATED.
  
 COMMENTS/QUESTIONS CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-30 Cont ID  
Sent By adavila Date 2007-05-30 Time 16:12 Rev Time 0.00
Received By adavila Date 2007-05-21 Time 20:37 Sent To  
Notes
2007-05-30 16:12:43PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE TWO (2) SIGNED AND SEALED SURVEYS.SURVEY
 SHALL BE LESS THAN A YEAR OLD.
  
 2. PROVIDE A LETTER FROM THE ENGINEERING SERVICES
 DEPARTMENT APPROVING THE PROPOSED ON-STREET PARKING
 SPACES.THE LETTER SHALL ALSO STATE THE TOTAL NUMBER
 OF AVAILABLE PARKING SPACES ALONG KANUGA DRIVE.
 A. PLEASE NOTE THAT ALL ON-STREET PARKING SPACES SHALL
 BE DELINEATED PRIOR TO BUILDING PERMIT APPROVAL.
 B. PROVIDE WIDTH AND DEPTH DIMENSIONS OF ALL APPROVED
 ON-STREET PARKING SPACES ON THE SITE PLAN.
 C. PROVIDE PARKING STALL DETAILS OF ALL APPROVED
 ON-STREET PARKING SPACES.
 D. PLEASE NOTE THAT FOUR (4) PARKING SPACES, ONE OF
 WHICH SHALL BE A HANDICAP PARKING SPACE, SHALL BE
 MAINTAINED FOR THIS SITE.
  
 3. HANDICAP SYMBOL SHALL BE TWO (2) FEET FROM THE OPEN
 END OF THE PARKING SPACE.
  
 4. PROVIDE DIMENSIONS OF THE AISLE WIDTH.PLEASE NOTE
 THAT PER SECTION 94-485(J) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, TWO-WAY DIRECTION MOVEMENT
 REQUIRES A MINIMUM OF 24 FEET WIDE REGARDLESS OF
 PARKING ANGLE AND DIMENSIONS.
  
 5. PURSUANT TO SECTION 94-441(C) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, RENOVATIONS, REPAIRS,
 ALTERATIONS OR REDEVELOPMENTS WHICH EXCEED 50 PERCENT
 OF THE VALUE OF THE STRUCTURE SHALL COMPLY WITH THE
 PROVISIONS OF ARTICLE XIV, LANDSCAPING, LAND CLEARING,
 AND TREE PROTECTION, OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
 A. A LANDSCAPE PLAN, PREPARED, SIGNED AND SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT, AND MEETING THE
 PROVISIONS OF ARTICLE XIV, LANDSCAPING, LAND CLEARING,
 AND TREE PROTECTION, OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS SHALL BE PROVIDED.
 B. THE LANDSCAPE REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM.
 C. PLEASE PROVIDE THE APPRAISED VALUE OF THE STRUCTURE.
 THE TOTAL VALUE OF THE PERMITS FOR THE RENOVATION OF
 THE BUILDING WILL BE CALCULATED TO DETERMINE THE 50
 PERCENT THRESHOLD .
  
 6. PROVIDE LANDSCAPE CALCULATIONS OF WHAT IS EXISTING
 VS. WHAT IS PROPOSED.
  
 7. A TREE REMOVAL LICENSE APPLICATION SHALL BE
 SUBMITTED TO THE PLANNING AND ZONING DEPARTMENT FOR ALL
 TREES (7 PALMS) THAT WILL BE REMOVED AND/OR RELOCATED.
  
  
 8. PROVIDE REAR SETBACK DIMENSION.
  
 9. THE PROPOSED FENCE/WALL IS LOCATED WITHIN THE
 VISIBILITY TRIANGLE.PLEASE NOTE THAT PER SECTION
 94-305(E) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS, AT ANY ROAD INTERSECTIONS, VISIBILITY
 SHALL NOT BE OBSCURED BY ANY ITEM BETWEEN 18 INCHES OR
 8 FEET IN HEIGHT WITHIN A TRIANGLE BEGINNING AT THE
 POINT WHERE PROPERTY LINES MEET AT THE CORNER, THEN 20
 FEET ALONG THE FRONT PROPERTY LINE, THENCE DIAGONALLY
 TO A POINT ALONG THE SIDE PROPERTY LINE 20 FEET FROM
 THE POINT OF BEGINNING, AND THEN TO THE POINT OF
 BEGINNING.SHEET S.2 INCORRECTLY SHOWS THE VISIBILITY
 TRIANGLE BEING AT THE POINT WHERE THE CURBS MEET.
  
 10. THE PROPOSED GATE ALONG THE WEST PROPERTY LINE
 SHALL BE NO LESS THAN 24 FEET WIDE.
  
 11. PLEASE NOTE THAT A RIGHT-OF-WAY PERMIT SHALL BE
 SUBMITTED FOR THE REPLACEMENT OF THE EXISTING
 SIDEWALK.
  
 12. PLEASE NOTE THAT THE LOCATION MAP HIGHLIGHTS TWO
 (2) DIFFERENT PROPERTIES/LOCATIONS.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
2007-05-17 09:03:35NEEDS