Plan Review Details - Permit 07040936
Plan Review Stops For Permit 07040936
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-29 Cont ID  
Sent By mjacobs Date 2007-06-29 Time 12:50 Rev Time 0.00
Received By mjacobs Date 2007-06-29 Time 11:16 Sent To PC
Notes
2007-06-29 11:17:11PROCESS PLAN / PRINT PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-06-26 Cont ID  
Sent By mjacobs Date 2007-06-26 Time 12:40 Rev Time 0.00
Received By mjacobs Date 2007-06-26 Time 10:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-08 Cont ID  
Sent By mjacobs Date 2007-05-08 Time 11:39 Rev Time 0.00
Received By mjacobs Date 2007-05-08 Time 11:05 Sent To  
Notes
2007-05-08 11:39:54BUILDING PLAN REVIEW
 PERMIT: 07040936
 ADD: 401 DIXIE HWY 4505/3505/2505/1506
 CONT: ANDREA CONSTRUCTION INC.
 TEL: (561)795/1136
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW1ST
 ACTION: DENIED
  
 1)THE VALUE IS TO LOW. IF, IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALLWSWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-22 Cont ID  
Sent By btrobaug Date 2007-06-22 Time 13:05 Rev Time 0.00
Received By btrobaug Date 2007-06-22 Time 12:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-30 Cont ID  
Sent By btrobaug Date 2007-04-30 Time 16:40 Rev Time 1.00
Received By btrobaug Date 2007-04-30 Time 13:28 Sent To  
Notes
2007-04-30 16:40:12 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE PROVIDE SPECIFICATIONS FOR THE "APC UPS"
 EQUIPMENT INDICATING THE LISTING OF OF SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-06-28 Cont ID  
Sent By mawillia Date 2007-06-28 Time 16:15 Rev Time 0.00
Received By mawillia Date 2007-06-28 Time 15:50 Sent To  
Notes
2007-06-28 16:15:35****UNSAT*****
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEET M-3 STAMPED, INITIALED, AND
 DATED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-10 Cont ID  
Sent By mawillia Date 2007-05-10 Time 16:21 Rev Time 0.00
Received By mawillia Date 2007-05-10 Time 13:27 Sent To  
Notes
2007-05-10 16:21:32*****UNSAT*****
  
  
 1.ON SHEET A1, UNDER LIFE SAFETY NOTE, CHANGE WORDING
 OF "EPGRADES" TO "UPGRADES" .
  
 2.ON SHEET A1, CHANGE WORDING OF "GENARAL" TO
 "GENERAL" .
  
 3.ON SHEET A1, GENERAL NOTES SECTION, NOTE #10 REFERS
 TO 18.3.3;BE ADVISED THAT CHAPTER 18 OF NFPA 101 -
 2003 EDITION IS FOR NEW HEALTH CARE OCCUPANCIES NOT
 EXISTING BUSINESS OCCUPANCIES AS STATED UNDER THE LIFE
 SAFETY INFORMATION.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 5.THE DEMOLITION OF OLD AND/OR THE STOCKING OF NEW
 BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE OR
 HINDER EGRESS FROM THE FLOOR OR WITHIN THE BUILDING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
2007-05-10 13:33:53*****

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-28 Cont ID  
Sent By adarroug Date 2007-06-19 Time 09:18 Rev Time 0.00
Received By mawillia Date 2007-06-19 Time 09:17 Sent To  
Notes
2007-06-19 09:18:11TO "BOB"#16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-10 Cont ID  
Sent By mawillia Date 2007-05-10 Time 13:27 Rev Time 0.00
Received By mawillia Date 2007-04-27 Time 08:49 Sent To  
Notes
2007-04-27 08:54:29TO "BOB"#4

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-06-19 Cont ID  
Sent By tgordon Date 2007-06-19 Time 11:02 Rev Time 0.25
Received By tgordon Date 2007-06-19 Time 11:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-01 Cont ID  
Sent By tgordon Date 2007-05-01 Time 11:29 Rev Time 0.35
Received By tgordon Date 2007-05-01 Time 11:29 Sent To  
Notes
2007-05-01 11:44:39*** DENIED ***
 1) MECHANICAL PLANS ARE OK WITH THE EXCEPTION OF THE
 COLD WATER PIPING FOR THE HUMIDIFIER. THIS IS POTABLE
 WATER AND WILL NEED A PLUMBING REVIEW, AND MOST LIKELY
 NEED A BACKFLOW PREVENTER, SEE 2004 FBC/P 608.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2007-06-27 Time   Rev Time 0.00
Received By jleech Date 2007-06-27 Time 07:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-10 Cont ID  
Sent By jleech Date 2007-05-10 Time 07:38 Rev Time 0.00
Received By jleech Date 2007-05-10 Time 07:34 Sent To  
Notes
2007-05-21 08:32:34LIST MANUFACTURE AND MODEL NUMBER OF CHECK VALVE TO BE
 USED. MUST BE RATED FOR HIGH HAZARD.
2007-05-10 07:43:53DENIED;
 POTABLE WATER SUPPLY MUST BE PROTECTED FROM BACK FLOW,
 SEE FBC-2004 PLUMBING SECTION 608.3. SHOW ON PLANS TYPE
 OF PROTECTION TO BE USED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695