Plan Review Details - Permit 07041004
Plan Review Stops For Permit 07041004
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-05-04 Cont ID  
Sent By btrobaug Date 2007-05-04 Time 13:43 Rev Time 0.33
Received By btrobaug Date 2007-05-04 Time 13:34 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-03 Cont ID  
Sent By btrobaug Date 2007-05-03 Time 07:23 Rev Time 0.50
Received By btrobaug Date 2007-05-03 Time 06:51 Sent To I
Notes
2007-05-03 07:12:43 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} THE APPLICATION DESCRIPTION MUST BE CHANGED TO
 REFLECT THE SCOPE OF WORK INTENDED.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 ALL SHEETS.
  
 3} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 4} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-03 Cont ID  
Sent By btrobaug Date 2007-05-03 Time 07:23 Rev Time 0.00
Received By btrobaug Date 2007-05-02 Time 09:25 Sent To PC
Notes
2007-05-02 09:25:22TO "E" BOX