Plan Review Details - Permit 07040934
Plan Review Stops For Permit 07040934
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-07-17 Cont ID  
Sent By lmartine Date 2008-07-17 Time 09:29 Rev Time 0.00
Received By lmartine Date 2008-07-17 Time 09:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-07-11 Cont ID  
Sent By lmartine Date 2008-07-11 Time 14:19 Rev Time 0.00
Received By lmartine Date 2008-07-11 Time 14:19 Sent To  
Notes
2008-07-11 14:50:51BUILDING REVIEW COMMENTS
  
  
  
  
 NEW PLAN PROVIDED INDICATES 25 FIXED SEATS, PLEASE
 IDENTIFY (2) ACCESSIBLE SEATS PER SECTION 11-5.1, 2004
 FBC.
  
 REVSION SHALL BE REVIEWED AND STAMPED BY THE PALM BEACH
 COUNTY IMPACT FEE OFFICE, SUBMIT COPY OFRECIEPT .
  
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-05 Cont ID  
Sent By lmartine Date 2008-06-05 Time 13:58 Rev Time 0.00
Received By lmartine Date 2008-06-05 Time 13:58 Sent To M
Notes
2008-06-05 14:20:54REVISION COMMENTS
  
  
  
 PLANS SUBMITTED SHALL BE PROPERLY SIGNED AND SEALED BY
 THE DESIGNER OF RECORD.
  
 PLEASE CLARIFY IF SUITE #1 IS NOW INCLUDED WITH THIS
 PERMIT, IF SO, THE PERMIT DISCRIPTION WILL NEED TO BE
 CHANGED TO REFLECT THIS.
  
 PROVIDE SEATING PLAN FOR 28, SEE SHEETA-3FOOD
 SERVICE PLAN APPROVAL.
  
 ELECTRICAL PLANS AND PERMIT ARE REQUIRED FOR NEW WORK
 IN SUITE 1.
  
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-05-25 Cont ID  
Sent By lmartine Date 2007-05-25 Time 10:24 Rev Time 0.00
Received By lmartine Date 2007-05-25 Time 10:24 Sent To  
Notes
2007-05-25 11:06:44GAVE PLANS TO MIKE WENNERGREN.
2007-05-25 11:04:58SHALL COMPLY WITH ELECTRICAL REVIEWER'S REQUEST FOR
 ENERGY EFFICIENCY CALCULATIONS.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-07-16 Cont ID  
Sent By dpalmer Date 2008-07-16 Time 13:05 Rev Time 0.00
Received By dpalmer Date 2008-07-16 Time 13:05 Sent To  
Notes
2008-07-16 13:05:50PLANS IN LUIS M OFFICE

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-07-08 Cont ID  
Sent By dpalmer Date 2008-07-08 Time 15:17 Rev Time 0.00
Received By dpalmer Date 2008-07-08 Time 15:17 Sent To  
Notes
2008-07-08 15:17:35** DENIEDREVISIONS **
  
 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE
 CALCULATIONS WHICH ARE SHOWN ON PLANS DO NOT MATCH WITH
 PLANS.
 PLEASE SEE THE FIXTURE LEGEND NEEDS TO BE COMPLETED.
 SOME EXAMPLES OF THIS WOULD BE THE TRACK LIGHTING WHICH
 IS MISSING FROM THE FIXTURE LEGEND.THIS IS ONE
 EXAMPLE OF FIXTURES ON PLANS NOT ON LEGEND AND IN
 CALCULATIONS.
 PLANS INDICATE A 60W FLUORESCENT FIXTURE/BULB. PLEASE
 VERIFY.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED AS METHOD
 *A* MAY NOT BE SUED. PLEASE SEE 13-101.1.0. HOW CAN
 METHOD *A* BE USED?
 PLEASE SEE 13-400.3.B, 13-400.3.A AND 13-400.3.C. THE
 VERSIONS OF CALCULATIONS SUBMITTED AS 3.0 MAY NOT BE
 USED. THE CURRENT VERSION FOR PERMIT APPLICATIONS IS
 2.5.
 PLEASE KNOW IN ANY CASE THE LIGHTING AS SHOWN IN THE
 INPUT DATA REPORT DOES NOT COORDINATE WITH PLANS.
 PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE BE SURE TO SEE THAT ALL FIXTURE WATTAGES ARE
 USED AND NOT BULB WATTAGE. PLEASE REVISE THE
 CALCULATIONS AND BE SURE TO SEE THE SPECIFIC
 REQUIREMENTS OF TRACK LIGHTING.
  
 2) NOTE: PLEASE VERIFY NEW TENANT SPACE WITH TWO
 SEPARATE METERS AND MAINS.
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
 NEC
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-07-08 Cont ID  
Sent By dpalmer Date 2008-07-08 Time 14:57 Rev Time 0.00
Received By dpalmer Date 2008-07-08 Time 14:57 Sent To  
Notes
2008-07-08 14:58:09REVISED ENERGY CALCULATIONS

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-09-07 Cont ID  
Sent By dpalmer Date 2007-09-07 Time 07:25 Rev Time 0.00
Received By dpalmer Date 2007-09-07 Time 07:18 Sent To PC
Notes
2007-09-07 07:27:09*** REVISION ON HOLD WAITING FOR LETTER FROM ENGINEER.
 SPOKE TO OWNER, HE WILL BRING IN OR MAIL.
 NEED TO REVIEW LETTER BEFORE RELEASING PLANS.
  
 ** ELEC REV WAS OK AND HAS ALREADY BEEN STAMPED PENDING
 LETTER.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-08-09 Cont ID  
Sent By dpalmer Date 2007-08-09 Time 13:36 Rev Time 0.00
Received By dpalmer Date 2007-08-09 Time 13:34 Sent To PC
Notes
2007-08-09 13:37:08** DENIED **
  
  
 1) NOTE:PLEASE SEE THAT PLANS ARE REQUIRED TO BE
 REVISED BY THE ENGINEER OF RECORD.
 FS 471.023, 471, FAC 61G15-23.002
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-19 Cont ID  
Sent By dpalmer Date 2007-06-19 Time 07:18 Rev Time 0.00
Received By dpalmer Date 2007-06-18 Time 16:08 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-07 Cont ID  
Sent By dpalmer Date 2007-05-07 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2007-05-07 Time 13:30 Sent To  
Notes
2007-05-07 14:48:03PLANS ROUTED BACK TO LUIS M.
2007-05-07 14:47:26 
 ** UNSAT **
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS UNDER THE
 2004 FBC W/2006 REVISIONS. PER 13-415.1.AB.1.1,
 13-415.2
 PLEASE SEE THE 2006 REVISIONS FOR CHANGES IN CHAPTER 13
 FROM THE 2004 FBC W/2005 REVISIONS.
  
 3) NOTE: PLEASE SEE 422.13 AS THE LOAD FOR WATER HEATER
 IS TO BE SHOWN AND FIGURED AT 125%. (CHANGED FROM
 PREVIOUS CODE).
  
 4) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK HAS NOW DECREASED TO ABOUT HALF AS PREVIOUSLY
 SUBMITTED?? PLEASE VERIFY AS VALUE MUST INCLUDE ALL
 LABOR AND MATERIALS EVEN IF MATERIALS OR ANY
 PERMANENTLY INSTALLED EQUIPMENT IS OWNER SUPPLIED.
 FBC 108.3
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-07-10 Cont ID  
Sent By mwennerg Date 2008-07-10 Time 11:06 Rev Time 0.00
Received By mwennerg Date 2008-07-10 Time 11:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-06-02 Cont ID  
Sent By mwennerg Date 2008-06-02 Time 13:55 Rev Time 0.00
Received By mwennerg Date 2008-06-02 Time 13:55 Sent To  
Notes
2008-06-02 13:57:17***DENIED***
  
 1) PLANS STILL REFERENCE NFPA 101, SECTION 27-3.3.1.
 PLEASE NOTE AS STATED IN LAST FIRE REVIEW THAT CHAPTER
 27 IS RESERVED IN NFPA 101, 2003 EDITION. PLEASE DELETE
 THAT INFORMATION FROM PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-05-25 Cont ID  
Sent By mwennerg Date 2007-05-25 Time 12:31 Rev Time 0.00
Received By mwennerg Date 2007-05-25 Time 12:31 Sent To  
Notes
2007-05-25 12:34:54INTERIOR FINISH CLASSIFICATION FOR WALLS AND CEILING
 SHALL COMPLY WITH NFPA 101, 2003 EDITION CHAPTER 10.
 PLEASE DELETE REFERENCE TO SEC. 27.3.3.1 AS CHAPTER 27
 IS RESERVED.

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2008-06-26 Cont ID  
Sent By mperson Date 2008-06-26 Time 16:48 Rev Time 0.00
Received By mperson Date 2008-06-26 Time 16:48 Sent To  
Notes
2008-06-26 16:49:03NOTE: NO CHANGES IN GAS.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-05-25 Cont ID  
Sent By mperson Date 2007-05-25 Time 16:17 Rev Time 0.00
Received By mperson Date 2007-05-25 Time 16:17 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 16:56 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 14:46 Sent To  
Notes
2008-06-17 16:56:48TO "COMM" BD#6

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-05-15 Cont ID  
Sent By adarroug Date 2008-05-15 Time 09:40 Rev Time 0.00
Received By adarroug Date 2008-05-15 Time 09:31 Sent To  
Notes
2008-05-15 09:40:36TO "COMM" BD#23

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-10-26 Cont ID  
Sent By shill Date 2007-10-26 Time 13:14 Rev Time 0.00
Received By shill Date 2007-10-26 Time 13:14 Sent To M
Notes
2007-10-26 13:14:36TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-21 Cont ID  
Sent By adarroug Date 2007-09-21 Time 15:08 Rev Time 0.00
Received By adarroug Date 2007-09-21 Time 15:07 Sent To M
Notes
2007-09-21 15:08:24TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 11:24 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 11:24 Sent To E
Notes
2007-09-05 11:25:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-03 Cont ID  
Sent By adarroug Date 2007-08-03 Time 11:02 Rev Time 0.00
Received By adarroug Date 2007-08-03 Time 11:02 Sent To E
Notes
2007-08-03 11:02:49TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 14:24 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 14:24 Sent To P
Notes
2007-06-12 10:24:24TO "MPERSON" DESK/ RESUB--PER "RBROWN"
2007-06-01 14:24:27WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-25 Cont ID  
Sent By mperson Date 2007-05-25 Time 16:28 Rev Time 0.00
Received By mperson Date 2007-04-27 Time 08:12 Sent To PC
Notes
2007-05-04 15:44:49 
 ROUTED TO L MARTINEZ FOR RE-STAMP BY PLAN REVIEWERS.
2007-04-27 08:12:25WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-06-23 Cont ID  
Sent By tgordon Date 2008-06-23 Time 16:04 Rev Time 1.00
Received By tgordon Date 2008-06-23 Time 16:04 Sent To  
Notes
2008-06-23 16:05:49REVISION TO MECH. PLAN M1 (COOLING LOAD CAL'S WERE
 REVISED AND FILED ON 6-5-08).

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-06-05 Cont ID  
Sent By tgordon Date 2008-06-05 Time 15:48 Rev Time 1.30
Received By tgordon Date 2008-06-05 Time 15:48 Sent To  
Notes
2008-06-05 16:01:07PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 **REVISION TO MECH. PLAN, COOLING LOAD CAL'S. AND
 E-CAL'S.**
 *** DENIED ***
  
 1) THE PLANS NEED TO BE SEALED BY THE ARCHITECT, PER
 FAC 61G1-16.003.
  
 2) ONE OF THE MECHANICAL PLANS IS A PHOTO COPY, PLEASE
 SUBMIT TWO SIGNED AND SEALED MECHANICAL PLANS.
  
 3) ELECTRICAL AND PLUMBING PLANS MAY NEED TO BE
 REVISED, PLEASE CHECK WITH THOSE REVIEWERS.
  
 ** THE REVISED ENERGY CAL'S ARE NOT REQUIRED FOR THE
 MECHANICAL REVISION, BUT MAY BE FOR OTHER TRADE
 REVIEWERS, PLEASE CHECK WITH BUILD. ELECT. AND PLUMB.
 REVIEWERS.
  
 *** REVISED COOLING LOAD CALCULATIONS WERE REVIEWED AND
 STAMPED, ONE SET WAS RETURNED WITH APPLICATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-10-31 Cont ID  
Sent By tgordon Date 2007-10-31 Time 15:53 Rev Time 0.45
Received By tgordon Date 2007-10-31 Time 15:53 Sent To  
Notes
2007-10-31 15:54:56REVISION TO MECH. PLAN, E-CAL'S. AND COOLING LOAD
 CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-09-24 Cont ID  
Sent By tgordon Date 2007-09-24 Time 09:48 Rev Time 0.40
Received By tgordon Date 2007-09-24 Time 09:48 Sent To  
Notes
2007-09-24 09:52:29PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) THE MECHANICAL PLAN NEEDS TO BE SIGNED AND SEALED BY
 THE ENGINEER, SEE F.A.C. 61G15-23.002.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-05-04 Cont ID  
Sent By tgordon Date 2007-05-04 Time 16:34 Rev Time 0.25
Received By tgordon Date 2007-05-04 Time 16:34 Sent To B
Notes
2007-05-04 16:36:12RE-STAMP.
  
 1) ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 (B) KITCHEN HOOD
 (C) FIRE SUPPRESSION
 ** SUBMIT PLANS WITH PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 3 Status N Date 2008-06-26 Cont ID  
Sent By mperson Date 2008-06-26 Time 16:47 Rev Time 0.00
Received By mperson Date 2008-06-26 Time 16:47 Sent To G
Notes
2008-06-26 16:48:11NOTE: NO CHANGES IN PLUMBING.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-06-12 Cont ID  
Sent By mperson Date 2007-06-12 Time 13:17 Rev Time 0.00
Received By mperson Date 2007-06-12 Time 13:17 Sent To E
Notes
2007-06-12 13:27:17NOTE: THE SAMPLE POINT AND DPBR WORK SHEETS WERE
 APPROVED ON THE PREVIOUS PERMIT #06080501, WHICH WILL
 REMAIN IN OUR FILES. THE 1ST ROUGH PLUMBING INSPECTION
 (PERMIT # 07010952) WAS APPROVED ON 01/25/07 WHICH
 INCLUDES THE GREASE SAMPLE POINT. UPON FUTHER REVIEW
 THE SUBMITTED PRINTS FOR THE CHANGE OF CONTRACTOR ARE A
 LIKE FOR LIKE ON THE PLUMBING.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-25 Cont ID  
Sent By mperson Date 2007-05-25 Time 15:41 Rev Time 0.00
Received By mperson Date 2007-05-25 Time 15:41 Sent To G
Notes
2007-05-25 16:12:08DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET P-1 IS INDICATING 1. DELETE GREASE
 INTERCEPTOR AND 2. ADD GREASE SAMPLE POINT. EVEN THOUGH
 THIS WAS APPROVED ON THE PRIOR PLANS. THOSE PLANS HAVE
 BEEN VOIDED DUE TO THE CHANGE IN CONTRACTOR. THESE NEW
 PLANS MUST AGAIN BE APPROVED BY THEUTILITY
 DEPARTMENT.NOTE: PER ARTICLE LLL. SEWERS AND SEWEAGE
 DISPOSAL. PLEASE CONTACT THE FOLLOWING.
  
 ENVIRONMENTAL COMPLIANCE MANAGER:
 LYNN MASSON
 PHONE= (561) 822-2271
 FAX= (561) 822-2279
 E-MAIL= [email protected]
  
 2. THE TWO COPIES OF PLANS MUST ALSO BE REVIEWED,
 APPROVED (STAMPED) AND THE TWO PAGE WORK SHEETS NEED TO
 BE COMPLETED AND ATTACHED TO THE PLANS BY DPBR HOTEL
 AND RESTAURANT DIVISION PER FBC-2004 CHAPTER 1, SECTION
 102.2.1.
  
 3. SHEET P-1 SANITARY RISER DIAGRAM: PLEASE ADD THE
 GREASE SAMPLE POINT TO THE RESUBMITTED SANITARY
 ISOMETRIC RISER DIAGRAM.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 1 Status P Date 2008-05-30 Cont ID  
Sent By astelly Date 2008-05-30 Time 17:37 Rev Time 0.00
Received By astelly Date 2008-05-30 Time 17:37 Sent To  
Notes
***NONE***